6.8.3
Implementation of the Stop Category 0
Bringing the motor to a standstill by immediately switching off the amplifier power supply (
STOP-
MODE & ACTFAULT parameters set to 1
). The switching sequence is precisely determined by
this circuit in order to avoid undesirable fault messages and servo amplifier failures.
It is not possible to achieve a Category 0 shut-down with the servo amplifier alone, since hard-wired
electromechanical components are compulsory for this type of disconnection.
A brake that is built into the motor must have an additional electromechanical control circuit, as well
as the control through the AX2040/2070, in order to meet Category 0.
Usually a brake in a servo motor only has the function of a holding brake. To ensure an emergency
stop function, the braking torque that is required must be checked. If the holding brake fulfills the
dynamic requirements, it must be taken into acount that this application will cause increased wear.
Circuit suggestion
(with EMERGENCY STOP Category 0, control function with contactor relays)
28
AX2040/2070 Product Manual
Technical description
06/2007
BECKHOFF
AX2040/2070
Содержание AX2040
Страница 35: ...7 4 Dimensions AX2040 2070 Product Manual 35 BECKHOFF 06 2007 Mechanical Installation...
Страница 44: ...8 6 Pin assignments 44 AX2040 2070 Product Manual Electrical Installation 06 2007 BECKHOFF...
Страница 108: ...This page has been deliberately left blank 108 AX2040 2070 Product Manual Expansion Cards 06 2007 BECKHOFF...