Low Voltage Connection
These units use a 24-volt AC low voltage circuit. The “
R
” terminal is the
hot
terminal and the “
C
” terminal is
grounded
.
“
G
” terminal is the
fan input
.
“
Y
” terminal is the
compressor input for cooling
1-Stage units only or 2-Stage units with ECONWM*
“
Pink Wire
” is
2nd Stage cooling
2-Stage units only with ECONWM*
“
Y1
” terminal is the
1st Stage compressor input for cooling
2-Stage units only — No ECONWM*
“
Y2
” terminal is the
2nd Stage compressor input for cooling
2-Stage units only — No ECONWM*
“
W1
” terminal is the
1st stage electric heat
.
“
W2
” terminal is the
2nd stage heat
(if equipped).
“
A
”, “
E
”, “
F
” terminals are the
ventilation inputs
. See Figures 8-10 for detailed diagrams.
NOTE: On models with “J” Control Module, Terminals 1, 2 and 3 are used for the alarm relay.
FIGURE 7
LOW VOLTAGE WIRING
BASIC A/C WITH OPTIONAL ELECTRIC HEAT
NO ECONOMIZER OR VENTILATION PACKAGES