Main contactor and charge contactor
Operation manual
b maXX
BM4100 (NWR)
Document no.: 5.04052.09
Baumüller Nürnberg GmbH
124
11.6
11.6 Main contactor and charge contactor
Use a main contactor and a charge contactor with a contact load capacity shown in the
table below.
11.7 Baumüller accessories
11.7.1 Shielding clamp
11.7.2 Cable RS232
Optically decoupled interface cable
Further lengths on request.
Device
Main contactor
Charge contactor
BM4135
60 A / 400 V or 60 A / 480 V
6 A / 400 - 480 V
BM4145
130 A / 400 V or 130 A / 480 V
6 A / 400 - 480 V
BM4163
250 A / 400 V or 250 A / 480 V
6 A / 400 - 480 V
Type
Part No.
Width 11 mm, for cable diameter up to 8 mm
00312171
Width 19 mm, for cable diameter 7 mm to 16 mm
00397366
Width 27 mm, for cable diameter 6 mm to 24 mm
00397375
Width 43 mm, for cable diameter 22 mm to 40 mm
00397376
NOTE!
In case you don’t use an optically decoupled interface cable, the cable shield has only
to be connected to the connector housing at the controller connector.
The company Baumüller Nürnberg GmbH recommends the usage of optically decou-
pled transmitters (e.g. from the company Ratioplast part no. 901SV232C6095 and
part no. 901SV232T6095)
Interface
Name
Length
Part No.
X1 (RS 232)
Programming cable
3 m
on request
Содержание b maXX 4100 Series
Страница 21: ...Safety Operation manual b maXX BM4100 NWR Document no 5 04052 09 21 of 142 2 Figure 2 Signs and labels BM416X ...
Страница 126: ...Baumüller accessories Operation manual b maXX BM4100 NWR Document no 5 04052 09 Baumüller Nürnberg GmbH 126 of 142 11 7 ...
Страница 138: ...Operation manual b maXX BM4100 NWR Document no 5 04052 09 Baumüller Nürnberg GmbH 138 of 142 Table of figures ...
Страница 142: ...Operation manual b maXX BM4100 NWR Document no 5 04052 09 Baumüller Nürnberg GmbH 142 of 142 Notes ...
Страница 143: ......