77
Manual Single Power Unit BUM64S/A/F
Document no.: 5.01056.03
11
S
ETTING
OUT
OF
OPERATION
,
STORAGE
In this chapter, we describe how the BUM64S/A/F is set out of operation and the storage
after.
11.1 Demands on the personnel
The personnel that you order to set the appliance out of operation, must have the required
knowledge and instructions to carry out these jobs properly. The personnel is to be cho-
sen in a way that the safety information found on the appliance, its parts and its connec-
tions are understood and observed.
11.2 Safety regulations
The sense of the safety regulations during commissioning must be applied to the set-out-
of-operation procedure as well.
DANGER
The following
will occur
,
if you do not observe this danger information:
m
serious personal injury
m
death
The hazard is:
Electricity.
Make sure that all electrical connections are switched powerless and are secured against un-
authorized reactivation.
The modules inside the appliance (e.g. capacitors) can hold dangerous charges! The capac-
itors used inside the appliance will take at least
10 min
to become discharged by themselves.
Before working at electrical connections check with suitable test instruments that there is no
more voltage at the terminals. Only demount the connecting cable after you are sure that they
are completely powerless.
11
Содержание BUM64A
Страница 1: ...E 5 01056 03 Manual Single Power Unit BUM64S A F ...
Страница 76: ...Manual Single Power Unit BUM64S A F Document no 5 01056 03 Baumüller Nürnberg Electronic GmbH Co KG 76 of 118 ...
Страница 86: ...Manual Single Power Unit BUM64S A F Document no 5 01056 03 Baumüller Nürnberg Electronic GmbH Co KG 86 of 118 ...
Страница 119: ......