9310200990 Rev G
BE1-79A Functional Description
3-3
Table 3-3. Contact Sensing Inputs Description for ACR11B Operation
Input Terminals
Description
V1
3,4
Typically connects to a 52a contact, which results in voltage being sensed
when the breaker is closed. If V1 senses voltage within three seconds after the
Reset 1, 2, 3, or 4 timer expires, a reset will be initiated. If the relay is in
lockout, a reset will be initiated anytime V1 senses voltage. (E Reset)
V2
6, 7
Voltage sensed at this input causes the relay to start a reclose sequence.
(Motor)
V3
11, 12
Used to monitor the 52b contact while the relay is in a reset condition. When
V3 senses voltage, the relay initiates a reclose sequence. (E Operate)
V4
11, 17
Connects to a 52b contact, which results in voltage being sensed when the
breaker is open. This input is typically used to provide an anti-pump feature. If
voltage is removed from V4 during a reclose attempt, the anti-pump feature
will prevent a further reclose attempt until the next reclose set time is reached.
This prevents multiple reclose attempts for a single reclose setting. (Z)
V5
5, 6
Internally connected to the relay power supply terminal. A loss of sensing
voltage at this input causes all necessary data to be stored in memory and all
contacts to return to their de-energized or “in-the-box” state.
Reset Switch
This momentary-action switch clears the front-panel In Sequence or Lockout LEDs and restores the relay
to a rest condition. The reset switch performs the same function as the manual clutch release on the
General Electric ACR11 relay. Operating power must be applied to terminals 5 and 6 in order for a reset
to occur.
Serial Communication Port
The communication port is a standard RS-232 (DECS-B-9) female connector located on the front panel.
This port provides the means to read and configure BE1-79A settings.
Microprocessor
All reclosing and communication functions are coordinated by the microprocessor. The BE1-79A uses an
eight-bit microprocessor with integral ROM (read-only memory) and RAM (random access memory). The
microprocessor is monitored by a watchdog circuit that resets the microprocessor if a problem is detected.
Outputs
The BE1-79A has 10 outputs. The function of each output depends on the operating configuration of the
relay. Tables 3-4 and 3-5 provide a description of each output for each relay configuration.
Table 3-4. Outputs Description for ACR11A Operation
Output Terminals
Description
C1
—
Not used in this application.
C2
13, 14
Closed during reset and open when voltage at input V3 is sensed. During a
reclose sequence, C2 will remain open until the relay returns to reset. (E1)
C3
15, 16
Functions as a programmable alarm contact. It can be set to function as a
relay fail output or a combination relay fail/lockout output. a detailed
explanation is provided in Section 4,
Communication Commands, Command
Descriptions, Alarm Output Command
. (JK)
C4
17, 18
Used in conjunction with the anti-pump function. C4 is closed when voltage is
sensed at input V2. (Z2)
C5
19, 20
Used in conjunction with the anti-pump function. C5 is closed when voltage is
sensed at input V2. (Z3)
Содержание BE1-79A
Страница 1: ...INSTRUCTION MANUAL FOR RECLOSING RELAY BE1 79A Publication 9310200990 Revision G 02 08...
Страница 2: ......
Страница 8: ...vi BE1 79A Introduction 9310200990 Rev G This page intentionally left blank...
Страница 10: ...ii BE1 79A General Information 9310200990 Rev G This page intentionally left blank...
Страница 16: ...ii BE1 79A Controls and Indicators 9310200990 Rev G This page intentionally left blank...
Страница 20: ...2 4 BE1 79A Controls and Indicators 9310200990 Rev G This page intentionally left blank...
Страница 22: ...ii BE1 79A Functional Description 9310200990 Rev G This page intentionally left blank...
Страница 34: ...ii BE1 79A Communication Commands 9310200990 Rev G This page intentionally left blank...
Страница 40: ...ii BE1 79A Installation and Configuration 9310200990 Rev G This page intentionally left blank...
Страница 43: ...9310200990 Rev G BE1 79A Installation and Configuration 5 3 Figure 5 2 Panel Cutout Dimensions S1 Case...
Страница 52: ...ii BE1 79A Testing 9310200990 Rev G This page intentionally left blank...
Страница 58: ...6 6 BE1 79A Testing 9310200990 Rev G This page intentionally left blank...
Страница 60: ...ii BE1 79A RS Contact Application 9310200990 Rev G This page intentionally left blank...
Страница 66: ...ii BE1 79A Terminal Communication 9310200990 Rev G This page intentionally left blank...