Monitoring functions
Manual Single Power Unit BUM64S/A/F
Document no.: 5.01056.03
Baumüller Nürnberg Electronic GmbH & Co. KG
72
8.4
m
Monitoring function internal auxiliary voltage
The voltage required for the driver circuit of the power transistors is monitored.
When the internal auxiliary voltage is missing, a message is generated. This message is
passed on to the controller. The "ready-for-use motor-side power module" is erased.
m
safety relay
(optional)
The switch state of the safety relay is monitored.
Further information about the safety relay you will find in
8.4.3
Messages over relay contacts
clamp terminal
description
figure 25: BB_Ext, X99AB
"ready-for-use feed module"
Contact
open
:
Message "ready-for-use feed module" not present.
Contact
closed
:
Message "ready-for-use feed module" present.
further information about "ready-for-use feed module" message you will find in
.
figure 26: Prew./error, X99AB
Pre-warning - error (Pre-warning is a synonym for the better word WARNING)
(Vorw./Stör. = Prew./error)
Contact
closed
:
Message WARNING not present.
Contact
open
:
Message WARNING present.
In which cases this message is generated read under
Monitoring functions of feed module
figure 27: X68
With the safety relay you can switch off the supply voltage of the transistor drivers. After cut-off the motor
is torque-free, but is not galvanic isolated from the power module. Because the motor is not galvanic iso-
lated from the module, the motor is not voltage-free!
A typical application for the safety relay is:
f
very fast resumption of operation after cut-off.
This is possible, because the DC link is not switched off.
Check back signal of safety relay (safety relay is available as an option)
Contact
closed
:
no +24V-supply for safety relay. The power output respectively the converter is blocked.
Contact
open
:
+24V-supply for the safety relay present. The power output respectively the converter can be driven by
the controller.
If the +24V-supply for the safety relay is cut off while the drive is under operation, the drive is immediately
switched torque-free (the appliance will generate no more energy).
To re-start the drive, keep to the following procedure:
switch on +24V-supply for safety relay.
erase existing messages by a reset of the controller.