38
6-847718-00 Rev. B00
Wiring (Cont.)
Inst
allation
Procedures
Building Automation System (Cont.)
ADI3 = device firmware version.
ADI4 = number of switched inputs
indicating an alarm condition.
ADI5 = number of remote alarm modules
indicating an alarm condition.
If you are planning to use the Metasys®
building automation system with the
TotalAlert 2, request the following file from
BeaconMedaes technical support:
Filename: TotalAlert2v1.ddl
************************************************
**********************
* BeaconMedæs TotalAlert2® Medical Gas Alarm
version 1.00
* Point Type Max Allowed
* ---------------------- -----------
* AD - Analog Data 32 (ADI & ADF read-only)
* BI - Binary Input
* Never map output points in a CS model and as
discrete objects.
* The N, N or Y, Y after the point label means:
* 1st one - Can be overridden
* 2nd one - Can be adjusted
************************************************
**********************
@MODEL+
CSMODEL "TotalAlert2", "VND"
BITITLE "Inputs"
ADTITLE "Alarm Summary"
CSBI "BI1" ,Y,N,"INPUT_A1","Normal","Alarm"
CSBI "BI2" ,Y,N,"INPUT_A2","Normal","Alarm"
CSBI "BI3" ,Y,N,"INPUT_A3","Normal","Alarm"
CSBI "BI4" ,Y,N,"INPUT_A4","Normal","Alarm"
CSBI "BI5" ,Y,N,"INPUT_A5","Normal","Alarm"
CSBI "BI6" ,Y,N,"INPUT_A6","Normal","Alarm"
CSBI "BI7" ,Y,N,"INPUT_A7","Normal","Alarm"
CSBI "BI8" ,Y,N,"INPUT_A8","Normal","Alarm"
CSBI "BI9" ,Y,N,"INPUT_A9","Normal","Alarm"
CSBI "BI10" ,Y,N,"INPUT_A10","Normal","Alarm"
CSBI "BI11" ,Y,N,"INPUT_A11","Normal","Alarm"
CSBI "BI12" ,Y,N,"INPUT_A12","Normal","Alarm"
CSBI "BI13" ,Y,N,"INPUT_A13","Normal","Alarm"
CSBI "BI14" ,Y,N,"INPUT_A14","Normal","Alarm"
CSBI "BI15" ,Y,N,"INPUT_A15","Normal","Alarm"
CSBI "BI16" ,Y,N,"INPUT_A16","Normal","Alarm"
CSBI "BI17" ,Y,N,"INPUT_A17","Normal","Alarm"
CSBI "BI18" ,Y,N,"INPUT_A18","Normal","Alarm"
CSBI "BI19" ,Y,N,"INPUT_A19","Normal","Alarm"
CSBI "BI20" ,Y,N,"INPUT_A20","Normal","Alarm"
CSBI "BI21" ,Y,N,"INPUT_A21","Normal","Alarm"
CSBI "BI22" ,Y,N,"INPUT_A22","Normal","Alarm"
CSBI "BI23" ,Y,N,"INPUT_A23","Normal","Alarm"
CSBI "BI24" ,Y,N,"INPUT_A24","Normal","Alarm"
CSBI "BI25" ,Y,N,"INPUT_A25","Normal","Alarm"
CSBI "BI26" ,Y,N,"INPUT_A26","Normal","Alarm"
CSBI "BI27" ,Y,N,"INPUT_A27","Normal","Alarm"
CSBI "BI28" ,Y,N,"INPUT_A28","Normal","Alarm"
CSBI "BI29" ,Y,N,"INPUT_A29","Normal","Alarm"
CSBI "BI30" ,Y,N,"INPUT_A30","Normal","Alarm"
CSBI "BI31" ,Y,N,"INPUT_A31","Normal","Alarm"
CSBI "BI32" ,Y,N,"INPUT_A32","Normal","Alarm"
CSBI "BI33" ,Y,N,"INPUT_B1","Normal","Alarm"
CSBI "BI34" ,Y,N,"INPUT_B2","Normal","Alarm"
CSBI "BI35" ,Y,N,"INPUT_B3","Normal","Alarm"
CSBI "BI36" ,Y,N,"INPUT_B4","Normal","Alarm"
CSBI "BI37" ,Y,N,"INPUT_B5","Normal","Alarm"
CSBI "BI38" ,Y,N,"INPUT_B6","Normal","Alarm"
CSBI "BI39" ,Y,N,"INPUT_B7","Normal","Alarm"
CSBI "BI40" ,Y,N,"INPUT_B8","Normal","Alarm"
CSBI "BI41" ,Y,N,"INPUT_B9","Normal","Alarm"
CSBI "BI42" ,Y,N,"INPUT_B10","Normal","Alarm"
CSBI "BI43" ,Y,N,"INPUT_B11","Normal","Alarm"
CSBI "BI44" ,Y,N,"INPUT_B12","Normal","Alarm"
CSBI "BI45" ,Y,N,"INPUT_B13","Normal","Alarm"
CSBI "BI46" ,Y,N,"INPUT_B14","Normal","Alarm"
CSBI "BI47" ,Y,N,"INPUT_B15","Normal","Alarm"
CSBI "BI48" ,Y,N,"INPUT_B16","Normal","Alarm"
CSBI "BI49" ,Y,N,"INPUT_B17","Normal","Alarm"
CSBI "BI50" ,Y,N,"INPUT_B18","Normal","Alarm"
CSBI "BI51" ,Y,N,"INPUT_B19","Normal","Alarm"
CSBI "BI52" ,Y,N,"INPUT_B20","Normal","Alarm"
CSBI "BI53" ,Y,N,"INPUT_B21","Normal","Alarm"
CSBI "BI54" ,Y,N,"INPUT_B22","Normal","Alarm"
CSBI "BI55" ,Y,N,"INPUT_B23","Normal","Alarm"
CSBI "BI56" ,Y,N,"INPUT_B24","Normal","Alarm"
CSBI "BI57" ,Y,N,"INPUT_B25","Normal","Alarm"
CSBI "BI58" ,Y,N,"INPUT_B26","Normal","Alarm"
CSBI "BI59" ,Y,N,"INPUT_B27","Normal","Alarm"
CSBI "BI60" ,Y,N,"INPUT_B28","Normal","Alarm"
CSBI "BI61" ,Y,N,"INPUT_B29","Normal","Alarm"
CSBI "BI62" ,Y,N,"INPUT_B30","Normal","Alarm"
CSBI "BI63" ,Y,N,"INPUT_B31","Normal","Alarm"
CSBI "BI64" ,Y,N,"INPUT_B32","Normal","Alarm"
CSBI "BI65" ,Y,N,"ANY_ALARM","No_Alarms","Alarm"
CSBI "BI66" ,Y,N,"AUD_ALM","Off","On"
CSAD "ADI1" ,N,Y,"Serial_1",""
CSAD "ADI2" ,N,Y,"Serial_2",""
CSAD "ADI3" ,N,Y,"VERSION",""
CSAD "ADI4" ,N,Y,"NUMBER_LOCAL_ALARMS",""
CSAD "ADI5" ,N,Y,"NUMBER_REMOTE_ALARMS",""
CSAI "AI1",Y,N,"DDM1",""
CSAI "AI2",Y,N,"DDM2",""
CSAI "AI3",Y,N,"DDM3",""
CSAI "AI4",Y,N,"DDM4",""
CSAI "AI5",Y,N,"DDM5",""
CSAI "AI6",Y,N,"DDM6",""
CSAI "AI7",Y,N,"DDM7",""
CSAI "AI8",Y,N,"DDM8",""
Содержание TotalAlert 2
Страница 1: ...Installation Operation and Maintenance Instructions 6 847718 00 Rev B00...
Страница 2: ......
Страница 22: ...20 6 847718 00 Rev B00...
Страница 97: ...95 6 847718 00 Rev B00 Figure 86 Clear Network Accepted Operation...
Страница 99: ...97 6 847718 00 Rev B00 Operation Figure 89 Event Log Cleared...
Страница 101: ...99 6 847718 00 Rev B00 Operation Figure 91 Transfer Setup Figure 92 Transfer Setup Complete...
Страница 129: ...127 6 847718 00 Rev B00 Troubleshooting Guide Troubleshooting...
Страница 130: ...128 6 847718 00 Rev B00...
Страница 139: ...137 6 847718 00 Rev B00 Replacement Parts Notes...
Страница 143: ......
Страница 144: ...2007 BeaconMed s All rights reserved 6 847718 00 Rev B00...