Standard Configuration
Operation Manual
Safety Module for b maXX 5000
BM5-O-SAF-002/3
Document no.: 5.11016.03
Baumüller Nürnberg GmbH
114
13.3
The cycle sensitivity of the STO-inputs is active at first. It is used for troubleshooting using
safety switch devices with relay-outputs. Therefore, the Safety Module’s cycle signals can
be applied directly via safe switches to the STO-inputs:
Connection for axis 1: "CLK_OUT_1" -> Electronic switch -> "STO_IN_1" or
connection for axis 2: "CLK_OUT_2" -> Electronic switch -> STO_IN_2"
However, the cycle sensitivity can be switched off by a bridge, "CLK_OUT_1" ->
DIG3_IN_1 (axis 1) and "CLK_OUT_2" -> DIG3_IN_2 (axis 2), which is wired from one
cycle output on the input 3 of the respective group (DIG3_IN_1 for axis 1 and DIG3_IN_2
for axis 2) .
Now STO-inputs, which are linked with safe switches can be connected to +24V, directly.
A cross connection identification is not possible in this case. Safety category 3 is valid!
In order to recognize, if the configuration data is on the Safety Module or if the standard
configuration is active, two different flashing sequences were determined for the green
LED of the controller’s assembly group.
An active standard configuration is made clear by a flashing green LED H2, whereat the
red LED H1 is off. The flashing pattern (50 ms on / 50 ms off) is displayed during the total
operating time (see
LEDs for the Display of Operating States
NOTE!
Deleting of configuration data on the Safety Module is possible via the button "Delete
parameterization" in the configuration tool ProSafePara.