3-22
when the event occurred.
The screen is automatically updated when a new event occurs. XON (Ctrl-Q) can be used to freeze the
screen and XOFF (Ctrl-S) will restart the screen update. Ctrl-R can be used to refresh the screen with the
latest data.
BE1-25/79TR SUMMARY REPORT
DATE: XX/XX/XX
TIME: XX:XX:XX
STATION: XXXXXXXXXXXXXXXXXXXX
RECORD NUMBER: XX
LINE: XXXXXXXXXXXXXXXXXXXX
RELAY SERIAL #
XXXXXXXXXXX
BREAKER # XXXXX
TIME
DIRECTION
EVENT NAME
HH:MM:SS.SH
RESET MODE
HH:MM:SS.SH
0
52 B
HH:MM:SS.SH
TRIGGER
HH:MM:SS.SH
0
LINE TEST 1
HH:MM:SS.SH
1
LINE TEST 1
HH:MM:SS.SH
LOSS OF POTENTIAL
PRESS 'P' FOR PREVIOUS OR 'N' FOR NEXT RECORD AND ARROW KEYS TO SCROLL
PRESS 'T' TO TRIGGER AN EVENT AND 'G' FOLLOWED WITH xx TO GO TO A RECORD
PRESS 'ESC' TO RETURN TO REPORTS MENU
Figure 3-16. Summary Report Screen
Detailed Report (Figure 3-17)
This activity screen provides a detailed report of each record beginning with the most recent record. Records
are numbered 1 to 99. When record #99 occurs the next following record will be record #1. Each record
contains a number of events. An event is stored every time that a control input changes, a system change
occurs, an output change occurs, or a mode changes. A record starts when an event is stored and the
record continues gathering events until the relay reaches RESET MODE or LOCKOUT MODE. RESET
MODE and LOCKOUT MODE are represented on the relay front panel when the Reset LED or Lockout LED
are lit. TRIGGER occurs when T is typed in this screen or in the SUMMARY REPORT screen to give the
status of the inputs and system parameters at a desired time.
Содержание BE1-25/79TR
Страница 1: ...05647 6 10 07 14 19 241 5 0 4 15 0 4 64 Publication 9 2787 00 990 Revision B 07 95...
Страница 23: ...BE1 25 79TR Controls and Indicators 2 3 Figure 2 3 Location of Controls and Indicators Control Panel...
Страница 25: ...BE1 25 79TR Controls and Indicators 2 5 Figure 2 5 Vertical BE1 25 79TR Sync Check Reclosing Relay Front View...
Страница 26: ...BE1 25 79TR Controls and Indicators 2 6 Figure 2 6 Vertical BE1 25 79TR Sync Check Reclosing Relay Rear View...
Страница 27: ...BE1 25 79TR Controls and Indicators 2 7 Figure 2 7 Front Panel Vertical Mount Relay...
Страница 29: ...BE1 25 79TR Functional Description 3 2 Figure 3 1 Functional Block Diagram...
Страница 60: ...BE1 25 79TR Installation 4 8 Figure 4 9 RS 232 Interconnection Diagram For IBM Type Computers...
Страница 61: ...BE1 25 79TR Installation 4 9 Figure 4 10 RS 232 Interconnection Diagram For Protective Relay Terminals...
Страница 63: ...BE1 25 79TR Testing 5 2 REAR VIEW FRONT VIEW Figure 5 1 BE1 25 79TR Test Simulator...
Страница 64: ...BE1 25 79TR Testing 5 3 Figure 5 2 BE1 25 79TR Test Simulator Schematic Diagram Sheet 1 of 2...
Страница 65: ...BE1 25 79TR Testing 5 4 Figure 5 3 BE1 25 79TR Test Simulator Schematic Diagram Sheet 2 of 2...
Страница 66: ...BE1 25 79TR Testing 5 5 Figure 5 4 Test Setup Diagram...