background image

Manual 2100-618 
Page 

6 of 21

SHIPPING DAMAGE

Upon receipt of equipment, the carton should be checked 
for external signs of shipping damage.  If damage is 
found, the receiving party must contact the last carrier 
immediately, preferably in writing, requesting inspection 
by the carrier’s agent.

GENERAL

The equipment covered in this manual is to be installed 
by trained, experienced service and installation 
technicians.

The refrigerant system is completely assembled and 
charged.  All internal wiring is complete.

The unit is designed for use with or without duct work.  
Flanges are provided for attaching the supply and return 
air ducts.

These instructions explain the recommended method to 
install the air cooled self-contained unit and the electrical 
wiring connections to the unit.

These instructions and any instructions packaged with 
any separate equipment required to make up the entire 
air conditioning system should be carefully read before 
beginning the installation.  Note particularly “Starting 
Procedure” and any tags and/or labels attached to the 
equipment.

While these instructions are intended as a general 
recommended guide, they do not supersede any national 
and/or local codes in any way.  Authorities having 
jurisdiction should be consulted before the installation 
is made.  See Page 3 for information on codes and 
standards.

Size of unit for a proposed installation should be based 
on heat loss/gain calculation made according to methods 
of Air Conditioning Contractors of America (ACCA).  
The air duct should be installed in accordance with the 
Standards of the National Fire Protection Association 
for the Installation of Air Conditioning and Ventilating 
Systems of Other Than Residence Type, NFPA No. 
90A, and Residence Type Warm Air Heating and Air 
Conditioning Systems, NFPA No. 90B.  Where local 
regulations are at a variance with instructions, installer 
should adhere to local codes.

j

  Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors.

 

Based on 75°C copper wire.  All wiring must conform to NEC and all local codes.

 

These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors.  Refer to the National  

  

Electrical Code (latest revision), article 310 for power conductor sizing.

CAUTION:

  When more than one field power conductor circuit is run through one conduit, the conductors must be 

derated.  Pay special attention to note 8 of table 310 regarding Ampacity Adjustment Factors when more than 3 

conductors are in a raceway.

TABLE  2

ELECTRICAL HEAT SPECIFICATIONS

SINGLE CIRCUIT

Models

Rated Volts 

and  

Phase

No. Field 

Power 

Circuits

Minimum 

Circuit 

Ampacity

j

Maximum 

External Fuse 

or Circuit 

Breaker

Field Power 

Wire Size

Ground  

Wire Size

W12AAAA0Z

A03
A05

230/208-1

1
1
1

9

20
27

15
20
30

14
12
10

14
12
10

W12AAAK00

K02

115-1

1
1

17
26

30
30

10
10

10
10

W12AAAD00

D03

240/220-1

1
1

9

20

15
20

14
12

14
12

Содержание W12AAA

Страница 1: ...MOUNTED PACKAGE AIR CONDITIONERS Model W12AAA INSTALLATION INSTRUCTIONS Manual 2100 618 Supersedes NEW File Tab 16 Date 06 04 14 Bard Manufacturing Company Inc Bryan Ohio 43506 Since 1914 Moving ahea...

Страница 2: ...2 Fresh Air Damper 7 Figure 3 Mounting Instructions 9 Figure 4 Wall Mounting Instructions 10 Figure 5 Wall Mounting Instructions 10 Figure 6 Common Wall Mounting Installations 11 Figure 7 Low Voltage...

Страница 3: ...ter and Summer Air Conditioning Duct Design for ACCA Manual D Residential Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning...

Страница 4: ...t Control J X Low Ambient Control and Alarm Relay VOLTS PHASE A 230 208 60 1 D 240 220 50 1 K 115 60 1 KW 00 No KW 02 2 2 KW 03 3 6 KW 05 5 0 KW 0Z Circuit Breaker Only VENTILATION OPTIONS X Barometri...

Страница 5: ...FLOW IS BLOW THRU 19 72 19 72 3 88 31 06 20 43 ELECTRICAL ENTRANCE SHIPPING LOCATION OPTIONAL TOP RAIN FLASHING DRAIN HOSE 10 00 5 00 30 13 17 00 5 00 32 00 22 25 25 750 2 50 MIS 3599 FRONT VIEW BACK...

Страница 6: ...a proposed installation should be based on heat loss gain calculation made according to methods of Air Conditioning Contractors of America ACCA The air duct should be installed in accordance with the...

Страница 7: ...a single story structure FILTERS A one inch throwaway filter is supplied with each unit The filter slides into position making it easy to service This filter can be serviced from the outside by remov...

Страница 8: ...ations if desired See Figure 3 3 Hook top rain flashing under back bend of top Top rain flashing is shipped attached to the back of the unit on the right side 4 Position unit in opening and secure wit...

Страница 9: ...LIED FOAM AIR SEAL WALL WALL STRUCTURE MIS 3600 FLANGES AND UNDER TOP FLASHING AT TIME OF INSTALLATION SUPPLY AIR DUCT RETURN AIR NOTE IT IS RECOMMENDED THAT A BEAD OF SILICONE CAULKING BE PLACED BEHI...

Страница 10: ...Manual 2100 618 Page 10 of 21 FIGURE 5 WALL MOUNTING INSTRUCTIONS FIGURE 4 WALL MOUNTING INSTRUCTIONS SEE FIGURE 3 MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS...

Страница 11: ...Manual 2100 618 Page 11 of 21 FIGURE 6 COMMON WALL MOUNTING INSTALLATIONS...

Страница 12: ...be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high starting current of the compressor motor See Table 2 for electrical specific...

Страница 13: ...h ECONWM Y1 terminal is the 1st Stage compressor input for cooling 2 Stage units only No ECONWM Y2 terminal is the 2nd Stage compressor input for cooling 2 Stage units only No ECONWM W1 terminal is th...

Страница 14: ...ONFIGURATION FROM HEAT PUMP TO HEAT COOL MUST BE CONFIGURED TO PROGRAMMABLE AND FAN SET TO PROGRAMMED FAN FOR THE A OUTPUT TO FUNCTION DURING SCHEDULED OCCUPIED PERIODS 4 2 1 OPTIONAL VENT PACKAGE 3 R...

Страница 15: ...NON PROGRAMMABLE THERMOSTAT ADD JUMPER FROM G TO E ONLY IF OPTIONAL CO2 CONTROLLER IS INSTALLED CHANGE SYSTEM TYPE SET UP FUNCTION 1 FROM 5 2 HEAT 1 COOL HEAT PUMP TO 6 2 HEAT 2 COOL CONVENTIONAL ADD...

Страница 16: ...A O B 3 A C UNIT Change model configuration from heat pump to heat cool and must be configured for W2 Factory Jumper Installed Must be energized to enable minimum position NOTE Economizer Control Def...

Страница 17: ...leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be used...

Страница 18: ...ssure switch and low pressure switch if employed is closed the compressor contactor is energized Upon shutdown the delay on break time starts and prevents restart until the delay on break and delay on...

Страница 19: ...38 second DOM 4 0 minute 240 seconds DOB 144 second DOM 5 0 minute 300 seconds DOB 150 second DOM During routine operation of the unit with no power interruptions the compressor will operate on demand...

Страница 20: ...e units Since many installation specific situations can affect the pressure readings this information should only be used by certified technicians as a guide for evaluating proper system performance T...

Страница 21: ...w Side High Side 139 315 143 335 146 357 148 381 151 405 154 430 156 455 159 482 161 510 164 539 W12AAAD 75 deg DB 62 deg WB Low Side High Side 125 314 129 334 132 357 134 380 137 404 139 429 141 454...