background image

Manual 2100-618 
Page 

18 of 21

START UP

IMPORTANT INSTALLER NOTE

For improved start up performance, wash the indoor coil 
with a dishwasher detergent.

SERVICE HINTS

  1.  Caution owner to maintain clean air filters at all 

times.  Also not to needlessly close off supply and 

return air registers.  This reduces airflow through the 

system which shortens equipment service life as well 
as increasing operation costs.

  2.  The unit is equipped with a high pressure cut out 

switch.

  3.  Check all power fuses or circuit breakers to be sure 

they are the correct rating.

  4.  Periodic cleaning of the outdoor coil to permit full 

and unrestricted airflow circulation is essential.

HIGH and LOW PRESSURE SWITCH

The W12AAA models are supplied with a remote reset 
high and low pressure switch.  If tripped, this pressure 
switch may be reset by turning the thermostat off then 
back on again.

SEQUENCE OF OPERATION

HEATING

 – Circuit R-Y makes at thermostat pulling 

in compressor contactor, starting the compressor 
and outdoor motor.  The G (indoor motor) circuit 
is automatically completed on any call for cooling 
operation or can be energized by manual fan switch 
on subbase for constant air circulation.  On a call for 
heating, circuit R-W1 make at the thermostat pulling in 
heat contact for the strip heat and blower operation.

COMPRESSOR CONTROL MODULE

The compressor control is an anti-short cycle/lockout 
timer with high and low pressure switch monitoring and 
alarm relay output.

Adjustable Delay on Make and Break Timer

On initial power up or any time power is interrupted to 
the unit the 

delay on make

 period begins, which will be 

2 minutes plus 10% of the 

delay on break

 setting.  When 

the delay on make is complete and the high pressure 
switch (and low pressure switch if employed) is closed, 
the compressor contactor is energized.  Upon shutdown 
the delay on break time starts and prevents restart until 
the delay on break and delay on make periods have 
expired.

During routine operation of the unit with no power 
interruptions the compressor will operate on demand 
with no delay.

High Pressure Switch and Lockout Sequence

If the high pressure switch opens, the compressor 
contactor will de-energize immediately.  The lockout 
timer will go into a 

soft lockout

 and stay in soft lockout 

until the high pressure switch closes 

and

 the delay on 

break time has expired.  If the high pressure switch opens 
again in this same operating cycle the unit will go into 
manual lockout condition and the alarm relay circuit 
will energize.  Recycling the wall thermostat resets the 
manual lockout.

Low Pressure Switch, Bypass  and Lockout 
Sequence

If the low pressure switch opens for more than 120 
seconds, the compressor contactor will de-energize 
and go into a soft lockout.  Regardless the state of the 
low pressure switch, the contactor will reenergize after 
the delay on make time delay has expired.  If the low 
pressure switch remains open, or opens again for longer 
that 120 seconds, the unit will go into manual lockout 
condition and the alarm relay circuit will energize.  
Recycling the wall thermostat resets the manual lockout.

Alarm Relay Output

Alarm terminal is output connection for applications 
where alarm relay is employed.  This terminal is powered 
whenever compressor is locked out due to HPC or LPC 
sequences as described.

NOTE:  Both high and low pressure switch controls 

are inherently automatic reset devices.  The 
high pressure switch and low pressure switch 

cut out and cut in settings are fixed by specific 

air conditioner or heat pump unit model.  The 
lockout features, both soft and manual, are a 
function of the Compressor Control Module.

Содержание W12AAA

Страница 1: ...MOUNTED PACKAGE AIR CONDITIONERS Model W12AAA INSTALLATION INSTRUCTIONS Manual 2100 618 Supersedes NEW File Tab 16 Date 06 04 14 Bard Manufacturing Company Inc Bryan Ohio 43506 Since 1914 Moving ahea...

Страница 2: ...2 Fresh Air Damper 7 Figure 3 Mounting Instructions 9 Figure 4 Wall Mounting Instructions 10 Figure 5 Wall Mounting Instructions 10 Figure 6 Common Wall Mounting Installations 11 Figure 7 Low Voltage...

Страница 3: ...ter and Summer Air Conditioning Duct Design for ACCA Manual D Residential Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning...

Страница 4: ...t Control J X Low Ambient Control and Alarm Relay VOLTS PHASE A 230 208 60 1 D 240 220 50 1 K 115 60 1 KW 00 No KW 02 2 2 KW 03 3 6 KW 05 5 0 KW 0Z Circuit Breaker Only VENTILATION OPTIONS X Barometri...

Страница 5: ...FLOW IS BLOW THRU 19 72 19 72 3 88 31 06 20 43 ELECTRICAL ENTRANCE SHIPPING LOCATION OPTIONAL TOP RAIN FLASHING DRAIN HOSE 10 00 5 00 30 13 17 00 5 00 32 00 22 25 25 750 2 50 MIS 3599 FRONT VIEW BACK...

Страница 6: ...a proposed installation should be based on heat loss gain calculation made according to methods of Air Conditioning Contractors of America ACCA The air duct should be installed in accordance with the...

Страница 7: ...a single story structure FILTERS A one inch throwaway filter is supplied with each unit The filter slides into position making it easy to service This filter can be serviced from the outside by remov...

Страница 8: ...ations if desired See Figure 3 3 Hook top rain flashing under back bend of top Top rain flashing is shipped attached to the back of the unit on the right side 4 Position unit in opening and secure wit...

Страница 9: ...LIED FOAM AIR SEAL WALL WALL STRUCTURE MIS 3600 FLANGES AND UNDER TOP FLASHING AT TIME OF INSTALLATION SUPPLY AIR DUCT RETURN AIR NOTE IT IS RECOMMENDED THAT A BEAD OF SILICONE CAULKING BE PLACED BEHI...

Страница 10: ...Manual 2100 618 Page 10 of 21 FIGURE 5 WALL MOUNTING INSTRUCTIONS FIGURE 4 WALL MOUNTING INSTRUCTIONS SEE FIGURE 3 MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS...

Страница 11: ...Manual 2100 618 Page 11 of 21 FIGURE 6 COMMON WALL MOUNTING INSTALLATIONS...

Страница 12: ...be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high starting current of the compressor motor See Table 2 for electrical specific...

Страница 13: ...h ECONWM Y1 terminal is the 1st Stage compressor input for cooling 2 Stage units only No ECONWM Y2 terminal is the 2nd Stage compressor input for cooling 2 Stage units only No ECONWM W1 terminal is th...

Страница 14: ...ONFIGURATION FROM HEAT PUMP TO HEAT COOL MUST BE CONFIGURED TO PROGRAMMABLE AND FAN SET TO PROGRAMMED FAN FOR THE A OUTPUT TO FUNCTION DURING SCHEDULED OCCUPIED PERIODS 4 2 1 OPTIONAL VENT PACKAGE 3 R...

Страница 15: ...NON PROGRAMMABLE THERMOSTAT ADD JUMPER FROM G TO E ONLY IF OPTIONAL CO2 CONTROLLER IS INSTALLED CHANGE SYSTEM TYPE SET UP FUNCTION 1 FROM 5 2 HEAT 1 COOL HEAT PUMP TO 6 2 HEAT 2 COOL CONVENTIONAL ADD...

Страница 16: ...A O B 3 A C UNIT Change model configuration from heat pump to heat cool and must be configured for W2 Factory Jumper Installed Must be energized to enable minimum position NOTE Economizer Control Def...

Страница 17: ...leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be used...

Страница 18: ...ssure switch and low pressure switch if employed is closed the compressor contactor is energized Upon shutdown the delay on break time starts and prevents restart until the delay on break and delay on...

Страница 19: ...38 second DOM 4 0 minute 240 seconds DOB 144 second DOM 5 0 minute 300 seconds DOB 150 second DOM During routine operation of the unit with no power interruptions the compressor will operate on demand...

Страница 20: ...e units Since many installation specific situations can affect the pressure readings this information should only be used by certified technicians as a guide for evaluating proper system performance T...

Страница 21: ...w Side High Side 139 315 143 335 146 357 148 381 151 405 154 430 156 455 159 482 161 510 164 539 W12AAAD 75 deg DB 62 deg WB Low Side High Side 125 314 129 334 132 357 134 380 137 404 139 429 141 454...

Отзывы: