background image

Manual

2100-519C

Page

39 of 42

TROUBLESHOOTING  GE  ECM™ MOTORS CONT’D.

Replacing ECM Control Module

To replace the control module for the GE variable-speed indoor blower
motor you need to take the following steps:

1. You MUST have the correct replacement module.  The controls are

factory programmed for specific operating modes.  Even though they look
alike, different modules may have completely different functionality.

USING THE WRONG CONTROL MODULE VOIDS ALL PRODUCT
WARRANTIES AND MAY PRODUCE UNEXPECTED RESULTS.

2. Begin by removing AC power from the furnace or air handler being

serviced.  

DO NOT WORK ON THE MOTOR WITH AC POWER

APPLIED.  

To avoid electric shock from the motor’s capacitors, disconnect

power and wait at least 5 minutes before opening motor.

3. It is usually not necessary to remove the motor from the blower

assembly.  However, it is recommended that the whole blower assembly,
with the motor, be removed from the furnace/air handler.  (Follow the
manufacturer’s procedures).  Unplug the two cable connectors to the motor.
There are latches on each connector.  

DO NOT PULL ON THE WIRES.

The plugs remove easily when properly released.

4. Locate the two standard ¼" hex head bolts at the rear of the control

housing (at the back end of the control opposite the shaft end).  

Refer

to Figure 25.  

Remove these two bolts from the motor and control

assembly while holding the motor in a way that will prevent the motor
or control from falling when the bolts are removed.  If an ECM2.0
control is being replaced (recognized by an aluminum casting rather
that a deep-drawn black steel can housing the electronics), remove
only the hex-head bolts.  

DO NOT REMOVE THE TORX-HEAD

SCREWS.

5. The control module is now free of mechanical attachment to the

motor endshield but is still connected by a plug and three wires inside
the control.  Carefully rotate the control to gain access to the plug at
the control end of the wires.  With thumb and forefinger, reach the
latch holding the plug to the control and release it by squeezing the
latch tab and the opposite side of the connector plug and gently pulling
the plug out of the connector socket in the control.  

DO NOT PULL

ON THE WIRES.  GRIP THE PLUG ONLY.

6. The control module is now completely detached from the motor.

Verify with a standard ohmmeter that the resistance from each motor
lead (in the motor plug just removed) to the motor shell is >100K
ohms.  

Refer to Figure 26.  

(Measure to unpainted motor end plate.)  If

any motor lead fails this test, do not proceed to install the control
module.  

THE MOTOR IS DEFECTIVE AND MUST BE

REPLACED.

  Installing the new control module will cause it to fail

also.

7. Verify that the replacement control is correct for your

application.  Refer to the manufacturer's authorized replacement list.

USING THE WRONG CONTROL WILL RESULT IN
IMPROPER OR NO BLOWER OPERATION.

  Orient the control

module so that the 3-wire motor plug can be inserted into the socket in
the control.  Carefully insert the plug and press it into the socket until
it latches.  

A SLIGHT CLICK WILL BE HEARD WHEN

PROPERLY INSERTED.

  Finish installing the replacement control per

one of the three following paragraphs, 8a, 8b or 8c.

8a. 

IF REPLACING AN ECM 2.0 CONTROL

 (control in cast

aluminum can with air vents on the back of the can) 

WITH AN ECM

2.3 CONTROL

 (control containing black potting for water protection

in black deep-drawn steel case with no vents in the bottom of the can),
locate the two through-bolts and plastic tab that are packed with the
replacement control.  Insert the plastic tab into the slot at the perimeter
of the open end of the can so that the pin is located on the inside of the
perimeter of the can.  Rotate the can so that the tab inserts into the tab
locater hole in the endshield of the motor.  Using the two through-
bolts provided with the replacement control, reattach the can to the
motor.

THE TWO THROUGH-BOLTS PROVIDED WITH THE
REPLACEMENT ECM 2.3 CONTROL ARE SHORTER THAN
THE BOLTS ORIGINALLY REMOVED FROM THE ECM 2.0
CONTROL AND MUST BE USED IF SECURE ATTACHMENT
OF THE CONTROL TO THE MOTOR IS TO BE ACHIEVED.

DO NOT OVERTIGHTEN THE BOLTS.

8b. 

IF REPLACING AN ECM 2.3 CONTROL

 

WITH AN ECM

2.3 CONTROL

, the plastic tab and shorter through-bolts are not needed.

The control can be oriented in two positions 180° apart.  

MAKE SURE

THE ORIENTATION YOU SELECT FOR REPLACING THE
CONTROL ASSURES THE CONTROL'S CABLE CONNECTORS
WILL BE LOCATED DOWNWARD IN THE APPLICATION SO
THAT WATER CANNOT RUN DOWN THE CABLES AND INTO
THE CONTROL.

  Simply orient the new control to the motor's

endshield, insert bolts, and tighten.  

DO NOT OVERTIGHTEN THE

BOLTS.

8c. 

IF REPLACING AN ECM 2.0 CONTROL WITH AN ECM 2.0

CONTROL 

(It is recommended that ECM 2.3 controls be used for all

replacements), 

the new control must be attached to the motor using

through bolts identical to those removed with the original control.  

DO

NOT OVERTIGHTEN THE BOLTS.

9. Reinstall the blower/motor assembly into the HVAC equipment.

Follow the manufacturer's suggested procedures.

10. Plug the 16-pin control plug into the motor.  The plug is keyed.

Make sure the connector is properly seated and latched.

11. Plug the 5-pin power connector into the motor.  Even though the

plug is keyed, 

OBSERVE THE PROPER ORIENTATION.  DO NOT

FORCE THE CONNECTOR.

  It plugs in very easily when properly

oriented.  

REVERSING THIS PLUG WILL CAUSE IMMEDIATE

FAILURE OF THE CONTROL MODULE.

12. Final installation check.  Make sure the motor is installed as follows:

a. Unit is as far INTO the blower housing as possible.
b.Belly bands are not on the control module or covering vent holes.
c. Motor connectors should be oriented between the 4 o’clock and 8

o’clock positions when the blower is positioned in its final
location and orientation.

d.Add a drip loop to the cables so that water cannot enter the motor

by draining down the cables.  

Refer to Figure 27.

The installation is now complete.  Reapply the AC power to the HVAC
equipment and verify that the new motor control module is working
properly.  Follow the manufacturer's procedures for disposition of the old
control module.

Motor

Motor OK when

R > 100k ohm

ECM 2.0

Only remove

Hex Head Bolts

Connector Orientation

Between 4 and 8 o'clock

Drip Loop

Back of

Control

Figure 5

Winding Test

Figure 4

Note:              
Use the shorter 
bolts and 
alignment pin 
supplied when 
replacing an 
ECM 2.0 
control.

Figure 3

ECM 
2.3/2.5

Power Connector
(5-pin)

Control Connector
(16-pin)

Hex-head Screws

Motor Connector
(3-pin)

Motor Connector
(3-pin)

Control Disassembly

Drip Loop

Push until

Latch Seats
Over Ramp

From Motor

Circuit

Board

Figure 26

Figure 25

Figure 27

Содержание Q-TEC Q24H1

Страница 1: ...0H1 Q36H1 Q42H1 Q48H1 Q60H1 Q TEC SERIES PACKAGED HEAT PUMP INSTALLATION INSTRUCTIONS Bard Manufacturing Company Inc Bryan Ohio 43506 Since 1914 Moving ahead just as planned Manual 2100 519C Supersede...

Страница 2: ...of Unit From Skid 7 Figure 4 Unit on Appliance Cart for Moving 8 Figure 5 Installation With Free Blow Plenum 9 Figure 6 Ducted Application 9 Figure 7 Supply Duct Connections 10 Figure 8 Filter Locatio...

Страница 3: ...mer Manual N Air Conditioning Low Pressure Low Velocity ACCA Manual D or Duct System Design Manual Q Winter and Summer Air Conditioning FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Condition...

Страница 4: ...8 6 3 0 5 1 9 4 0 6 8 6 3 0 5 1 9 4 Q TEC Series General Information Q TEC MODEL NOMENCLATURE Q 36 H 1 A 10 X X V X X X SPECIAL UNITS L Low Ampacity Circuit REVISION VOLTS PHASE A 230 208 60 1 B 230 2...

Страница 5: ...4 0 5 0 5 8 8 8 8 0 1 0 1 0 1 0 1 Z 0 B 1 H 2 4 Q 6 0 B 9 0 B 5 5 1 B 3 8 0 2 0 3 2 1 1 1 1 5 2 3 4 2 5 3 5 5 3 0 5 0 6 0 6 8 8 6 6 0 1 0 1 0 1 0 1 Z 0 C 1 H 2 4 Q 6 0 C 9 0 C 5 5 1 C 3 0 6 4 1 1 1 1...

Страница 6: ...Manual 2100 519C Page 6 of 42 FIGURE 1 UNIT DIMENSIONS Q24H1 Q30H1 Q36H1 Q42H1 Q48H1 Q60H1...

Страница 7: ...emoved to provide a place to hold the unit The unit can be slid forward on the skid until the front wheels hang over the edge of the skid See Figure 3 B The unit can be tipped forward and slid down th...

Страница 8: ...structions and any instructions packaged with any separate equipment required to make up the entire air conditioning system should be carefully read before beginning the installation Note particularly...

Страница 9: ...Manual 2100 519C Page 9 of 42 FIGURE 6 DUCTEDAPPLICATION FIGURE 5 INSTALLATION WITH FREE BLOW PLENUM...

Страница 10: ...either free blow with the use of QPB Plenum Box or a duct supply air system The QPB and QPBHW Plenum Box mounts on top of the unit and has both vertically and horizontally adjustable louvers on the f...

Страница 11: ...oor or through the wall If the drain is to be routed through an unconditioned space it must be protected from freezing The drain line must be able to be removed from the unit if it is necessary to rem...

Страница 12: ...AR DRAIN WATER TRAP FIGURE 11 REAR DRAIN TOP VIEW WALL MAXIMUM 10 FOR REAR DRAIN COUPLINGS NOT SHOWN BUT RECOMMENDED FOR EASE OF REMOVABILITY FOR SERVICE SLEEVE DRAIN LINE WALL BRACKET UNIT FIGURE 9 O...

Страница 13: ...Manual 2100 519C Page 13 of 42 MIS 2469 DRAIN BOX WALL SLEEVE OVERFLOW TUBE CAULK AROUND TUBE FIGURE 12A...

Страница 14: ...PLASTIC PIPE NIPPLE HORIZONTAL TO FLOOR TIGHTEN THREADS SO TEE IS THREADS APPLY TEFLON TAPE TO REAR DRAIN CONNECTION IN Q Tec PRODUCT 1 2 SLIP X 1 2 SLIP X 3 4 NPT TEE SUPPLIED WITH DRAIN BOX KIT PLU...

Страница 15: ...Manual 2100 519C Page 15 of 42 REMOVE KNOCK OUT FOR INDOOR DRAIN HOSE CONNECTOR MIS 2471 FIGURE 12C If Used...

Страница 16: ...RAIN PAN MOVE HOSE FROM ATTACHMENT IN LOWER DRAIN PAN AND SLIDE ONTO DRAIN BOX BARB FITTING SECURING WITH SUPPLIED CLAMP IF OUTDOOR PAN IS BYPASSED WILL REDUCE RISK OF ALGAE GROWTH IN THE OUTDOOR PAN...

Страница 17: ...OUNTING METHOD 1 BOTTOM TRIM PIECE BOTTOM TRIM EXTENSION MOUNTING BRACKET SIDE TRIM 2 PCS SIDE TRIM 2 PCS CABINET SIDE PANEL ENLARGED VIEW OF MOUNTING BRACKET SHOWING SLEEVE TO CABINET ATTACHMENT MOUN...

Страница 18: ...eck both sides of the unit as it is being rolled to keep it centered in the sleeve Also check the alignment to the mounting brackets This unit must be level from side to side If adjustments are necess...

Страница 19: ...gram will be marked Use Copper Conductors Only These instructions MUST BE adhered to Refer to the National Electrical Code NEC for complete current carrying capacity data on the various insulation gra...

Страница 20: ...talled ventilation option E terminal or pin 3 of P2 is the emergency heat input This terminal energizes the emergency heat relay R O F S N O I T C E N N O C E G A T L O V W O L L O R T N O C C D D y l...

Страница 21: ...g o r P n o N e l b a m m a r g o r P l a n o i t n e v n o C r o P H r e v o e g n a h c l a u n a M r o o t u A 8 5 0 3 0 4 8 1 5 1 1 D 0 2 2 5 H T t a e H e g a t s 2 l o o C e g a t s 2 e l b a m...

Страница 22: ...hermostat TH522001151 MIS 2687 Rc REMOTE THERMOSTAT WIRING DIAGRAM X THERMOSTAT OPTION Low Voltage Terminal Block 9 10 6 5 3 11 8 Plug 2 1 12 7 2 G 4 1 1 Factory installed jumper A FIGURE 17A REMOTE T...

Страница 23: ...2A1008 Out Bard Part 8403 058 Thermostat Orange G Brown Green Optional CO2 Controller Relay Part 8201 062 4 Terminal Block 9 10 6 5 3 11 8 Plug 2 1 Factory installed jumper G 12 Low Voltage Mount rela...

Страница 24: ...ck White 1 G O B Yellow Brown White 11 8 4 R Temp and Humidity Controller Orange Pink 4102 062 A L FIGURE 18 UNIT MOUNTED THERMOSTAT WIRING DIAGRAM A THERMOSTAT OPTION NOTE On option X or A the CS2000...

Страница 25: ...White Blue 9 W1 E 10 6 Temp and Humidity Controller PART 8403 060 5 Black White G O B 3 11 8 4102 060 R Y1 Plug 2 C W2 1 Yellow 12 Red Yellow Brown 7 Orange A Brown White 4 FIGURE 19 UNIT MOUNTED THE...

Страница 26: ...k White G O B 3 11 8 4102 059 R Y1 Plug 2 C W2 1 Yellow 12 Red Yellow Brown 7 A Brown White 2 4 Black White Red White Brown White Orange Orange Orange Green Brown Yellow Black Red Red White Black Whit...

Страница 27: ...iple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be...

Страница 28: ...or damage due to phase reversal The phase monitor in this unit is equipped with two LEDs If the Y signal is present at the phase monitor and phases are correct the green LED will light and the compres...

Страница 29: ...the top center screw only from the cabinet side panel g Remove screws that attach the duct work to the unit flanges This unit is equipped with four rollers mounted to the base For ease of pulling uni...

Страница 30: ...be raised up and the bottom can be pulled toward the front of the unit and removed VENT OPTIONS BAROMETRIC FRESH AIR DAMPER Standard Before starting make sure the power has been turned off The return...

Страница 31: ...Manual 2100 519C Page 31 of 42 FIGURE 21 FRESH AIR DAMPER REMOVAL MOUNTING SCREW...

Страница 32: ...Manual 2100 519C Page 32 of 42 FIGURE 22 QERV REMOVAL MOUNTING SCREWS FRONT FILL LOWER BLOWER ASSEMBLY POWER CONNECTOR POWER CONNECTORS...

Страница 33: ...e control has a bypass to eliminate nuisance lockout on cold start up The bypass timer should be set to 120 seconds and this is to assure there is no nuisance tripping of the low pressure control duri...

Страница 34: ...P terminals shorted for the speedup to be completed and the defrost cycle to start As soon as the defrost cycle kicks in remove the shorting instrument from the SPEEDUP terminals Otherwise the timing...

Страница 35: ...42 120 SW 1 SW 2 TIME SEC OFF OFF ON ON OFF ON OFF ON 30 60 180 LOW PRESSURE BYPASS TIMER SWITCH FACTORY SETTING 120 SECONDS ACCUMULATED RUN TIME SELECTOR FACTORY SETTING 30 MIN MIS 2684 A ON OFF FIGU...

Страница 36: ...r o t i c a p a c r o t o M r o t i c a p a c e c a l p e R r o t i c a p a c d e t r o h s r o n e p o r o f k c e h C g n i t a r r o t i c a p a c k c e h C e v l a v g n i s r e v e R e z i g r e...

Страница 37: ...4 6 3 5 1 5 0 2 5 4 1 5 0 5 8 2 0 9 4 0 9 5 4 1 0 0 2 6 4 5 5 8 4 4 4 5 5 3 4 5 9 2 2 4 7 7 0 1 4 8 9 8 9 3 7 5 7 8 3 2 5 6 7 3 3 8 5 6 3 8 4 5 5 3 5 4 5 4 3 4 7 5 3 3 4 3 6 2 3 3 2 7 1 3 0 4 8 0 3 0...

Страница 38: ...it s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Check...

Страница 39: ...2 0 CONTROL control in cast aluminum can with air vents on the back of the can WITH AN ECM 2 3 CONTROL control containing black potting for water protection in black deep drawn steel case with no ven...

Страница 40: ...5 7 0 5 7 0 5 7 NOTE These units are equipped with a variable speed ECM indoor motor that automatically adjust itself to maintain approximately the same rate of indoor airflow in both heating and coo...

Страница 41: ...1 9 6 3 3 3 1 9 8 3 4 3 1 0 1 4 6 3 1 4 3 4 7 3 1 9 5 4 8 3 1 6 8 4 0 4 1 4 1 5 2 4 1 3 4 5 B D 0 8 B W 7 6 e d i S w o L e d i S h g i H 0 4 1 0 6 3 1 4 1 8 7 3 2 4 1 9 9 3 3 4 1 1 2 4 3 4 1 8 4 4 7...

Страница 42: ...1 9 6 3 3 6 9 6 4 3 0 0 1 5 5 3 4 0 1 5 6 3 7 0 1 4 7 3 1 H 2 4 Q 0 7 e d i S w o L e d i S h g i H 0 3 2 7 2 8 3 3 8 2 6 4 4 9 2 4 5 5 0 3 1 6 7 1 3 8 6 8 2 3 6 7 9 3 3 3 8 0 5 3 0 9 2 6 3 6 9 3 7 3...

Отзывы: