background image

Manual 2100-618 
Page 

17 of 21

START UP

THESE UNITS REQUIRE R-410A 
REFRIGERANT AND POLYOL 
ESTER OIL.

GENERAL:

1.  Use separate service equipment to avoid cross    
 

contamination of oil and refrigerants.

2.  Use recovery equipment rated for R-410A  

 

 refrigerant.

3.  Use manifold gauges rated for R-410A (800 psi/250  
 

psi low).

4.  R-410A is a binary blend of HFC-32 and HFC-125.

5.  R-410A is nearly azeotropic - similar to R-22 and  
 

R-12.  Although nearly azeotropic, charge with    

 

liquid refrigerant.

6.  R-410A operates at 40-70% higher pressure than   
 

R-22, and systems designed for R-22 cannot  

 

 

withstand this higher pressure.

7.  R-410A has an ozone depletion potential of zero,  
 

but must be reclaimed due to its global warming   

 potential.

8.  R-410A compressors use Polyol Ester oil.

9.  Polyol Ester oil is hygroscopic; it will rapidly absorb  
 

moisture and strongly hold this moisture in the oil.

10. A liquid line dryer must be used - even a deep  

 

 

vacuum will not separate moisture from the oil.

11.  Limit atmospheric exposure to 15 minutes.

12. If compressor removal is necessary, always plug   
 

compressor immediately after removal.  Purge with  

 

small amount of nitrogen when inserting plugs.

TOPPING OFF SYSTEM CHARGE

If a leak has occurred in the system, Bard Manufacturing 
recommends reclaiming, evacuating (see criteria above), 
and charging to the nameplate charge.  If done correctly, 
topping off the system charge can be done without 
problems.

With R-410A, there are no significant changes in the 

refrigerant composition during multiple leaks and 
recharges.  R-410A refrigerant is close to being an 
azeotropic blend (it behaves like a pure compound 
or single component refrigerant).  The remaining 
refrigerant charge, in the system, may be used after leaks 
have occurred and then “top-off” the charge by utilizing 
the pressure charts on the inner control panel cover as a 
guideline.

REMEMBER:  

When adding R-410A refrigerant, it must 

come out of the charging cylinder/tank as a liquid to 
avoid any fractionation, and to insure optimal system 
performance.  Refer to instructions for the cylinder that 
is being utilized for proper method of liquid extraction.

SAFETY PRACTICES:

1.  Never mix R-410A with other refrigerants.

2.  Use gloves and safety glasses, Polyol Ester oils can  
 

be irritating to the skin, and liquid refrigerant will  

 

freeze the skin.

3.  Never use air and R-410A to leak check; the  

 

 

mixture may become flammable.

4.  Do not inhale R-410A – the vapor attacks the  

 

 

nervous system, creating dizziness, loss of  

 

 

coordination and slurred speech.  Cardiac  

 

 

irregularities, unconsciousness and ultimate death  

 

can result from breathing this concentration.

5.  Do not burn R-410A.  This decomposition  

 

 

produces hazardous vapors.  Evacuate the area if   

 exposed.

6.  Use only cylinders rated DOT4BA/4BW 400.

7.  Never fill cylinders over 80% of total capacity.

8.  Store cylinders in a cool area, out of direct  

 

 sunlight.

9.  Never heat cylinders above 125°F.

10. Never trap liquid R-410A in manifold sets, gauge  

 

lines or cylinders.  R-410A expands significantly at  

 

warmer temperatures.  Once a cylinder or line is full  

 

of liquid, any further rise in temperature will  

 

 

cause it to burst.

        WARNING

Failure to conform to these practices 
could lead to damage, injury or death.

Содержание W12AAA

Страница 1: ...MOUNTED PACKAGE AIR CONDITIONERS Model W12AAA INSTALLATION INSTRUCTIONS Manual 2100 618 Supersedes NEW File Tab 16 Date 06 04 14 Bard Manufacturing Company Inc Bryan Ohio 43506 Since 1914 Moving ahea...

Страница 2: ...2 Fresh Air Damper 7 Figure 3 Mounting Instructions 9 Figure 4 Wall Mounting Instructions 10 Figure 5 Wall Mounting Instructions 10 Figure 6 Common Wall Mounting Installations 11 Figure 7 Low Voltage...

Страница 3: ...ter and Summer Air Conditioning Duct Design for ACCA Manual D Residential Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning...

Страница 4: ...t Control J X Low Ambient Control and Alarm Relay VOLTS PHASE A 230 208 60 1 D 240 220 50 1 K 115 60 1 KW 00 No KW 02 2 2 KW 03 3 6 KW 05 5 0 KW 0Z Circuit Breaker Only VENTILATION OPTIONS X Barometri...

Страница 5: ...FLOW IS BLOW THRU 19 72 19 72 3 88 31 06 20 43 ELECTRICAL ENTRANCE SHIPPING LOCATION OPTIONAL TOP RAIN FLASHING DRAIN HOSE 10 00 5 00 30 13 17 00 5 00 32 00 22 25 25 750 2 50 MIS 3599 FRONT VIEW BACK...

Страница 6: ...a proposed installation should be based on heat loss gain calculation made according to methods of Air Conditioning Contractors of America ACCA The air duct should be installed in accordance with the...

Страница 7: ...a single story structure FILTERS A one inch throwaway filter is supplied with each unit The filter slides into position making it easy to service This filter can be serviced from the outside by remov...

Страница 8: ...ations if desired See Figure 3 3 Hook top rain flashing under back bend of top Top rain flashing is shipped attached to the back of the unit on the right side 4 Position unit in opening and secure wit...

Страница 9: ...LIED FOAM AIR SEAL WALL WALL STRUCTURE MIS 3600 FLANGES AND UNDER TOP FLASHING AT TIME OF INSTALLATION SUPPLY AIR DUCT RETURN AIR NOTE IT IS RECOMMENDED THAT A BEAD OF SILICONE CAULKING BE PLACED BEHI...

Страница 10: ...Manual 2100 618 Page 10 of 21 FIGURE 5 WALL MOUNTING INSTRUCTIONS FIGURE 4 WALL MOUNTING INSTRUCTIONS SEE FIGURE 3 MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS...

Страница 11: ...Manual 2100 618 Page 11 of 21 FIGURE 6 COMMON WALL MOUNTING INSTALLATIONS...

Страница 12: ...be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high starting current of the compressor motor See Table 2 for electrical specific...

Страница 13: ...h ECONWM Y1 terminal is the 1st Stage compressor input for cooling 2 Stage units only No ECONWM Y2 terminal is the 2nd Stage compressor input for cooling 2 Stage units only No ECONWM W1 terminal is th...

Страница 14: ...ONFIGURATION FROM HEAT PUMP TO HEAT COOL MUST BE CONFIGURED TO PROGRAMMABLE AND FAN SET TO PROGRAMMED FAN FOR THE A OUTPUT TO FUNCTION DURING SCHEDULED OCCUPIED PERIODS 4 2 1 OPTIONAL VENT PACKAGE 3 R...

Страница 15: ...NON PROGRAMMABLE THERMOSTAT ADD JUMPER FROM G TO E ONLY IF OPTIONAL CO2 CONTROLLER IS INSTALLED CHANGE SYSTEM TYPE SET UP FUNCTION 1 FROM 5 2 HEAT 1 COOL HEAT PUMP TO 6 2 HEAT 2 COOL CONVENTIONAL ADD...

Страница 16: ...A O B 3 A C UNIT Change model configuration from heat pump to heat cool and must be configured for W2 Factory Jumper Installed Must be energized to enable minimum position NOTE Economizer Control Def...

Страница 17: ...leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be used...

Страница 18: ...ssure switch and low pressure switch if employed is closed the compressor contactor is energized Upon shutdown the delay on break time starts and prevents restart until the delay on break and delay on...

Страница 19: ...38 second DOM 4 0 minute 240 seconds DOB 144 second DOM 5 0 minute 300 seconds DOB 150 second DOM During routine operation of the unit with no power interruptions the compressor will operate on demand...

Страница 20: ...e units Since many installation specific situations can affect the pressure readings this information should only be used by certified technicians as a guide for evaluating proper system performance T...

Страница 21: ...w Side High Side 139 315 143 335 146 357 148 381 151 405 154 430 156 455 159 482 161 510 164 539 W12AAAD 75 deg DB 62 deg WB Low Side High Side 125 314 129 334 132 357 134 380 137 404 139 429 141 454...

Отзывы: