BE1-25/79TR General Information
1-6
Figure 1-4. Loop Station Application Example
and freezes the reclose timers any time this input is opened regardless of voltage monitor conditions.
Reclosing Example
Automated reclosing applications can be as simple or complex as your particular station requires. All
connections between BE1-25/79TR relays, monitoring inputs, and contact sensing inputs are not shown in
our example.
Our example, Figures 1-4 illustrates a typical three transformer looped station automated reclosing
application. In this example, four BE1-25/79TR relays are used. BE1-25/79TR relay number 1 is connected
across breaker 52-1 (Line 1 potential transformer (PT) feeds the relay line input and bus D PT feeds the
relay bus input). BE1-25/79TR relay number 2 is connected in a similar manner for breaker 52-2. BE1-
25/79TR relay number 3 is connected to motor operated switch 89-4 with bus D PT feeding the line input
and bus E PT feeding the bus input. BE1-25/79TR relay number 4 is connected in a similar manner for
motor operated switch 89-5, Bus F, and Bus E. When reclosing 89-4 and 89-5, 89-4 is set to close first.
Figures 1-5 through 1-8 illustrate connections for the four BE1-25/79TR relays in our example application.
Legend (for Figures 1-5 through 1-8)
43/A-Auto/Manual Switch
43C/ON-Carrier Switch ON
52b-Breaker Position
86-Lockout Relay
94-Aux Tripping Relay
BLK- Block High Speed Reclose
CE-Master Timer Enable
F/FCC-Power Fail Feature Cut-Out
H/FCC-High Speed Feature Cut-Out
HRC- High Speed Reclose Cancel
HRI-High Speed Reclose Initiate
HSR-High Speed Reclose Enable
LT1-First Line Test Enable
P/FCC-Parallel Feature Cut-Out
PAR-Parallel Enable
PF-Power Failure Enable
R/FCC-Restore Feature Cut-Out
RP1-First Restore Power Enable
T/FCC-Test Feature Cut-Out
Содержание BE1-25/79TR
Страница 1: ...05647 6 10 07 14 19 241 5 0 4 15 0 4 64 Publication 9 2787 00 990 Revision B 07 95...
Страница 23: ...BE1 25 79TR Controls and Indicators 2 3 Figure 2 3 Location of Controls and Indicators Control Panel...
Страница 25: ...BE1 25 79TR Controls and Indicators 2 5 Figure 2 5 Vertical BE1 25 79TR Sync Check Reclosing Relay Front View...
Страница 26: ...BE1 25 79TR Controls and Indicators 2 6 Figure 2 6 Vertical BE1 25 79TR Sync Check Reclosing Relay Rear View...
Страница 27: ...BE1 25 79TR Controls and Indicators 2 7 Figure 2 7 Front Panel Vertical Mount Relay...
Страница 29: ...BE1 25 79TR Functional Description 3 2 Figure 3 1 Functional Block Diagram...
Страница 60: ...BE1 25 79TR Installation 4 8 Figure 4 9 RS 232 Interconnection Diagram For IBM Type Computers...
Страница 61: ...BE1 25 79TR Installation 4 9 Figure 4 10 RS 232 Interconnection Diagram For Protective Relay Terminals...
Страница 63: ...BE1 25 79TR Testing 5 2 REAR VIEW FRONT VIEW Figure 5 1 BE1 25 79TR Test Simulator...
Страница 64: ...BE1 25 79TR Testing 5 3 Figure 5 2 BE1 25 79TR Test Simulator Schematic Diagram Sheet 1 of 2...
Страница 65: ...BE1 25 79TR Testing 5 4 Figure 5 3 BE1 25 79TR Test Simulator Schematic Diagram Sheet 2 of 2...
Страница 66: ...BE1 25 79TR Testing 5 5 Figure 5 4 Test Setup Diagram...