6-1
CAUTION
Substitution of printed circuit boards or individual components does not necessarily
mean the relay will operate properly. Always test the relay before placing it in
operation.
SECTION 6
MAINTENANCE
GENERAL
BE1-25/79TR Sync-Check Reclosing Relays require no preventive maintenance other than clock battery
replacement (estimated 10 year life). If the relay fails to function properly and factory repair is desired,
contact the Customer Service Department of the Power Systems Group, Basler Electric, for a return
authorization number prior to shipping.
IN-HOUSE REPAIR
In-house replacement of individual components may be difficult and should not be attempted unless
appropriate equipment and qualified personnel are available.
If in-house repair is to be attempted, replacement parts may be purchased locally. The quality of
replacement parts must be at least equal to that of the original components.
Where special components are involved, Basler Electric part numbers may be obtained from the number
stamped on the component or assembly. These parts may be ordered directly from Basler Electric.
When complete boards or assemblies are needed, the following information is required.
1. Relay part number.
2. Relay serial number.
3. Board or assembly.
a) Board or assembly name.
b) Part number.
c) Serial number.
d) Revision letter.
STORAGE
This protective relay contains aluminum electrolytic capacitors which generally have a life expectancy in
excess of 10 years at storage temperatures less than 40
C. Typically, the life expectancy of the
capacitor is cut in half for every 10
C rise in temperature. Storage life can be extended if, at one-year
intervals, power is applied to the relay for a period of thirty minutes.
Содержание BE1-25/79TR
Страница 1: ...05647 6 10 07 14 19 241 5 0 4 15 0 4 64 Publication 9 2787 00 990 Revision B 07 95...
Страница 23: ...BE1 25 79TR Controls and Indicators 2 3 Figure 2 3 Location of Controls and Indicators Control Panel...
Страница 25: ...BE1 25 79TR Controls and Indicators 2 5 Figure 2 5 Vertical BE1 25 79TR Sync Check Reclosing Relay Front View...
Страница 26: ...BE1 25 79TR Controls and Indicators 2 6 Figure 2 6 Vertical BE1 25 79TR Sync Check Reclosing Relay Rear View...
Страница 27: ...BE1 25 79TR Controls and Indicators 2 7 Figure 2 7 Front Panel Vertical Mount Relay...
Страница 29: ...BE1 25 79TR Functional Description 3 2 Figure 3 1 Functional Block Diagram...
Страница 60: ...BE1 25 79TR Installation 4 8 Figure 4 9 RS 232 Interconnection Diagram For IBM Type Computers...
Страница 61: ...BE1 25 79TR Installation 4 9 Figure 4 10 RS 232 Interconnection Diagram For Protective Relay Terminals...
Страница 63: ...BE1 25 79TR Testing 5 2 REAR VIEW FRONT VIEW Figure 5 1 BE1 25 79TR Test Simulator...
Страница 64: ...BE1 25 79TR Testing 5 3 Figure 5 2 BE1 25 79TR Test Simulator Schematic Diagram Sheet 1 of 2...
Страница 65: ...BE1 25 79TR Testing 5 4 Figure 5 3 BE1 25 79TR Test Simulator Schematic Diagram Sheet 2 of 2...
Страница 66: ...BE1 25 79TR Testing 5 5 Figure 5 4 Test Setup Diagram...