Baumer_GIM500R_CANopen_MA_EN.docx
11/29
www.baumer.com
03.19
3.3.5
Emergency service
Internal device error or bus problems initiate an emergency message:
COB-ID
DLC Byte0 Byte 1
Byte 2
Byte 3
Byte 4
Byte 5
Byte 6
Byte 7
80h+Node-ID
8
Error Code
Error ID
Manufacturer Specific
Byte 0+1: Error Codes
Error Code (hex) Meaning
0000
Error Reset or No Error
1000
Generic Error
4200
Device Temperature
(Internal temperature above working temperature)
5010
Physical Measurement Error
(Sensor is out of measuring range)
FF01
Internal Sensor Error
The GIM500 inclination sensor features varied diagnostic options.
In the event of error affecting device operation, an emergency message is once transmitted by Error ID.
The error should be considered as active, until the sensor is sending 0000h Error code for the corresponding
Error ID.
The LED is red continuous as long as the error is present. For the time of error presence, the inclination
value should be considered invalid. Should the error prevail and remain active, please contact Baumer
support.
Diagnosis active errors
CANopen
The LED status indicator lights up red.
If the error is active, an error message is sent.
CANopen EMCY-Message Frame Structure:
COB-ID
[hex]
Error
Code
LSB
[hex]
Error
Code
MSB
[hex]
Error
Register
[hex]
Error
Module
LSB
[hex]
Error
Module
MSB
[hex]
Error
ID
MSB
[hex]
Error
ID
LSB
[hex]
Reserved
[hex]
Description
0x80+Node-
ID
00
10
00
See
error
list
See
error
list
See
error
list
See
error
list
00
“Generic error”
was set
0x80+Node-
ID
00
00
00
See
error
list
See
error
list
00
00
00
“Generic error”
was reset
0x80+Node-
ID
00
42
00
00
10
10
00
00
“Temperature
error” was set
0x80+Node-
ID
00
00
00
00
10
00
00
00
“Temperature
error” was
reset
0x80+Node-
ID
01
FF
00
00
22
10
01
00
„Longitudinal
sensor defect“
was set