Manual 2100-618
Page
21 of 21
TABLE 9
PRESSURE TABLE
COOLING
Air Temperature Entering Outdoor Coil °F
W12AAA
TABLE 10
OPTIONAL FIELD INSTALLED ACCESSORIES
Model
Return Air
Temperature
Pressure
75°
80°
85°
90°
95°
100°
105°
100°
115°
120°
W12AAAA
W12AAAK
75 deg. DB
62 deg. WB
Low Side
High Side
125
296
129
316
132
336
134
359
137
381
139
405
141
429
144
454
146
481
148
508
80 deg. DB
67 deg. WB
Low Side
High Side
134
304
138
324
141
345
143
368
146
391
149
415
151
440
154
466
156
493
158
521
85 deg. DB
72 deg. WB
Low Side
High Side
139
315
143
335
146
357
148
381
151
405
154
430
156
455
159
482
161
510
164
539
W12AAAD
75 deg. DB
62 deg. WB
Low Side
High Side
125
314
129
334
132
357
134
380
137
404
139
429
141
454
144
482
146
510
148
538
80 deg. DB
67 deg. WB
Low Side
High Side
134
322
138
343
141
366
143
390
146
414
149
440
151
466
154
494
156
523
158
552
85 deg. DB
72 deg. WB
Low Side
High Side
139
333
143
355
146
379
148
404
151
428
154
455
156
482
159
511
161
541
164
571
Model
Description
BOP-1A
Blank Off Plate
X
BFAD-1
Barometric Fresh Air Damper
X
JIFM-1A
Economizer with Exhaust
X
CMA-28
Low Ambient Control
X
CRVS-1A
Commercial Ventilator - Spring Return
X
Low Side Pressure +4 PSIG
High Side Pr10 PSIG