Manual 2100-620A
Page
104 of 107
APPENDIX 2: TEC-EYE ARCHITECTURE (CONT.)
Screen
Menu Item
Value
Description
D2 Status
Closed
Current status of filter switch input
(closed means no input)
High Pressure DI 3
Off
"On" to allow artificial manipulation of
high pressure switch input
Manual Position
Open/Closed
Change to "Closed" to artifically create
high pressure input
D3 Status
Closed
Current status of high pressure input
(open means no input)
Low Pressure DI 4
Off
"On" to allow artificial manipulation of
low pressure switch input
Manual Position
Open/Closed
Change to "Closed" to artifically create
low pressure input
D3 Status
Closed
Current status of low pressure input
(open means no input)
Blower Status DI 5
Off
"On" to allow artificial manipulation of
blower status input
Manual Position
Open/Closed
Change to "Closed" to artifically create
blower status input
D3 Status
Closed
Current status of blower status input
(open means no input)
Damper Switch Status DI 6
Off
"On" to allow artificial manipulation of
damper switch status input
Manual Position
Open/Closed
Change to "Closed" to artificially create
damper switch status input
D3 Status
Closed
Current status of damper switch status
input (open means no input)
Relay Outputs
Cooling Stg 1 Manual Relay 2 Off
"On" to allow artificial manipulation of
cooling stage 1 relay action
Manual Position
On/Off
Change to "On" to artificially force
cooling stage 1 relay
Relay 2 Status
Off
Current status of cooling stage 1 relay
(off means no relay action)
Cooling Stg 2 Manual Relay 3 Off
"On" to allow artificial manipulation of
cooling stage 2 relay action
Manual Position
On/Off
Change to "On" to artificially force
cooling stage 2 relay
Relay 3 Status
Off
Current status of cooling stage 2 relay
(off means no relay action)
Heating Manual Relay 4
Off
"On" to allow artificial manipulation of
heating relay action
Manual Position
On/Off
Change to "On" to artificially force
heating relay
Relay 4 Status
Off
Current status of heating relay (off
means no relay action)
Blower Manual Relay 4
Off
"On" to allow artificial manipulation of
blower relay action
Содержание D36A2P/BLD.10304
Страница 6: ...Manual 2100 620A Page 6 of 107 ...
Страница 7: ...Manual 2100 620A Page 7 of 107 SECTION 1 INSTALLATION INSTRUCTIONS ...
Страница 39: ...Manual 2100 620A Page 39 of 107 SECTION 2 SERVICE INSTRUCTIONS ...
Страница 73: ...Manual 2100 620A Page 73 of 107 SECTION 3 PARTS MANUAL ...
Страница 88: ...Manual 2100 620A Page 88 of 107 BARD LINKTM PLC LEAD LAG CONTROLLER SEXP 755 6 4 8 7 2 9 1 5 3 ...
Страница 90: ...Manual 2100 620A Page 90 of 107 ...
Страница 91: ...Manual 2100 620A Page 91 of 107 SECTION 4 APPENDICES ...