OPERATIONS 

PAGE 26 

7. OPERATIONS 

This chapter gives a detailed description of exactly how the Cv3 will 
operate after the start-up programming has been completed.  Parameters 
which may be altered are pointed out, with reference to the appropriate 
Program Code section. 
 

Alarm Sequence 

When the B1277 detects an alarm condition, it dials the first telephone 
number stored in the directory.  When the telephone call is answered, the 
B1277 will announce its Site ID, the list of any alarms present, and prompt 
the user to “Enter Acknowledge Code”.  It will repeat this message a 
minimum of three times, pausing five seconds after each announcement to 
wait for an acknowledgement.  When the Acknowledge Code is detected, 
The B1277 will announce “Alarms Acknowledged” and then prompt you 
to “Enter Command Code”. 
 
If the calling number is busy, if there is no answer, or if the B1277 does 
not receive the Acknowledge Code after announcing the alarm, it will 
terminate the call then call the next number in the directory.  If the B1277 
reaches the end of the directory without being acknowledged, it will wait 
two minutes (

Directory Timer

) then start calling again beginning at the top 

of the directory. 
 
In addition to making voice calls, the B1277 may be programmed to 
announce the alarms a number of times over radio, a public address 
system, or send out a Text Message or email containing the alarm 
information. 
 

Acknowledging an Alarm 

When the B1277 calls you on the telephone, it may take up to five seconds 
before it starts speaking.  After it announces the alarms, it prompts you to 
“Enter Acknowledge Code”.  You have five seconds to begin entering 
digits. 
 
If the B1277 has been programmed to operate its relays (

Output 

Configuration

), you may send a relay code over the telephone before 

acknowledging the alarms.  The B1277 will actuate the relay, speak the 
associated voice message, then prompt you again to “Enter Acknowledge 
Code”.  After the B1277 has detected the Acknowledge Code, it will speak 
the phrase “Alarms Acknowledged” and return to the “Enter Command 
Code” level.  If no activity occurs for five seconds, it will hang up. 
 
Appending the 

#

 digit at the end of the Acknowledge code allows you to 

Содержание B1277-HSPA

Страница 1: ...Installation Operation Manual March 2017 Rev 4 1 200 550 71st Avenue SE Phone 403 255 9544 Calgary Alberta Canada Fax 403 259 2343 T2H 0S6 www barnettprotalk com email sales barnettprotalk com...

Страница 2: ......

Страница 3: ...YOUR OUTPUTS 7 5 PROGRAMMING 8 PROGRAMMING WITH A PC 8 PROGRAMMING WITH A HANDSET 9 HANDSET PROGRAMMING CODES 10 6 TESTING THE INSTALLATION 25 7 OPERATIONS 26 8 SPECIFICATIONS 31 9 TECHNICAL DRAWINGS...

Страница 4: ...ng a remote telephone for control of external equipment Configuration of the ProTalk Cv3 can be accomplished using the dedicated PC application Additionally limited programming can be done using a loc...

Страница 5: ...der who will provide you with a Mobile Identification Number MIN Additionally to program the Cv3 and the embedded transceiver one of the following is required Standard telephone set with DTMF keypad o...

Страница 6: ...put voltages between 8 and 30 volts DC The internal battery is limited to 1 4Ahr if you require a larger battery capacity please contact our sales office for alternative battery options Since a Cv3 eq...

Страница 7: ...sales office if your needs exceed the limits of this antenna as we may be able to supply or recommend an appropriate substitute Installation using a two way radio or public address system The radio po...

Страница 8: ...0 Technical drawings have been provided on page 40 for your reference In addition to the standard detection of an alarm state at the input a digitally formatted input can also be configured as an intr...

Страница 9: ...volts DC and 0 to 30 volts DC For analog voltage operation connect the signal to the single terminal for inputs 1 through 6 and the terminal for inputs 7 through 10 Inputs 7 through 10 are also capab...

