![Baxi LINA 3 COMFORT HT Скачать руководство пользователя страница 79](http://html1.mh-extra.com/html/baxi/lina-3-comfort-ht/lina-3-comfort-ht_instruction-manual_2711793079.webp)
79
926.420.3 - EN
INSTRUCTIONS FOR FITTERS
PARAMETER SETTINGS
•
“K REG”
Adjustment constant (0.5...9.0) of the temperature of the heating system delivery water (factory setting =
3 - See Chart 1). Set value with
+/-
. A high value generates a higher delivery temperature in the heating system.
By setting a correct
K REG
adjustment constant, the ambient temperature remains at the set value regardless of the
changes in external temperature.
•
“BUILD”
Adjustment parameter for the size of the building (1..10 - factory setting 5). Set value with
+/-
. An
elevated value is associated with a building / heating system with elevated heat inertia, vice-versa, a low value is
associated with small rooms or systems with low heat inertia (thermoconvectors).
•
“KORR”
Defines the effect of the ambient temperature on the setpoint. Values range from 0 to 20. Increasing this
value increases the effect of ambient temperature.
•
“AMBON”
Enables/disables the ambient probe of the AVS 77 climate controller (factory setting = 1). 1 means the
ambient probe is enabled while 0 means it is disabled. With the function enabled, the temperature control of the
rooms depends on the selected boiler delivery temperature (“CH SL”). Press
+/-
to modify this value.
•
“SDR”
Ambient hysteresis. Can be set from 0.5 °C to 4 °C with
+/-
.
•
“HW PR”
Enables the DHW programmer (0-1-2). Factory setting = 1.
• 0: Disabled
• 1: Always enabled
• 2: Enabled with weekly DHW programme (“HW PR” see section 3.7)
•
“OFFTR”
Offset of the ambient probe measurement on the display (from -3°C to +3°C) – factory setting =0.
•
“OFFVI”
Climate controller operating mode after offset of the temperature measured by the ambient probe (parame-
ter OFFTR) – factory setting =0.
0: Offset of the value and adjustment of the temperature to the modified value
1: Only offset of the value, the temperature is adjusted to the value prior to modification.
•
“L FCT”
If set to 1, the anti-legionellosis function is enabled.
•
“LTIME”
Time the function is maintained after reaching
“LTEMP”
•
“LTEMP”
Maximum temperature for the anti-legionellosis function (60°C).
•
“COOL”
Enable/Disable control of ambient temperature in summer (factory setting=0). Set this parameter to 1 to
enable the function and add two new boiler operating modes, as per section 3.2:
SUMMER - OFF - WINTER - HEATING ONLY -
COOL - COOL
To enable the function press button repeatedly until the display is shows to the right of the time.
This function is used to enable the climate controller to command one or more external conditioning devices (e.g.:
air-conditioners) in summer. The boiler relay board therefore enables the external conditioning system when ambient
temperature exceeds the temperature value set on the climate controller. During an operating request in this mode,
flashes on the display. For relay board connections, see the SERVICE instructions
.
•
“LMU34”
If set to 1, enables control of the software version of the LMU34 electronic board
•
“STBY”
Setting the STANDBY mode (see OFF/SUMMER operating modes in section 3.2) on systems with two or
more zones for the zone controlled by the “TA” ambient thermostat. Factory setting = 0.
0: No modification
1: The two temperature set-points “
CH2SR
” (ambient temperature setpoint for the heating circuit of the n. zones
controlled by the “TA”) and “
CH2SF
” (water temperature setpoint for the heating circuit of the n. zones controlled
by the “TA”) are “forced” to their minimum values of 5°C and 20°C respectively. The boiler pump operates con-
stantly provided the “TA” continues to make a heat demand.
•
“RMOD”
Enables/Disables the room temperature setpoint modulation. Factory setting = 1.
0: Disabled
1: Enabled ¯
•
CASE 1:
without outdoor sensor.
The burner modulates both with the flow temperature setpoint and the room temperature setpoint. The closed the tem-
perature value is to the room temperature setpoint, the more the calculated flow temperature setpoint decreases.
For other cases see the table below.
Содержание LINA 3 COMFORT HT
Страница 42: ...42 926 420 3 IT ISTRUZIONI DESTINATE ALL INSTALLATORE HT 1 120 HT 1 240 HT 1 280 CG_2056 0901_1502...
Страница 128: ...128 926 420 3 RU BAXI BAXI 2009 142 EC 92 42 EEC 2004 108 EC 2006 95 EC BAXI S p A CSQ ISO14001 ISO9001 OHSAS 18001...
Страница 131: ...131 926 420 3 RU 3 BAXI CLOW AVS 77 5 12 3 2 3 3 1 0702_2404 4 4 0702_2405 3 2...
Страница 133: ...133 926 420 3 RU 3 4 1 3 1 1 t 1 HW SP 3 4 1 IP PROG 1 3 5 PROG OK OK Day 1 7 IP 3 6 1 4 4 3 6...
Страница 138: ...138 926 420 3 RU 10 10 45 90 02 2 47 47 DD 02 2 45 1 4 4 2 PARTY MAN 60 4 4 1 0703_0507 60...
Страница 140: ...140 926 420 3 RU 8 15 20 5 30 ERROR 9 2 ERROR 2 ERROR 5 AVS 77 155 0703_0904 RESET 4 4 0705_0601 CG_1922 RESET...
Страница 147: ...147 926 420 3 RU 15 4 15 5 0704_1507 L max 15 m 0706_2902 0706_2903 L max 14 m L max 15 m 0706_2904 1 L1 L2 max 80 m 15...
Страница 150: ...150 926 420 3 RU 11 1 a b 11 2 2 11 3 1 2 4 17 17 2 0705_1602 M2 18 3 4 12 0605_1604 M2...
Страница 153: ...153 926 420 3 RU 20 14 AVS 77 16 14 AVS 77 0709_0701 CG_1933 1 AVS 77 1 1 2 3 N...
Страница 158: ...158 926 420 3 RU OK 9 1 110 OK 9 1 90 OK 9 1 0 5 3 5 30 0 5 24 10 24 3 0 1 1 0 23...
Страница 159: ...159 926 420 3 RU 24 25 2 2 18 020429_0300 21 OF 555 0 OF 555 0 1 15 15 OF 555 0 0 25 1 17 CG_2190 0911_1201...
Страница 164: ...164 926 420 3 RU 1 setpoint setpoint setpoint setpoint AMBON RMOD AMBON RMOD T AMBON RMOD EXT T 0 0 1 1 1 1 0...
Страница 167: ...167 926 420 3 RU 0901_1506 CG_1934B 32 N R G V B V HT 280 HT 330 NTC RESET NTC...
Страница 168: ...168 926 420 3 RU 0901_1503 CG_2056 HT 1 120 HT 1 240 HT 1 280 N R G V B V RESET NTC...
Страница 340: ...340 926 420 3 EL GR BAXI CE 2009 142 92 42 2004 108 2006 95 S p A CSQ ISO9001 ISO14001 OHSAS18001 BAXIS p A...
Страница 344: ...344 926 420 3 EL GR 4 2 3 1 2 COOL 31 COOL 31 3 2 COMFORT 3 6 ff 3 3 25 25 50 50 75 75 100...
Страница 345: ...345 926 420 3 EL GR 3 4 1 3 1 1 C tAMB 1 C HW SP C 3 4 1 IP PROG 1 OK OK Day 1 7 3 5 PROG 3 6 1 4 4 3 6...
Страница 350: ...350 926 420 3 EL GR 10 10 45 90 HH 02 2 47 47 DD 02 2 45 1 0703_0507 60 4 4 2 PARTY MAN MM 60 4 4 1 AMB...
Страница 352: ...352 926 420 3 EL GR 8 5 C 30 C ERROR E 9 2 ERROR 2 reset RESET AVS 77 0703_0904 155E RESET 4 4 0705_0601 CG_1922 RESET...
Страница 362: ...362 926 420 3 EL GR E 11 1 a b 11 2 M2 3 1 2 4 C 17 17 2 0705_1602 M2 18 3 4 12 0605_1604 M2...
Страница 365: ...365 926 420 3 EL GR 20 14 0709_0701 CG_1933 1 AVS 77 AVS 77 16 14 AVS 77 1 1 2 3 N...
Страница 370: ...370 926 420 3 EL GR OK 9 1 NTC 110 C OK 9 1 90 C OK 9 1 0 5 bar 3 5 C 30 C 24 10 24 3 bar 0 23...
Страница 371: ...371 926 420 3 EL GR 24 25 O2 CO2 CO 18 020429_0300 21 OF 555 0 OF 555 0 1 15 OF 555 0 0 25 1 17 CG_2190 0911_1201...
Страница 376: ...376 926 420 3 EL GR AMBON RMOD EXT T AMBON RMOD EXT T 0 0 COMFORT 1 1 1 1 0...
Страница 379: ...379 926 420 3 EL GR 0901_1506 CG_1934B 32 C M N R G V B G HT 240 HT 280 HT 330 NTC NTC RESET NTC FASTON...
Страница 380: ...380 926 420 3 EL GR 0901_1503 CG_2056 HT 1 120 HT 1 240 HT 1 280 BOILER C M N R G V B G NTC NTC RESET FASTON...
Страница 382: ...382 926 420 3 EL GR...
Страница 383: ...383 926 420 3 EL GR...