926.420.3 - EN
INSTRUCTIONS FOR FITTERS
21. PROGRAMMING BOARD PARAMETERS USING THE AVS 77 CLIMATE CONTROLLER
0703_0910
To set the boiler parameters, proceed as follows:
• press and hold down
IP
for at least three seconds;
• press and hold down
and then press
(see figure 15).
When the function is enabled,
“OF 725”
appears on the display
followed by the software version of the LMU34 board.
To modify boiler parameters, proceed as follows:
• Press
+/-
and
together and hold down for 3 seconds;
(this accesses the list of parameters, the display shows
OF
504
alternating with the parameter itself).
• press buttons
+/-
to scroll the parameters (see table be-
low);
• press buttons
+/-
to modify individual parameters;
• press
OK
to confirm the modified parameter and return to the
list of parameters;
• press
IP
to exit
Figure 15
* These parameters differ depending on the model of boiler installed. See the Service instructions for a complete
list of parameters and settings.
Summary of parameters that can be adjusted with the AVS 77 climate controller
Parameters
Description of parameters
Default
504
Maximum heating delivery temperature (°C)
80
516
Automatic summer-winter switching
30
532
Gradient of
“kt”
heating curve
15
534
Ambient temperature offset
0
536
Maximum fan speed (rpm) in heating mode (max. power in heating mode)
*
541
Max. PWM (%) in heating mode
*
544
Pump post-circulation time (s)
180
545
Minimum burner pause time (s) in heating phase
180
555.0
Chimney sweep function:
1:
enabled
0:
disabled
0
555.1
Anti-legionellosis function:
1:
enabled
0:
disabled
1
555.2
Hydraulic device setting
0
555.3
NOT USED
-
555.4
AVS 77
climate controller
1:
delivery temperature controlled by AVS 77, heat demand is managed by the boiler AT
0:
delivery temperature and heat demand are managed independently by AVS 77 or TA.
0
555.5...555.7
NOT USED
0
608
PWM (%) setting: ignition power
*
609
PWM (%) setting: minimum power
*
610
PWM (%) setting: maximum power
*
611
Rpm setting: ignition power
*
612
Rpm setting: minimum power
*
613
Rpm setting: maximum power
*
614
OT input setting (AVS 77)
0
641
Post-ventilation time setting (s)
10
677
Boiler power adjustment
max. (100%) - min. (0%) during calibration
0
651
Tipologia caldaia (impostazione circuito idraulico)
1
: appliance for heating only
2
: instantaneous appliance
4
: with preheating (section 3.7.1)
*
Содержание LINA 3 COMFORT HT
Страница 42: ...42 926 420 3 IT ISTRUZIONI DESTINATE ALL INSTALLATORE HT 1 120 HT 1 240 HT 1 280 CG_2056 0901_1502...
Страница 128: ...128 926 420 3 RU BAXI BAXI 2009 142 EC 92 42 EEC 2004 108 EC 2006 95 EC BAXI S p A CSQ ISO14001 ISO9001 OHSAS 18001...
Страница 131: ...131 926 420 3 RU 3 BAXI CLOW AVS 77 5 12 3 2 3 3 1 0702_2404 4 4 0702_2405 3 2...
Страница 133: ...133 926 420 3 RU 3 4 1 3 1 1 t 1 HW SP 3 4 1 IP PROG 1 3 5 PROG OK OK Day 1 7 IP 3 6 1 4 4 3 6...
Страница 138: ...138 926 420 3 RU 10 10 45 90 02 2 47 47 DD 02 2 45 1 4 4 2 PARTY MAN 60 4 4 1 0703_0507 60...
Страница 140: ...140 926 420 3 RU 8 15 20 5 30 ERROR 9 2 ERROR 2 ERROR 5 AVS 77 155 0703_0904 RESET 4 4 0705_0601 CG_1922 RESET...
Страница 147: ...147 926 420 3 RU 15 4 15 5 0704_1507 L max 15 m 0706_2902 0706_2903 L max 14 m L max 15 m 0706_2904 1 L1 L2 max 80 m 15...
Страница 150: ...150 926 420 3 RU 11 1 a b 11 2 2 11 3 1 2 4 17 17 2 0705_1602 M2 18 3 4 12 0605_1604 M2...
Страница 153: ...153 926 420 3 RU 20 14 AVS 77 16 14 AVS 77 0709_0701 CG_1933 1 AVS 77 1 1 2 3 N...
Страница 158: ...158 926 420 3 RU OK 9 1 110 OK 9 1 90 OK 9 1 0 5 3 5 30 0 5 24 10 24 3 0 1 1 0 23...
Страница 159: ...159 926 420 3 RU 24 25 2 2 18 020429_0300 21 OF 555 0 OF 555 0 1 15 15 OF 555 0 0 25 1 17 CG_2190 0911_1201...
Страница 164: ...164 926 420 3 RU 1 setpoint setpoint setpoint setpoint AMBON RMOD AMBON RMOD T AMBON RMOD EXT T 0 0 1 1 1 1 0...
Страница 167: ...167 926 420 3 RU 0901_1506 CG_1934B 32 N R G V B V HT 280 HT 330 NTC RESET NTC...
Страница 168: ...168 926 420 3 RU 0901_1503 CG_2056 HT 1 120 HT 1 240 HT 1 280 N R G V B V RESET NTC...
Страница 340: ...340 926 420 3 EL GR BAXI CE 2009 142 92 42 2004 108 2006 95 S p A CSQ ISO9001 ISO14001 OHSAS18001 BAXIS p A...
Страница 344: ...344 926 420 3 EL GR 4 2 3 1 2 COOL 31 COOL 31 3 2 COMFORT 3 6 ff 3 3 25 25 50 50 75 75 100...
Страница 345: ...345 926 420 3 EL GR 3 4 1 3 1 1 C tAMB 1 C HW SP C 3 4 1 IP PROG 1 OK OK Day 1 7 3 5 PROG 3 6 1 4 4 3 6...
Страница 350: ...350 926 420 3 EL GR 10 10 45 90 HH 02 2 47 47 DD 02 2 45 1 0703_0507 60 4 4 2 PARTY MAN MM 60 4 4 1 AMB...
Страница 352: ...352 926 420 3 EL GR 8 5 C 30 C ERROR E 9 2 ERROR 2 reset RESET AVS 77 0703_0904 155E RESET 4 4 0705_0601 CG_1922 RESET...
Страница 362: ...362 926 420 3 EL GR E 11 1 a b 11 2 M2 3 1 2 4 C 17 17 2 0705_1602 M2 18 3 4 12 0605_1604 M2...
Страница 365: ...365 926 420 3 EL GR 20 14 0709_0701 CG_1933 1 AVS 77 AVS 77 16 14 AVS 77 1 1 2 3 N...
Страница 370: ...370 926 420 3 EL GR OK 9 1 NTC 110 C OK 9 1 90 C OK 9 1 0 5 bar 3 5 C 30 C 24 10 24 3 bar 0 23...
Страница 371: ...371 926 420 3 EL GR 24 25 O2 CO2 CO 18 020429_0300 21 OF 555 0 OF 555 0 1 15 OF 555 0 0 25 1 17 CG_2190 0911_1201...
Страница 376: ...376 926 420 3 EL GR AMBON RMOD EXT T AMBON RMOD EXT T 0 0 COMFORT 1 1 1 1 0...
Страница 379: ...379 926 420 3 EL GR 0901_1506 CG_1934B 32 C M N R G V B G HT 240 HT 280 HT 330 NTC NTC RESET NTC FASTON...
Страница 380: ...380 926 420 3 EL GR 0901_1503 CG_2056 HT 1 120 HT 1 240 HT 1 280 BOILER C M N R G V B G NTC NTC RESET FASTON...
Страница 382: ...382 926 420 3 EL GR...
Страница 383: ...383 926 420 3 EL GR...