DUCT WORK

All duct work, supply and return must be properly sized 

for the design air flow requirement of the equipment.  

Air Conditioning Contractors of America (ACCA) is 
an excellent guide to proper sizing.  All duct work or 
portions thereof not in the conditioned space should be 
properly insulated in order to both conserve energy and 
prevent condensation or moisture damage.

Refer to Table 8 for maximum static pressure available 
for duct design.

Design the duct work according to methods given by 
the Air Conditioning Contractors of America (ACCA).  
When duct runs through unheated spaces, it should be 
insulated with a minimum of one inch of insulation.  
Use insulation with a vapor barrier on the outside of the 
insulation.  Flexible joints should be used to connect the 
duct work to the equipment in order to keep the noise 
transmission to a minimum.

Ducts through the walls must be insulated and all joints 
taped or sealed to prevent air or moisture entering the 
wall cavity.

Some installations may not require any return air duct.  
It is recommended that on this type of installation that 

a filter grille be located in the wall.  Filters must be of 

sufficient size to allow a maximum velocity of 400 FPM.

NOTE:  If no return air duct is used, applicable 

installation codes may limit this cabinet to 
installation only in a single story structure.

FILTERS

A one inch throwaway filter is supplied with each unit.  

The filter slides into position making it easy to service.  

This filter can be serviced from the outside by removing 

the service door.  A 2-inch pleated filter is also available 

as an optional accessory.  The internal filter brackets are 

adjustable to accommodate the 2-inch filter by bending 

the metal tabs holding the 1-inch filter down.  There are 

two tabs on each side of the filter.

FRESH AIR INTAKE

All units are built with fresh air inlet slots punched in the 
service panel.

If the unit is equipped with a fresh air damper assembly, 
the assembly is shipped already attached to the unit.  The 
damper blade is locked in the closed position.  To allow 
the damper to operate, the maximum and minimum blade 
position stops must be installed.  See Figure 2.  

All capacity, efficiency and cost of operation information 

as required for Department of Energy “Energyguide” 
Fact Sheets is based upon the fresh air blank-off plate 
in place and is recommended for maximum energy 

efficiency.

The blank-off plate is available upon request from the 
factory and is installed in place of the fresh air damper 
shipped with each unit.

CONDENSATE DRAIN

A plastic drain hose extends from the drain pan at the top 
of the unit down to the unit base.  There are openings in 
the unit base for the drain hose to pass through.  In the 
event the drain hose is connected to a drain system of 
some type, it must be an open or vented type system to 
assure proper drainage.

FIGURE  2

FRESH AIR DAMPER

Содержание W12AAA

Страница 1: ...MOUNTED PACKAGE AIR CONDITIONERS Model W12AAA INSTALLATION INSTRUCTIONS Manual 2100 618 Supersedes NEW File Tab 16 Date 06 04 14 Bard Manufacturing Company Inc Bryan Ohio 43506 Since 1914 Moving ahea...

Страница 2: ...2 Fresh Air Damper 7 Figure 3 Mounting Instructions 9 Figure 4 Wall Mounting Instructions 10 Figure 5 Wall Mounting Instructions 10 Figure 6 Common Wall Mounting Installations 11 Figure 7 Low Voltage...

Страница 3: ...ter and Summer Air Conditioning Duct Design for ACCA Manual D Residential Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning...

Страница 4: ...t Control J X Low Ambient Control and Alarm Relay VOLTS PHASE A 230 208 60 1 D 240 220 50 1 K 115 60 1 KW 00 No KW 02 2 2 KW 03 3 6 KW 05 5 0 KW 0Z Circuit Breaker Only VENTILATION OPTIONS X Barometri...

Страница 5: ...FLOW IS BLOW THRU 19 72 19 72 3 88 31 06 20 43 ELECTRICAL ENTRANCE SHIPPING LOCATION OPTIONAL TOP RAIN FLASHING DRAIN HOSE 10 00 5 00 30 13 17 00 5 00 32 00 22 25 25 750 2 50 MIS 3599 FRONT VIEW BACK...

Страница 6: ...a proposed installation should be based on heat loss gain calculation made according to methods of Air Conditioning Contractors of America ACCA The air duct should be installed in accordance with the...

Страница 7: ...a single story structure FILTERS A one inch throwaway filter is supplied with each unit The filter slides into position making it easy to service This filter can be serviced from the outside by remov...

Страница 8: ...ations if desired See Figure 3 3 Hook top rain flashing under back bend of top Top rain flashing is shipped attached to the back of the unit on the right side 4 Position unit in opening and secure wit...

Страница 9: ...LIED FOAM AIR SEAL WALL WALL STRUCTURE MIS 3600 FLANGES AND UNDER TOP FLASHING AT TIME OF INSTALLATION SUPPLY AIR DUCT RETURN AIR NOTE IT IS RECOMMENDED THAT A BEAD OF SILICONE CAULKING BE PLACED BEHI...

Страница 10: ...Manual 2100 618 Page 10 of 21 FIGURE 5 WALL MOUNTING INSTRUCTIONS FIGURE 4 WALL MOUNTING INSTRUCTIONS SEE FIGURE 3 MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS...

Страница 11: ...Manual 2100 618 Page 11 of 21 FIGURE 6 COMMON WALL MOUNTING INSTALLATIONS...

Страница 12: ...be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high starting current of the compressor motor See Table 2 for electrical specific...

Страница 13: ...h ECONWM Y1 terminal is the 1st Stage compressor input for cooling 2 Stage units only No ECONWM Y2 terminal is the 2nd Stage compressor input for cooling 2 Stage units only No ECONWM W1 terminal is th...

Страница 14: ...ONFIGURATION FROM HEAT PUMP TO HEAT COOL MUST BE CONFIGURED TO PROGRAMMABLE AND FAN SET TO PROGRAMMED FAN FOR THE A OUTPUT TO FUNCTION DURING SCHEDULED OCCUPIED PERIODS 4 2 1 OPTIONAL VENT PACKAGE 3 R...

Страница 15: ...NON PROGRAMMABLE THERMOSTAT ADD JUMPER FROM G TO E ONLY IF OPTIONAL CO2 CONTROLLER IS INSTALLED CHANGE SYSTEM TYPE SET UP FUNCTION 1 FROM 5 2 HEAT 1 COOL HEAT PUMP TO 6 2 HEAT 2 COOL CONVENTIONAL ADD...

Страница 16: ...A O B 3 A C UNIT Change model configuration from heat pump to heat cool and must be configured for W2 Factory Jumper Installed Must be energized to enable minimum position NOTE Economizer Control Def...

Страница 17: ...leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be used...

Страница 18: ...ssure switch and low pressure switch if employed is closed the compressor contactor is energized Upon shutdown the delay on break time starts and prevents restart until the delay on break and delay on...

Страница 19: ...38 second DOM 4 0 minute 240 seconds DOB 144 second DOM 5 0 minute 300 seconds DOB 150 second DOM During routine operation of the unit with no power interruptions the compressor will operate on demand...

Страница 20: ...e units Since many installation specific situations can affect the pressure readings this information should only be used by certified technicians as a guide for evaluating proper system performance T...

Страница 21: ...w Side High Side 139 315 143 335 146 357 148 381 151 405 154 430 156 455 159 482 161 510 164 539 W12AAAD 75 deg DB 62 deg WB Low Side High Side 125 314 129 334 132 357 134 380 137 404 139 429 141 454...