Страница 10: ...al statuses available are new alarm present any alarm present a pulsed output when an acknowledgement is received or as a system alarm When used for status indicators specific relays are assigned as f...

Страница 11: ...e time If you are using the USB connection you will need to install the drivers found on the installation CD Select USB Driver Update from the CD Menu This will launch the USB driver application Selec...

Страница 12: ...Programming For a remote session call in to the B1277 from your touch tone telephone set When answering an incoming call this unit responds depending on the previously programmed Security Level settin...

Страница 13: ...d for five seconds the Cv3 will announce the menu choices 1 Voices page 11 2 Directories page 12 3 General Site Configuration page 14 5 Output Configuration page 16 6 Group and Shift Configuration pag...

Страница 14: ...l voices Exit to Main Menu Exit to Main Menu Playback or Record Voices Cv3 Site is Ajax Compressor Station or Input 1 is Low Temperature or Output 1 is Yard Lights You 2 Record new voice Exit to voice...

Страница 15: ...that follows for the available directory entries Cv3 Group 1 on Shift 1 Directory Line 1 is or Directory Line 1 is DIAL 4032559544 VOICE You 2 Edit current line 3 Erase current line 4 Insert line Next...

Страница 16: ...he telephone number 1 RADIO ALERT VOICE 2X WAIT X is the time in seconds 255 9X SMS TEXT X is the data phone number Custom Sequences Custom sequences are created by selecting a prefix to define the po...

Страница 17: ...Menu Next setting Cv3 Relay voices are You X Enter new value 0 off 1 on Exit to Main Menu Next setting Cv3 Security Level is You X Enter new value 1 2 or 3 Exit to Main Menu Next setting Cv3 Access Co...

Страница 18: ...ys 1 Monday 2 Tuesday Exit to Main Menu Next setting Cv3 Status Report Text Message Number is You X Enter new destination phone number 0 Erase phone number disabled Exit to Main Menu Next setting Cv3...

Страница 19: ...for this input Menu items for Manual On Off Outputs are Cv3 Output One Type is On Off Cv3 Output Format is You x Enter a new value 0 NO contacts 1 NC contacts Exit to Main Menu Next setting Cv3 DTMF...

Страница 20: ...1 seconds 2 minutes Exit to I O Configurations Next Setting Cv3 Output Time is You x Enter new value 1 to 65535 Exit to Main Menu Next Setting Menu items for Automatic On Off Outputs Relays 1 2 or 4...

Страница 21: ...0 NO contacts 1 NC contacts Exit to Main Menu Next setting Cv3 Output Scale is You x Enter new value 1 seconds 2 minutes Exit to I O Configuration Next Setting Cv3 Output Time is You x Enter new valu...

Страница 22: ...ng Cv3 Interrogate Code is You X Enter a new DTMF code Erase Exit to Main Menu Next setting Cv3 Directory Timer is You X Enter new value 1 to 255 min Exit to Main Menu Next setting Cv3 Acknowledge Req...

Страница 23: ...steps Exit to Main Menu Next setting Cv3 Radio Volume One is minus TX Tone You X Enter a new value 0 to 20 Exit to Main Menu Next setting Cv3 Radio Volume Two is minus TX DTMF You X Enter a new value...

Страница 24: ...PROGRAMMING PAGE 21 8 Reset Database Cv3 Empty Program Cv3 Alert Enter Octo Three One Star Star You 31 Confirm Exit to Main Menu Exit to Main Menu Cv3 Program is Empty...

Страница 25: ...PAGE 22 9 Cellular Module Status Cv3 Phone Interrogate Cv3 Signal Strength is 0 to 15 3 poor 6 good You Exit to Main Menu Next item Cv3 Roaming status is 0 or 1 0 Off 1 On You Exit to Main Menu Exit t...

Страница 26: ...ontains a HSPA based module that is pre configured at the factory except for the assigned Mobile Number Cv3 Program Phone Cv3 SIM Card Number is 19 or 20 digit number You Exit to Main Menu Next item C...

Страница 27: ...rsion Cv3 Module Number is You Exit to Main Menu You Next Cv3 Hardware version is You Exit to Main Menu You Next Cv3 Firmware version is You Exit to Main Menu You Next Cv3 Options are You Exit to Main...

Страница 28: ...d Yellow No Signal Solid Red 4 Flashing Red Invalid MIN Not Registered Flashing Red 4 Solid Yellow Invalid MIN Registered Flashing Green 1 to 4 Solid Green Invalid MIN Roaming Flashing Yellow 1 to 4 S...

Страница 29: ...the directory If the B1277 reaches the end of the directory without being acknowledged it will wait two minutes Directory Timer then start calling again beginning at the top of the directory In addit...

Страница 30: ...efined codes Acknowledge code Interrogate code Totalizer or Accumulator input reset code Intrusion input arm or disarm code Shift change code Relay on or off code Program mode access code If an Access...

Страница 31: ...the group Green Group alarms are unacknowledged Flashing Red Group alarms are acknowledged Solid Red Group alarms are being reported Flashing Yellow 2 ALARM 12 ten hardware inputs one power supply mon...

Страница 32: ...mode in effect Normal conditions Short Green Flash Error condition Short Red Flash Tone Idle Off While a tone is being transmitted Solid Red While a tone is being received Solid Green Voice Voice Off...

Страница 33: ...dicator Pressing the power switch briefly will restore operation to full power While the Cv3 is operating at full power pressing the switch briefly will force it into low power mode The unit cannot be...

Страница 34: ...tand up to 30 VDC Inputs 1 to 6 Analog voltage mode Input impedance 210k ohm Range 0 to 5 or 0 to 30 VDC Digital mode Internal 4 7k ohm pull up resistor to 5 VDC Operates with ground closure Low state...

Страница 35: ...e between 0 dBm and 20 dBm RX audio 600 ohms single ended capacitor coupled Adjustable between 0 dBm and 20 dBm Program Ports Telset RJ11 connector Internal telset bias from the primary power supply O...

Страница 36: ...TECHNICAL DRAWINGS PAGE 33 9 TECHNICAL DRAWINGS Unit Dimensions...

Страница 37: ...TECHNICAL DRAWINGS PAGE 34 Wiring Inputs Digital connection Inputs 1 through 6 Digital connection Inputs 7 through 10 Analog Connection DC Voltage Inputs 1 through 6...

Страница 38: ...TECHNICAL DRAWINGS PAGE 35 Analog Connection DC Voltage Inputs 7 through 10 Analog Connection DC Current Inputs 7 through 10...

Страница 39: ...ng all the electronics can now be removed from the base of the Cv3 The SIM card socket can be seen near the center of the board by the cutout provided for the antenna cable Pressing it in until a clic...

Страница 40: ...h and low alarm setpoint with an accepted range on the input terminal of 0 to 5 VDC Call Activity Detect a function that when enabled delays alarm annunciation until the recipient of the call speaks i...

Страница 41: ...es are defined and the directories used have unique lists of callout instructions GSM Global System for Mobile Communications a mobile telephony standard used by carriers such as AT T Mobility T Mobil...

Страница 42: ...isolated contacts that have the capacity to be used to turn on lights or sirens or control other equipment Shift a time when an alternate directory or set of directories is used Shift Select Input an...

Страница 43: ...Ltd At 1 800 268 2646 or email support barnett engg com Product Repairs For all your repair needs please contact Barnett Engineering Ltd Barnett Engineering Ltd commits to a Repair Turnaround Time of...

Страница 44: ...cept any interference received including interference that my cause undesired operation Warning This equipment generates uses and can radiate radio frequency energy If not installed and used in accord...

Страница 45: ...ment or refund the purchase price at Barnett Engineering Ltd s option after return of such equipment by buyer to Barnett Engineering Ltd Shipment to Barnett Engineering Ltd s facility shall be borne o...

Отзывы: