INSTALLATION INSTRUCTIONS

WALL MOUNTING INFORMATION

  1.  These units are secured by wall mounting brackets 

which secure the unit to the outside wall surface at 
both sides.

  2.  On wood frame walls, the wall construction must be 

strong and rigid enough to carry the weight of the 
unit without transmitting any unit vibration.

  3.  Concrete block walls must be thoroughly inspected 

to insure that they are capable of carrying the weight 
of the installed unit.

MOUNTING THE UNIT

  1.  Two holes, for the supply and return air openings, 

must be cut through the wall as shown in Figure 3.

  2.  Locate and mark lag bolt locations, if desired.  See 

Figure 3.

  3.  Hook top rain flashing under back bend of top.  Top 

rain flashing is shipped attached to the back of the 

unit on the right side.

  4.  Position unit in opening and secure with 5/16 lag 

bolts; use 7/8 inch diameter flat washers on the lag 

bolts.

  5.  Secure rain flashing to wall and caulk across entire 

length of top.  See Figure 3.

  6.  For additional mounting rigidity, the return air 

and supply air frames or collars can be drilled 
and screwed or welded to the structural wall itself 
(depending upon wall construction).  Be sure to 
observe required clearance if combustible wall.

  7.  On side-by-side installations, maintain a minimum 

of 20 inches clearance on right side to allow access 

to control panel and allow proper airflow to outdoor 

coil.  Additional clearance may be required to meet 
local or national codes.

Содержание W12AAA

Страница 1: ...MOUNTED PACKAGE AIR CONDITIONERS Model W12AAA INSTALLATION INSTRUCTIONS Manual 2100 618 Supersedes NEW File Tab 16 Date 06 04 14 Bard Manufacturing Company Inc Bryan Ohio 43506 Since 1914 Moving ahea...

Страница 2: ...2 Fresh Air Damper 7 Figure 3 Mounting Instructions 9 Figure 4 Wall Mounting Instructions 10 Figure 5 Wall Mounting Instructions 10 Figure 6 Common Wall Mounting Installations 11 Figure 7 Low Voltage...

Страница 3: ...ter and Summer Air Conditioning Duct Design for ACCA Manual D Residential Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning...

Страница 4: ...t Control J X Low Ambient Control and Alarm Relay VOLTS PHASE A 230 208 60 1 D 240 220 50 1 K 115 60 1 KW 00 No KW 02 2 2 KW 03 3 6 KW 05 5 0 KW 0Z Circuit Breaker Only VENTILATION OPTIONS X Barometri...

Страница 5: ...FLOW IS BLOW THRU 19 72 19 72 3 88 31 06 20 43 ELECTRICAL ENTRANCE SHIPPING LOCATION OPTIONAL TOP RAIN FLASHING DRAIN HOSE 10 00 5 00 30 13 17 00 5 00 32 00 22 25 25 750 2 50 MIS 3599 FRONT VIEW BACK...

Страница 6: ...a proposed installation should be based on heat loss gain calculation made according to methods of Air Conditioning Contractors of America ACCA The air duct should be installed in accordance with the...

Страница 7: ...a single story structure FILTERS A one inch throwaway filter is supplied with each unit The filter slides into position making it easy to service This filter can be serviced from the outside by remov...

Страница 8: ...ations if desired See Figure 3 3 Hook top rain flashing under back bend of top Top rain flashing is shipped attached to the back of the unit on the right side 4 Position unit in opening and secure wit...

Страница 9: ...LIED FOAM AIR SEAL WALL WALL STRUCTURE MIS 3600 FLANGES AND UNDER TOP FLASHING AT TIME OF INSTALLATION SUPPLY AIR DUCT RETURN AIR NOTE IT IS RECOMMENDED THAT A BEAD OF SILICONE CAULKING BE PLACED BEHI...

Страница 10: ...Manual 2100 618 Page 10 of 21 FIGURE 5 WALL MOUNTING INSTRUCTIONS FIGURE 4 WALL MOUNTING INSTRUCTIONS SEE FIGURE 3 MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS...

Страница 11: ...Manual 2100 618 Page 11 of 21 FIGURE 6 COMMON WALL MOUNTING INSTALLATIONS...

Страница 12: ...be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high starting current of the compressor motor See Table 2 for electrical specific...

Страница 13: ...h ECONWM Y1 terminal is the 1st Stage compressor input for cooling 2 Stage units only No ECONWM Y2 terminal is the 2nd Stage compressor input for cooling 2 Stage units only No ECONWM W1 terminal is th...

Страница 14: ...ONFIGURATION FROM HEAT PUMP TO HEAT COOL MUST BE CONFIGURED TO PROGRAMMABLE AND FAN SET TO PROGRAMMED FAN FOR THE A OUTPUT TO FUNCTION DURING SCHEDULED OCCUPIED PERIODS 4 2 1 OPTIONAL VENT PACKAGE 3 R...

Страница 15: ...NON PROGRAMMABLE THERMOSTAT ADD JUMPER FROM G TO E ONLY IF OPTIONAL CO2 CONTROLLER IS INSTALLED CHANGE SYSTEM TYPE SET UP FUNCTION 1 FROM 5 2 HEAT 1 COOL HEAT PUMP TO 6 2 HEAT 2 COOL CONVENTIONAL ADD...

Страница 16: ...A O B 3 A C UNIT Change model configuration from heat pump to heat cool and must be configured for W2 Factory Jumper Installed Must be energized to enable minimum position NOTE Economizer Control Def...

Страница 17: ...leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be used...

Страница 18: ...ssure switch and low pressure switch if employed is closed the compressor contactor is energized Upon shutdown the delay on break time starts and prevents restart until the delay on break and delay on...

Страница 19: ...38 second DOM 4 0 minute 240 seconds DOB 144 second DOM 5 0 minute 300 seconds DOB 150 second DOM During routine operation of the unit with no power interruptions the compressor will operate on demand...

Страница 20: ...e units Since many installation specific situations can affect the pressure readings this information should only be used by certified technicians as a guide for evaluating proper system performance T...

Страница 21: ...w Side High Side 139 315 143 335 146 357 148 381 151 405 154 430 156 455 159 482 161 510 164 539 W12AAAD 75 deg DB 62 deg WB Low Side High Side 125 314 129 334 132 357 134 380 137 404 139 429 141 454...

Отзывы: