APPENDIX 2: TEC-EYE ARCHITECTURE
Screen
Menu Item
Value
Description
Status Screen
The Status screen is the default screen on startup, and
anytime more than 5 minutes has elapsed from last change.
(Use UP/DOWN arrow keys to scroll)
Displays current data
RAT
°F
Current return air temperature
SAT
°F
Current supply Air temperature
OAT
°F
Current outdoor air temperature
OAH
%
Current outdoor air humidity
Dewpoint
°F
Current temperature of dewpoint
Blower
Off/On
Displays status of blower
Damper
%
Displays percentage of current opening
Master Control
Master Control
Current operational status, "Running
Stand Alone" if communication lost
Status
Unit On
D-Series controller board is currently
active, "Off by Keyboard" if disabled by
TEC-EYE
Main Menu
Main Menu screen(s) allows access to operational
programming, access by pressing MENU key at any time.
(MENU key to enter, use UP/DOWN arrow keys to scroll)
On/Off Unit
Unit Address
1
Physical address of controller
Power by Display On/Off
Status
On
"OFF by Keyboard" system has been
turned off at controller
Setpoint
All setpoint changes are
limited to 60 minutes
Cooling Setpoint
77°F
Heating Setpoint
60°F
Cooling Stg. Diff.
5°F
Heating Stg. Diff.
2°F
FreeCool
55°F
FreeCool Enable
50°F
Differential
10°F
DC OA-Return Diff.
10°F
Supply Temp Low Limit
45°F
Damper Time
150 seconds
Time alloted before damper fail is
realized
Runtest Time
76 seconds
Freeze Temp Low Limit
30°F
Temperature sensed by Freezestat
which initiates compressor shutdown
CAUTION:
The Bard DC-FCU System has been pre-programmed with what is widely considered to be the best
settings for efficiency and operation. Any changes to internal programming through the LC-Series Controller or the
TEC-EYE not covered within this manual may cause the systems to operate improperly, cause internal damage to
the HVAC units, cause the shelter to overheat, or other very serious consequences. Although complete controller
programming architecture for both the LC-Controller and TEC-EYE has been provided, going outside the boundaries
of what has been covered in this manual not recommended.
Содержание D36A2P/BLD.10304
Страница 6: ...Manual 2100 620A Page 6 of 107 ...
Страница 7: ...Manual 2100 620A Page 7 of 107 SECTION 1 INSTALLATION INSTRUCTIONS ...
Страница 39: ...Manual 2100 620A Page 39 of 107 SECTION 2 SERVICE INSTRUCTIONS ...
Страница 73: ...Manual 2100 620A Page 73 of 107 SECTION 3 PARTS MANUAL ...
Страница 88: ...Manual 2100 620A Page 88 of 107 BARD LINKTM PLC LEAD LAG CONTROLLER SEXP 755 6 4 8 7 2 9 1 5 3 ...
Страница 90: ...Manual 2100 620A Page 90 of 107 ...
Страница 91: ...Manual 2100 620A Page 91 of 107 SECTION 4 APPENDICES ...