Flow Meter MID type 6823-x
103
Measuring System MAK TIGER 3003 Service manual, SA 131128, 10.03.2020
16.3
Assembly/installation
1
cover
5
flat gasket
9
electrodes
2
fastening clamp
6
type plate
3
cable feed
7
hexagon
head
screw
4
connection
8
sealing ring
The flowmeter can be mounted in the flow direction rising 15 ° to 90 °. The
position of the EMF must be chosen so that it is always filled with liquid, in-
stalled after the air separator and at the point with the maximum pressure in
the pipeline.
It is strictly mandatory to provide a straight flow-calming section upstream and
downstream of the MID of L
2 x nominal diameter D.
Installation
The positive direction of flow is indicated by an arrow on the type plate (6).