OPERATIONS 

PAGE 27 

acknowledge the alarm for sixty minutes only (

General Operation

).  After 

one hour, the B1277 will check the alarm inputs again, and if the same 
alarm is still present, it will begin the reporting cycle as if it were a new 
alarm. 
 
To acknowledge the B1277 locally, configure an input as an Acknowledge 
Input and activate it.  If the Site ID and “Alarm” is heard after attempting 
to acknowledge the alarms, the unit is reporting that additional alarm 
conditions exist that have not been announced and the acknowledgement 
will not occur.  If this occurs, enter the Interrogate Code to hear all the 
current alarm conditions and then enter the Acknowledge Code. 
 

Telephoning the B1277 

When you call the B1277 on the telephone, it will answer and announce its 
site ID, and possibly the phrase “No Alarms”, and then prompt you to 
“Enter Command Code”.  The B1277 then waits ten seconds for you to 
enter one of the following user defined codes: 
 

 

Acknowledge code 

 

Interrogate code 

 

Totalizer or Accumulator input reset code 

 

Intrusion input arm or disarm code 

 

Shift change code 

 

Relay on or off code 

 

Program mode access code 

 
If an Access code has not been programmed, the B1277 will automatically 
go into the programming mode after five seconds, prompting you to 
“Enter Program Code”.  You may then program the B1277 from your 
telephone the same as you would from a local programming phone. 
 
The B1277 will hang up whenever it has waited for more than ten seconds 
without receiving a control code. 
 

Reports 

At programmed times or specific events, the B1277 will generate and send 
reports containing the information collected in a text format. A Status 
Report indicates the value of each of the alarms or monitored inputs at the 
time the report was sent. An Event Summary Report contains a listing of 
all events that have occurred since the last report was sent. A Notification 
Report shows the alarm state of the unit and is sent when the state changes 
between idle, alarming and acknowledged. Each of the reports is sent only 
once with no operator response expected.  
 

Содержание B1277-HSPA

Страница 1: ...Installation Operation Manual March 2017 Rev 4 1 200 550 71st Avenue SE Phone 403 255 9544 Calgary Alberta Canada Fax 403 259 2343 T2H 0S6 www barnettprotalk com email sales barnettprotalk com...

Страница 2: ......

Страница 3: ...YOUR OUTPUTS 7 5 PROGRAMMING 8 PROGRAMMING WITH A PC 8 PROGRAMMING WITH A HANDSET 9 HANDSET PROGRAMMING CODES 10 6 TESTING THE INSTALLATION 25 7 OPERATIONS 26 8 SPECIFICATIONS 31 9 TECHNICAL DRAWINGS...

Страница 4: ...ng a remote telephone for control of external equipment Configuration of the ProTalk Cv3 can be accomplished using the dedicated PC application Additionally limited programming can be done using a loc...

Страница 5: ...der who will provide you with a Mobile Identification Number MIN Additionally to program the Cv3 and the embedded transceiver one of the following is required Standard telephone set with DTMF keypad o...

Страница 6: ...put voltages between 8 and 30 volts DC The internal battery is limited to 1 4Ahr if you require a larger battery capacity please contact our sales office for alternative battery options Since a Cv3 eq...

Страница 7: ...sales office if your needs exceed the limits of this antenna as we may be able to supply or recommend an appropriate substitute Installation using a two way radio or public address system The radio po...

Страница 8: ...0 Technical drawings have been provided on page 40 for your reference In addition to the standard detection of an alarm state at the input a digitally formatted input can also be configured as an intr...

Страница 9: ...volts DC and 0 to 30 volts DC For analog voltage operation connect the signal to the single terminal for inputs 1 through 6 and the terminal for inputs 7 through 10 Inputs 7 through 10 are also capab...

Страница 10: ...al statuses available are new alarm present any alarm present a pulsed output when an acknowledgement is received or as a system alarm When used for status indicators specific relays are assigned as f...

Страница 11: ...e time If you are using the USB connection you will need to install the drivers found on the installation CD Select USB Driver Update from the CD Menu This will launch the USB driver application Selec...

Страница 12: ...Programming For a remote session call in to the B1277 from your touch tone telephone set When answering an incoming call this unit responds depending on the previously programmed Security Level settin...

Страница 13: ...d for five seconds the Cv3 will announce the menu choices 1 Voices page 11 2 Directories page 12 3 General Site Configuration page 14 5 Output Configuration page 16 6 Group and Shift Configuration pag...

Страница 14: ...l voices Exit to Main Menu Exit to Main Menu Playback or Record Voices Cv3 Site is Ajax Compressor Station or Input 1 is Low Temperature or Output 1 is Yard Lights You 2 Record new voice Exit to voice...

Страница 15: ...that follows for the available directory entries Cv3 Group 1 on Shift 1 Directory Line 1 is or Directory Line 1 is DIAL 4032559544 VOICE You 2 Edit current line 3 Erase current line 4 Insert line Next...

Страница 16: ...he telephone number 1 RADIO ALERT VOICE 2X WAIT X is the time in seconds 255 9X SMS TEXT X is the data phone number Custom Sequences Custom sequences are created by selecting a prefix to define the po...

Страница 17: ...Menu Next setting Cv3 Relay voices are You X Enter new value 0 off 1 on Exit to Main Menu Next setting Cv3 Security Level is You X Enter new value 1 2 or 3 Exit to Main Menu Next setting Cv3 Access Co...

Страница 18: ...ys 1 Monday 2 Tuesday Exit to Main Menu Next setting Cv3 Status Report Text Message Number is You X Enter new destination phone number 0 Erase phone number disabled Exit to Main Menu Next setting Cv3...

Страница 19: ...for this input Menu items for Manual On Off Outputs are Cv3 Output One Type is On Off Cv3 Output Format is You x Enter a new value 0 NO contacts 1 NC contacts Exit to Main Menu Next setting Cv3 DTMF...

Страница 20: ...1 seconds 2 minutes Exit to I O Configurations Next Setting Cv3 Output Time is You x Enter new value 1 to 65535 Exit to Main Menu Next Setting Menu items for Automatic On Off Outputs Relays 1 2 or 4...

Страница 21: ...0 NO contacts 1 NC contacts Exit to Main Menu Next setting Cv3 Output Scale is You x Enter new value 1 seconds 2 minutes Exit to I O Configuration Next Setting Cv3 Output Time is You x Enter new valu...

Страница 22: ...ng Cv3 Interrogate Code is You X Enter a new DTMF code Erase Exit to Main Menu Next setting Cv3 Directory Timer is You X Enter new value 1 to 255 min Exit to Main Menu Next setting Cv3 Acknowledge Req...

Страница 23: ...steps Exit to Main Menu Next setting Cv3 Radio Volume One is minus TX Tone You X Enter a new value 0 to 20 Exit to Main Menu Next setting Cv3 Radio Volume Two is minus TX DTMF You X Enter a new value...

Страница 24: ...PROGRAMMING PAGE 21 8 Reset Database Cv3 Empty Program Cv3 Alert Enter Octo Three One Star Star You 31 Confirm Exit to Main Menu Exit to Main Menu Cv3 Program is Empty...

Страница 25: ...PAGE 22 9 Cellular Module Status Cv3 Phone Interrogate Cv3 Signal Strength is 0 to 15 3 poor 6 good You Exit to Main Menu Next item Cv3 Roaming status is 0 or 1 0 Off 1 On You Exit to Main Menu Exit t...

Страница 26: ...ontains a HSPA based module that is pre configured at the factory except for the assigned Mobile Number Cv3 Program Phone Cv3 SIM Card Number is 19 or 20 digit number You Exit to Main Menu Next item C...

Страница 27: ...rsion Cv3 Module Number is You Exit to Main Menu You Next Cv3 Hardware version is You Exit to Main Menu You Next Cv3 Firmware version is You Exit to Main Menu You Next Cv3 Options are You Exit to Main...

Страница 28: ...d Yellow No Signal Solid Red 4 Flashing Red Invalid MIN Not Registered Flashing Red 4 Solid Yellow Invalid MIN Registered Flashing Green 1 to 4 Solid Green Invalid MIN Roaming Flashing Yellow 1 to 4 S...

Страница 29: ...the directory If the B1277 reaches the end of the directory without being acknowledged it will wait two minutes Directory Timer then start calling again beginning at the top of the directory In addit...

Страница 30: ...efined codes Acknowledge code Interrogate code Totalizer or Accumulator input reset code Intrusion input arm or disarm code Shift change code Relay on or off code Program mode access code If an Access...

Страница 31: ...the group Green Group alarms are unacknowledged Flashing Red Group alarms are acknowledged Solid Red Group alarms are being reported Flashing Yellow 2 ALARM 12 ten hardware inputs one power supply mon...

Страница 32: ...mode in effect Normal conditions Short Green Flash Error condition Short Red Flash Tone Idle Off While a tone is being transmitted Solid Red While a tone is being received Solid Green Voice Voice Off...

Страница 33: ...dicator Pressing the power switch briefly will restore operation to full power While the Cv3 is operating at full power pressing the switch briefly will force it into low power mode The unit cannot be...

Страница 34: ...tand up to 30 VDC Inputs 1 to 6 Analog voltage mode Input impedance 210k ohm Range 0 to 5 or 0 to 30 VDC Digital mode Internal 4 7k ohm pull up resistor to 5 VDC Operates with ground closure Low state...

Страница 35: ...e between 0 dBm and 20 dBm RX audio 600 ohms single ended capacitor coupled Adjustable between 0 dBm and 20 dBm Program Ports Telset RJ11 connector Internal telset bias from the primary power supply O...

Страница 36: ...TECHNICAL DRAWINGS PAGE 33 9 TECHNICAL DRAWINGS Unit Dimensions...

Страница 37: ...TECHNICAL DRAWINGS PAGE 34 Wiring Inputs Digital connection Inputs 1 through 6 Digital connection Inputs 7 through 10 Analog Connection DC Voltage Inputs 1 through 6...

Страница 38: ...TECHNICAL DRAWINGS PAGE 35 Analog Connection DC Voltage Inputs 7 through 10 Analog Connection DC Current Inputs 7 through 10...

Страница 39: ...ng all the electronics can now be removed from the base of the Cv3 The SIM card socket can be seen near the center of the board by the cutout provided for the antenna cable Pressing it in until a clic...

Страница 40: ...h and low alarm setpoint with an accepted range on the input terminal of 0 to 5 VDC Call Activity Detect a function that when enabled delays alarm annunciation until the recipient of the call speaks i...

Страница 41: ...es are defined and the directories used have unique lists of callout instructions GSM Global System for Mobile Communications a mobile telephony standard used by carriers such as AT T Mobility T Mobil...

Страница 42: ...isolated contacts that have the capacity to be used to turn on lights or sirens or control other equipment Shift a time when an alternate directory or set of directories is used Shift Select Input an...

Страница 43: ...Ltd At 1 800 268 2646 or email support barnett engg com Product Repairs For all your repair needs please contact Barnett Engineering Ltd Barnett Engineering Ltd commits to a Repair Turnaround Time of...

Страница 44: ...cept any interference received including interference that my cause undesired operation Warning This equipment generates uses and can radiate radio frequency energy If not installed and used in accord...

Страница 45: ...ment or refund the purchase price at Barnett Engineering Ltd s option after return of such equipment by buyer to Barnett Engineering Ltd Shipment to Barnett Engineering Ltd s facility shall be borne o...

Отзывы: