background image

Manual

2100-519C

Page

11 of 42

FRESH AIR INTAKE

This unit is equipped with a fresh air damper assembly.
The damper blade is locked in the closed position when
the unit is shipped from the Factory.  To allow the
damper to operate remove the two plastic locking pins,
one on each end of the blade.  This will allow for
maximum fresh airflow.  The damper blade will now
open when the indoor blower is operating.  If less than
maximum fresh airflow is required, reinsert the plastic
pins to limit damper blade opening to desired level.
Two extra pins are provided (taped to the inside of the
assembly) which may be used to hold the blade in some
position other than minimum or maximum position.
This fresh air assembly is located in the rear of  the unit
and to gain access to make these adjustments remove
the air filter service door.

All capacity, efficiency and cost of operation
information as required for Department of Energy
“Energyguide” Fact Sheets are based upon the fresh air
blank-off plate in place and is recommended for
maximum energy efficiency.

The blank-off plate is available upon request from the
factory and is installed in place of the fresh air damper
shipped with each unit.

For details on energy recovery ventilation see Page 30.

SERVICE LIGHT

The unit is equipped with a service light which signals
the user that service is required.  The light is located in
the upper control panel and is visible only when the
hinged service/filter access door is open.

The 

Service Unit

 light indicates that the unit has been

shut off by a high or low pressure device.  This indicates
that the unit needs to be serviced.  See Page 33 for details.

CONDENSATE DRAIN

There are two drain connections on the unit.  The rear
drain is the primary drain, and is located on the right
lower rear panel of the unit.  The optional side drain is
located on the bottom right side of the unit.  The side
drain is shipped with a plug installed.

The 

side drain

 requires a water trap for proper drainage.

See Figure 9.  The drain can be routed through the floor
or through the wall.  

If the drain is to be routed through

an unconditioned space, it must be protected from
freezing

 The drain line must be able to be removed from

the unit if it is necessary to remove the unit from the wall.
When the side drain is used, the plug must be removed
and installed in the rear drain outlet.

The 

rear drain

 can be used with wall thickness of up to

10 inches where a water trap can be installed between
the unit and the interior wall.  See Figure 10.  The trap
cannot extend beyond the edge of the unit or it will
interfere with the wall mounting bracket.  The drain can
be routed through the floor or through the wall.  If the
drain is routed through the wall, the drain line must be
positioned such that it will not interfere with  the sleeve
flange or the grille.  See Figure 11.  

If the drain is to be

routed through an unconditioned space, it must be
protected from freezing

.

OPTIONAL REAR DRAIN KITS

Optional Rear Drain Kit, Bard Model QCDS48A, is
also available for these products.  The optional rear
drain kit offers multiple benefits that include the
following:

• Allows unit to be rolled away from the sleeve

without having to disconnect any hard plumbing
connections.

• Allows indoor coil condensate to be easily

connected to Rear Drain Box while bypassing the
outdoor coil drain pan.  This aids in minimizing the
potential for biological growth to occur by
minimizing the standing water and exposing it to
warm temperatures.

See Figures 12A, 12B, 12C and 12D.

The drain box permanently mounts onto the wall sleeve
and is then either piped directly outdoors, or can be
piped vertically.  The Q-Tec unit is then equipped with
fittings on the rear of the unit that slide into the drain
box as it is wheeled towards the wall sleeve.

NOTE:

 

On models equipped with a refrigerant

subcooler in the lower drain pan may experience a 2-
3% decrease in cooling performance and efficiency
when the indoor condensate is routed around the
outdoor coil drain pan/subcooler assembly.  Unit rated
performance and efficiency are with the indoor
condensate routed to the outdoor coil pan.

There is also a heated version of the rear drain box
available (Model #QCDS48H) for installation in
northern climates where freezing may occur.

Содержание Q-TEC Q24H1

Страница 1: ...0H1 Q36H1 Q42H1 Q48H1 Q60H1 Q TEC SERIES PACKAGED HEAT PUMP INSTALLATION INSTRUCTIONS Bard Manufacturing Company Inc Bryan Ohio 43506 Since 1914 Moving ahead just as planned Manual 2100 519C Supersede...

Страница 2: ...of Unit From Skid 7 Figure 4 Unit on Appliance Cart for Moving 8 Figure 5 Installation With Free Blow Plenum 9 Figure 6 Ducted Application 9 Figure 7 Supply Duct Connections 10 Figure 8 Filter Locatio...

Страница 3: ...mer Manual N Air Conditioning Low Pressure Low Velocity ACCA Manual D or Duct System Design Manual Q Winter and Summer Air Conditioning FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Condition...

Страница 4: ...8 6 3 0 5 1 9 4 0 6 8 6 3 0 5 1 9 4 Q TEC Series General Information Q TEC MODEL NOMENCLATURE Q 36 H 1 A 10 X X V X X X SPECIAL UNITS L Low Ampacity Circuit REVISION VOLTS PHASE A 230 208 60 1 B 230 2...

Страница 5: ...4 0 5 0 5 8 8 8 8 0 1 0 1 0 1 0 1 Z 0 B 1 H 2 4 Q 6 0 B 9 0 B 5 5 1 B 3 8 0 2 0 3 2 1 1 1 1 5 2 3 4 2 5 3 5 5 3 0 5 0 6 0 6 8 8 6 6 0 1 0 1 0 1 0 1 Z 0 C 1 H 2 4 Q 6 0 C 9 0 C 5 5 1 C 3 0 6 4 1 1 1 1...

Страница 6: ...Manual 2100 519C Page 6 of 42 FIGURE 1 UNIT DIMENSIONS Q24H1 Q30H1 Q36H1 Q42H1 Q48H1 Q60H1...

Страница 7: ...emoved to provide a place to hold the unit The unit can be slid forward on the skid until the front wheels hang over the edge of the skid See Figure 3 B The unit can be tipped forward and slid down th...

Страница 8: ...structions and any instructions packaged with any separate equipment required to make up the entire air conditioning system should be carefully read before beginning the installation Note particularly...

Страница 9: ...Manual 2100 519C Page 9 of 42 FIGURE 6 DUCTEDAPPLICATION FIGURE 5 INSTALLATION WITH FREE BLOW PLENUM...

Страница 10: ...either free blow with the use of QPB Plenum Box or a duct supply air system The QPB and QPBHW Plenum Box mounts on top of the unit and has both vertically and horizontally adjustable louvers on the f...

Страница 11: ...oor or through the wall If the drain is to be routed through an unconditioned space it must be protected from freezing The drain line must be able to be removed from the unit if it is necessary to rem...

Страница 12: ...AR DRAIN WATER TRAP FIGURE 11 REAR DRAIN TOP VIEW WALL MAXIMUM 10 FOR REAR DRAIN COUPLINGS NOT SHOWN BUT RECOMMENDED FOR EASE OF REMOVABILITY FOR SERVICE SLEEVE DRAIN LINE WALL BRACKET UNIT FIGURE 9 O...

Страница 13: ...Manual 2100 519C Page 13 of 42 MIS 2469 DRAIN BOX WALL SLEEVE OVERFLOW TUBE CAULK AROUND TUBE FIGURE 12A...

Страница 14: ...PLASTIC PIPE NIPPLE HORIZONTAL TO FLOOR TIGHTEN THREADS SO TEE IS THREADS APPLY TEFLON TAPE TO REAR DRAIN CONNECTION IN Q Tec PRODUCT 1 2 SLIP X 1 2 SLIP X 3 4 NPT TEE SUPPLIED WITH DRAIN BOX KIT PLU...

Страница 15: ...Manual 2100 519C Page 15 of 42 REMOVE KNOCK OUT FOR INDOOR DRAIN HOSE CONNECTOR MIS 2471 FIGURE 12C If Used...

Страница 16: ...RAIN PAN MOVE HOSE FROM ATTACHMENT IN LOWER DRAIN PAN AND SLIDE ONTO DRAIN BOX BARB FITTING SECURING WITH SUPPLIED CLAMP IF OUTDOOR PAN IS BYPASSED WILL REDUCE RISK OF ALGAE GROWTH IN THE OUTDOOR PAN...

Страница 17: ...OUNTING METHOD 1 BOTTOM TRIM PIECE BOTTOM TRIM EXTENSION MOUNTING BRACKET SIDE TRIM 2 PCS SIDE TRIM 2 PCS CABINET SIDE PANEL ENLARGED VIEW OF MOUNTING BRACKET SHOWING SLEEVE TO CABINET ATTACHMENT MOUN...

Страница 18: ...eck both sides of the unit as it is being rolled to keep it centered in the sleeve Also check the alignment to the mounting brackets This unit must be level from side to side If adjustments are necess...

Страница 19: ...gram will be marked Use Copper Conductors Only These instructions MUST BE adhered to Refer to the National Electrical Code NEC for complete current carrying capacity data on the various insulation gra...

Страница 20: ...talled ventilation option E terminal or pin 3 of P2 is the emergency heat input This terminal energizes the emergency heat relay R O F S N O I T C E N N O C E G A T L O V W O L L O R T N O C C D D y l...

Страница 21: ...g o r P n o N e l b a m m a r g o r P l a n o i t n e v n o C r o P H r e v o e g n a h c l a u n a M r o o t u A 8 5 0 3 0 4 8 1 5 1 1 D 0 2 2 5 H T t a e H e g a t s 2 l o o C e g a t s 2 e l b a m...

Страница 22: ...hermostat TH522001151 MIS 2687 Rc REMOTE THERMOSTAT WIRING DIAGRAM X THERMOSTAT OPTION Low Voltage Terminal Block 9 10 6 5 3 11 8 Plug 2 1 12 7 2 G 4 1 1 Factory installed jumper A FIGURE 17A REMOTE T...

Страница 23: ...2A1008 Out Bard Part 8403 058 Thermostat Orange G Brown Green Optional CO2 Controller Relay Part 8201 062 4 Terminal Block 9 10 6 5 3 11 8 Plug 2 1 Factory installed jumper G 12 Low Voltage Mount rela...

Страница 24: ...ck White 1 G O B Yellow Brown White 11 8 4 R Temp and Humidity Controller Orange Pink 4102 062 A L FIGURE 18 UNIT MOUNTED THERMOSTAT WIRING DIAGRAM A THERMOSTAT OPTION NOTE On option X or A the CS2000...

Страница 25: ...White Blue 9 W1 E 10 6 Temp and Humidity Controller PART 8403 060 5 Black White G O B 3 11 8 4102 060 R Y1 Plug 2 C W2 1 Yellow 12 Red Yellow Brown 7 Orange A Brown White 4 FIGURE 19 UNIT MOUNTED THE...

Страница 26: ...k White G O B 3 11 8 4102 059 R Y1 Plug 2 C W2 1 Yellow 12 Red Yellow Brown 7 A Brown White 2 4 Black White Red White Brown White Orange Orange Orange Green Brown Yellow Black Red Red White Black Whit...

Страница 27: ...iple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be...

Страница 28: ...or damage due to phase reversal The phase monitor in this unit is equipped with two LEDs If the Y signal is present at the phase monitor and phases are correct the green LED will light and the compres...

Страница 29: ...the top center screw only from the cabinet side panel g Remove screws that attach the duct work to the unit flanges This unit is equipped with four rollers mounted to the base For ease of pulling uni...

Страница 30: ...be raised up and the bottom can be pulled toward the front of the unit and removed VENT OPTIONS BAROMETRIC FRESH AIR DAMPER Standard Before starting make sure the power has been turned off The return...

Страница 31: ...Manual 2100 519C Page 31 of 42 FIGURE 21 FRESH AIR DAMPER REMOVAL MOUNTING SCREW...

Страница 32: ...Manual 2100 519C Page 32 of 42 FIGURE 22 QERV REMOVAL MOUNTING SCREWS FRONT FILL LOWER BLOWER ASSEMBLY POWER CONNECTOR POWER CONNECTORS...

Страница 33: ...e control has a bypass to eliminate nuisance lockout on cold start up The bypass timer should be set to 120 seconds and this is to assure there is no nuisance tripping of the low pressure control duri...

Страница 34: ...P terminals shorted for the speedup to be completed and the defrost cycle to start As soon as the defrost cycle kicks in remove the shorting instrument from the SPEEDUP terminals Otherwise the timing...

Страница 35: ...42 120 SW 1 SW 2 TIME SEC OFF OFF ON ON OFF ON OFF ON 30 60 180 LOW PRESSURE BYPASS TIMER SWITCH FACTORY SETTING 120 SECONDS ACCUMULATED RUN TIME SELECTOR FACTORY SETTING 30 MIN MIS 2684 A ON OFF FIGU...

Страница 36: ...r o t i c a p a c r o t o M r o t i c a p a c e c a l p e R r o t i c a p a c d e t r o h s r o n e p o r o f k c e h C g n i t a r r o t i c a p a c k c e h C e v l a v g n i s r e v e R e z i g r e...

Страница 37: ...4 6 3 5 1 5 0 2 5 4 1 5 0 5 8 2 0 9 4 0 9 5 4 1 0 0 2 6 4 5 5 8 4 4 4 5 5 3 4 5 9 2 2 4 7 7 0 1 4 8 9 8 9 3 7 5 7 8 3 2 5 6 7 3 3 8 5 6 3 8 4 5 5 3 5 4 5 4 3 4 7 5 3 3 4 3 6 2 3 3 2 7 1 3 0 4 8 0 3 0...

Страница 38: ...it s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Check...

Страница 39: ...2 0 CONTROL control in cast aluminum can with air vents on the back of the can WITH AN ECM 2 3 CONTROL control containing black potting for water protection in black deep drawn steel case with no ven...

Страница 40: ...5 7 0 5 7 0 5 7 NOTE These units are equipped with a variable speed ECM indoor motor that automatically adjust itself to maintain approximately the same rate of indoor airflow in both heating and coo...

Страница 41: ...1 9 6 3 3 3 1 9 8 3 4 3 1 0 1 4 6 3 1 4 3 4 7 3 1 9 5 4 8 3 1 6 8 4 0 4 1 4 1 5 2 4 1 3 4 5 B D 0 8 B W 7 6 e d i S w o L e d i S h g i H 0 4 1 0 6 3 1 4 1 8 7 3 2 4 1 9 9 3 3 4 1 1 2 4 3 4 1 8 4 4 7...

Страница 42: ...1 9 6 3 3 6 9 6 4 3 0 0 1 5 5 3 4 0 1 5 6 3 7 0 1 4 7 3 1 H 2 4 Q 0 7 e d i S w o L e d i S h g i H 0 3 2 7 2 8 3 3 8 2 6 4 4 9 2 4 5 5 0 3 1 6 7 1 3 8 6 8 2 3 6 7 9 3 3 3 8 0 5 3 0 9 2 6 3 6 9 3 7 3...

Отзывы: