SERVICE HINTS

1. Caution user to maintain clean air filters at all

times.  Also, not to needlessly close off supply air
registers.  This may reduce airflow through the
system, which shortens equipment service life as
well as increasing operating costs and noise
levels.

2. Switching to heating cycle at 75°F or higher

outside temperature may cause a nuisance trip of
the remote reset high pressure switch.  Turn
thermostat off, then on to reset the high pressure
switch.

3. The heat pump wall thermostats perform multiple

functions.  Be sure that all function switches are
correctly set for the desired operating mode
before trying to diagnose any reported service
problems.

4. Check all power fuses or circuit breakers to be

sure they are the correct rating.

5. Periodic cleaning of the outdoor coil to permit

full and unrestricted airflow circulation is
essential.

6. Some service requires the need to remove the unit

from the wall including replacement of the indoor
coil and/or the outdoor coil.  Also, servicing the
outdoor fan motor or fan blade will require
removing the unit from the wall if the unit is
installed at a height that is not easily accessible
from the outside of the building.

In order to remove the unit from the wall the
following procedure must be used:

a. Turn off power to the unit at the remote

location.  Some units may have more than one
power supply.

b. Disconnect field wiring at unit terminal block

and remove from unit.

c. Disconnect condensate drain.

d. Remove the lower skirting around the unit.

e. Remove wall mounting brackets from wall on

each side of the unit and/or remove the
internal bolts in the lower section securing unit
to wall sleeve.

f. If unit is attached to duct work, remove upper

cabinet extension by removing the top center
screw only from the cabinet side panel.

g. Remove screws that attach the duct work to

the unit flanges.

This unit is equipped with four rollers
mounted to the base.  For ease of pulling unit
out from the wall, you may want to remove
the bottom service door which requires
removal of the return air panel, and grip the
front flange of the base pan then pull straight
out.

7. Annual maintenance is required to make sure that

all of the systems are functioning properly.

a. Check to make sure that the drains are not

obstructed in any way.

b. Remove any debris in the condenser section of

the unit.

c. Inspect and clean mist eliminator as described

below.

d. Inspect and wash outdoor coil as necessary.

MIST ELIMINATOR SERVICE

A mist eliminator is supplied with the wall sleeve.  The
mist eliminator is constructed of an aluminum frame
and mesh.  The mist eliminator is located in the top
section of the wall sleeve and can be removed from the
inside of the building without removing the unit from
the wall.  This requires that the ventilation package be
removed.

It is recommended that the mist eliminator be inspected
annually and serviced as required.  The mist eliminator
can be inspected from the outside of the building by
looking through the outdoor grille.  The mist eliminator
can be serviced from the outside by using a vacuum
cleaner.  The outdoor grille must be removed.  Use the
vacuum to remove dirt and debris from the surface of
the mist eliminator.  If additional cleaning is required,
the mist eliminator will have to be removed from the
sleeve.

The ventilation package will have to be removed to gain
access to the mist eliminator.  If the blank off plate
option is used, it is not necessary to service the mist
eliminator.  The steps necessary to remove each of the
vent options are listed on the following pages.

The mist eliminator can be cleaned by washing with
soap and water.  The excess water should be shaken off
the mist eliminator before it is reinstalled.

Содержание Q-TEC Q24H1

Страница 1: ...0H1 Q36H1 Q42H1 Q48H1 Q60H1 Q TEC SERIES PACKAGED HEAT PUMP INSTALLATION INSTRUCTIONS Bard Manufacturing Company Inc Bryan Ohio 43506 Since 1914 Moving ahead just as planned Manual 2100 519C Supersede...

Страница 2: ...of Unit From Skid 7 Figure 4 Unit on Appliance Cart for Moving 8 Figure 5 Installation With Free Blow Plenum 9 Figure 6 Ducted Application 9 Figure 7 Supply Duct Connections 10 Figure 8 Filter Locatio...

Страница 3: ...mer Manual N Air Conditioning Low Pressure Low Velocity ACCA Manual D or Duct System Design Manual Q Winter and Summer Air Conditioning FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Condition...

Страница 4: ...8 6 3 0 5 1 9 4 0 6 8 6 3 0 5 1 9 4 Q TEC Series General Information Q TEC MODEL NOMENCLATURE Q 36 H 1 A 10 X X V X X X SPECIAL UNITS L Low Ampacity Circuit REVISION VOLTS PHASE A 230 208 60 1 B 230 2...

Страница 5: ...4 0 5 0 5 8 8 8 8 0 1 0 1 0 1 0 1 Z 0 B 1 H 2 4 Q 6 0 B 9 0 B 5 5 1 B 3 8 0 2 0 3 2 1 1 1 1 5 2 3 4 2 5 3 5 5 3 0 5 0 6 0 6 8 8 6 6 0 1 0 1 0 1 0 1 Z 0 C 1 H 2 4 Q 6 0 C 9 0 C 5 5 1 C 3 0 6 4 1 1 1 1...

Страница 6: ...Manual 2100 519C Page 6 of 42 FIGURE 1 UNIT DIMENSIONS Q24H1 Q30H1 Q36H1 Q42H1 Q48H1 Q60H1...

Страница 7: ...emoved to provide a place to hold the unit The unit can be slid forward on the skid until the front wheels hang over the edge of the skid See Figure 3 B The unit can be tipped forward and slid down th...

Страница 8: ...structions and any instructions packaged with any separate equipment required to make up the entire air conditioning system should be carefully read before beginning the installation Note particularly...

Страница 9: ...Manual 2100 519C Page 9 of 42 FIGURE 6 DUCTEDAPPLICATION FIGURE 5 INSTALLATION WITH FREE BLOW PLENUM...

Страница 10: ...either free blow with the use of QPB Plenum Box or a duct supply air system The QPB and QPBHW Plenum Box mounts on top of the unit and has both vertically and horizontally adjustable louvers on the f...

Страница 11: ...oor or through the wall If the drain is to be routed through an unconditioned space it must be protected from freezing The drain line must be able to be removed from the unit if it is necessary to rem...

Страница 12: ...AR DRAIN WATER TRAP FIGURE 11 REAR DRAIN TOP VIEW WALL MAXIMUM 10 FOR REAR DRAIN COUPLINGS NOT SHOWN BUT RECOMMENDED FOR EASE OF REMOVABILITY FOR SERVICE SLEEVE DRAIN LINE WALL BRACKET UNIT FIGURE 9 O...

Страница 13: ...Manual 2100 519C Page 13 of 42 MIS 2469 DRAIN BOX WALL SLEEVE OVERFLOW TUBE CAULK AROUND TUBE FIGURE 12A...

Страница 14: ...PLASTIC PIPE NIPPLE HORIZONTAL TO FLOOR TIGHTEN THREADS SO TEE IS THREADS APPLY TEFLON TAPE TO REAR DRAIN CONNECTION IN Q Tec PRODUCT 1 2 SLIP X 1 2 SLIP X 3 4 NPT TEE SUPPLIED WITH DRAIN BOX KIT PLU...

Страница 15: ...Manual 2100 519C Page 15 of 42 REMOVE KNOCK OUT FOR INDOOR DRAIN HOSE CONNECTOR MIS 2471 FIGURE 12C If Used...

Страница 16: ...RAIN PAN MOVE HOSE FROM ATTACHMENT IN LOWER DRAIN PAN AND SLIDE ONTO DRAIN BOX BARB FITTING SECURING WITH SUPPLIED CLAMP IF OUTDOOR PAN IS BYPASSED WILL REDUCE RISK OF ALGAE GROWTH IN THE OUTDOOR PAN...

Страница 17: ...OUNTING METHOD 1 BOTTOM TRIM PIECE BOTTOM TRIM EXTENSION MOUNTING BRACKET SIDE TRIM 2 PCS SIDE TRIM 2 PCS CABINET SIDE PANEL ENLARGED VIEW OF MOUNTING BRACKET SHOWING SLEEVE TO CABINET ATTACHMENT MOUN...

Страница 18: ...eck both sides of the unit as it is being rolled to keep it centered in the sleeve Also check the alignment to the mounting brackets This unit must be level from side to side If adjustments are necess...

Страница 19: ...gram will be marked Use Copper Conductors Only These instructions MUST BE adhered to Refer to the National Electrical Code NEC for complete current carrying capacity data on the various insulation gra...

Страница 20: ...talled ventilation option E terminal or pin 3 of P2 is the emergency heat input This terminal energizes the emergency heat relay R O F S N O I T C E N N O C E G A T L O V W O L L O R T N O C C D D y l...

Страница 21: ...g o r P n o N e l b a m m a r g o r P l a n o i t n e v n o C r o P H r e v o e g n a h c l a u n a M r o o t u A 8 5 0 3 0 4 8 1 5 1 1 D 0 2 2 5 H T t a e H e g a t s 2 l o o C e g a t s 2 e l b a m...

Страница 22: ...hermostat TH522001151 MIS 2687 Rc REMOTE THERMOSTAT WIRING DIAGRAM X THERMOSTAT OPTION Low Voltage Terminal Block 9 10 6 5 3 11 8 Plug 2 1 12 7 2 G 4 1 1 Factory installed jumper A FIGURE 17A REMOTE T...

Страница 23: ...2A1008 Out Bard Part 8403 058 Thermostat Orange G Brown Green Optional CO2 Controller Relay Part 8201 062 4 Terminal Block 9 10 6 5 3 11 8 Plug 2 1 Factory installed jumper G 12 Low Voltage Mount rela...

Страница 24: ...ck White 1 G O B Yellow Brown White 11 8 4 R Temp and Humidity Controller Orange Pink 4102 062 A L FIGURE 18 UNIT MOUNTED THERMOSTAT WIRING DIAGRAM A THERMOSTAT OPTION NOTE On option X or A the CS2000...

Страница 25: ...White Blue 9 W1 E 10 6 Temp and Humidity Controller PART 8403 060 5 Black White G O B 3 11 8 4102 060 R Y1 Plug 2 C W2 1 Yellow 12 Red Yellow Brown 7 Orange A Brown White 4 FIGURE 19 UNIT MOUNTED THE...

Страница 26: ...k White G O B 3 11 8 4102 059 R Y1 Plug 2 C W2 1 Yellow 12 Red Yellow Brown 7 A Brown White 2 4 Black White Red White Brown White Orange Orange Orange Green Brown Yellow Black Red Red White Black Whit...

Страница 27: ...iple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be...

Страница 28: ...or damage due to phase reversal The phase monitor in this unit is equipped with two LEDs If the Y signal is present at the phase monitor and phases are correct the green LED will light and the compres...

Страница 29: ...the top center screw only from the cabinet side panel g Remove screws that attach the duct work to the unit flanges This unit is equipped with four rollers mounted to the base For ease of pulling uni...

Страница 30: ...be raised up and the bottom can be pulled toward the front of the unit and removed VENT OPTIONS BAROMETRIC FRESH AIR DAMPER Standard Before starting make sure the power has been turned off The return...

Страница 31: ...Manual 2100 519C Page 31 of 42 FIGURE 21 FRESH AIR DAMPER REMOVAL MOUNTING SCREW...

Страница 32: ...Manual 2100 519C Page 32 of 42 FIGURE 22 QERV REMOVAL MOUNTING SCREWS FRONT FILL LOWER BLOWER ASSEMBLY POWER CONNECTOR POWER CONNECTORS...

Страница 33: ...e control has a bypass to eliminate nuisance lockout on cold start up The bypass timer should be set to 120 seconds and this is to assure there is no nuisance tripping of the low pressure control duri...

Страница 34: ...P terminals shorted for the speedup to be completed and the defrost cycle to start As soon as the defrost cycle kicks in remove the shorting instrument from the SPEEDUP terminals Otherwise the timing...

Страница 35: ...42 120 SW 1 SW 2 TIME SEC OFF OFF ON ON OFF ON OFF ON 30 60 180 LOW PRESSURE BYPASS TIMER SWITCH FACTORY SETTING 120 SECONDS ACCUMULATED RUN TIME SELECTOR FACTORY SETTING 30 MIN MIS 2684 A ON OFF FIGU...

Страница 36: ...r o t i c a p a c r o t o M r o t i c a p a c e c a l p e R r o t i c a p a c d e t r o h s r o n e p o r o f k c e h C g n i t a r r o t i c a p a c k c e h C e v l a v g n i s r e v e R e z i g r e...

Страница 37: ...4 6 3 5 1 5 0 2 5 4 1 5 0 5 8 2 0 9 4 0 9 5 4 1 0 0 2 6 4 5 5 8 4 4 4 5 5 3 4 5 9 2 2 4 7 7 0 1 4 8 9 8 9 3 7 5 7 8 3 2 5 6 7 3 3 8 5 6 3 8 4 5 5 3 5 4 5 4 3 4 7 5 3 3 4 3 6 2 3 3 2 7 1 3 0 4 8 0 3 0...

Страница 38: ...it s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Check...

Страница 39: ...2 0 CONTROL control in cast aluminum can with air vents on the back of the can WITH AN ECM 2 3 CONTROL control containing black potting for water protection in black deep drawn steel case with no ven...

Страница 40: ...5 7 0 5 7 0 5 7 NOTE These units are equipped with a variable speed ECM indoor motor that automatically adjust itself to maintain approximately the same rate of indoor airflow in both heating and coo...

Страница 41: ...1 9 6 3 3 3 1 9 8 3 4 3 1 0 1 4 6 3 1 4 3 4 7 3 1 9 5 4 8 3 1 6 8 4 0 4 1 4 1 5 2 4 1 3 4 5 B D 0 8 B W 7 6 e d i S w o L e d i S h g i H 0 4 1 0 6 3 1 4 1 8 7 3 2 4 1 9 9 3 3 4 1 1 2 4 3 4 1 8 4 4 7...

Страница 42: ...1 9 6 3 3 6 9 6 4 3 0 0 1 5 5 3 4 0 1 5 6 3 7 0 1 4 7 3 1 H 2 4 Q 0 7 e d i S w o L e d i S h g i H 0 3 2 7 2 8 3 3 8 2 6 4 4 9 2 4 5 5 0 3 1 6 7 1 3 8 6 8 2 3 6 7 9 3 3 3 8 0 5 3 0 9 2 6 3 6 9 3 7 3...

Отзывы: