DANGER!
The operating mode ("With encoder" / "Without encoder") can be activated axis-
specific in the controller by ProDrive in the menu. The following must be selected
when using "Operating mode" (P019.052):
m
„Start page\Axis1\Configuration\Motor\Motor-In general\Motor-Type" or
m
„Start page\Axis2\Configuration\Motor\Motor-In general\Motor-Type"
If the controller is operated in the "Open Loop" (encoderless) mode, then encoder-
dependent safety functions may not be parameterized!
Requirements for the use of rotary encoders for the safety-related monitoring
Operation Manual
Safety Module for b maXX 5000
BM5-O-SAF-002/3
Document no.: 5.11016.03
Baumüller Nürnberg GmbH
40
7.5
7.5.2
Acknowledgment encoder fail status
In the Module version "Software extension" the encoder fail status can be acknowledged
by the controller again. In order to do this, the following must be complied with:
m
Deactivate all of the safety functions.
m
Acknowledge the message "Encoder fail" in the controller.
m
Generate a movement at the drive, so that the module can reset the internal
diagnostic time leading to the encoder fail.
m
If position-dependent safety functions were defined homing must be executed once
more.
Optionally to the controller, the message "Encoder fail" can be acknowledged by the S1
key of the SAF module. The key must be pressed approximately 500 ms. The green LED
H2 lights up if the key is pressed.
NOTE!
The encoder fail status can be acknowledged, if prior to this all of the safety functions
were deactivated. After this, a movement of the drive must be carried out, so that the
module detects a movement of the encoder and can reset the internal diagnostic
time.
When using the safety function SLP or SCA homing must be carried out once more
as a safe absolute position is required.
DANGER!
Before the deactivation of safety functions it must be considered that all persons keep
the distance from the danger range of the machine or installation or that all persons
on-site were informed about the planned deactivation of the safety functions and of
the following movement.
Only until afterwards the safety functions may be deactivated and the drive or the
machine may be used!