![Bard D36A2P/BLD.10304 Скачать руководство пользователя страница 36](http://html1.mh-extra.com/html/bard/d36a2p-bld-10304/d36a2p-bld-10304_installation-and-service-instructions-manual_474567036.webp)
Manual 2100-620A
Page
36 of 107
SYSTEM START-UP
FIGURE 1.29
Bard-Link
TM
Controller Display
ALARM KEY
Allows viewing of active alarms
Silences audible alarms
Resets active alarms
MENU KEY
Allows entry to Main Menu
ESCAPE KEY
Returns to previous menu level
Cancels a changed entry
UP KEY
Steps to next screen in the display menu
Changes (increases) the value of a modifiable field
ENTER KEY
Accepts current value of a modifiable field
Advances cursor
DOWN KEY
Steps back to previous screen in the display menu
Changes (decreases) the value of a modifiable field
1. Set Controller Date and Time
1) Shut down all breakers to system, both wall-
mount units and the Bard-Link
TM
controller.
2) Restore power (both AC and DC) to the two
wall-mount units.
3) Turn on power to the Bard-Link
TM
controller.
There is a forty (40) second delay prior to
any function (other than display backlight)
becoming active. The Status screen is the
default screen when the controller has power.
4) Access the Main Menu by pressing the Menu
key.
5) Press the UP or DOWN keys to scroll to the
Clock/Scheduler menu. Press the ENTER key
(see Figure 1.30).
6)
Move the cursor to the Date line by pressing
the ENTER key. Press the UP or DOWN keys to
change the date. The Day line will automatically
change when the date has been altered.
7) Press the ENTER key to move to the Hour line.
Press the UP or DOWN keys to change the
time. Press the ENTER key to set the time.
8) Press the ESCAPE several times to return to
the Status menu.
FIGURE 1.31
Status Display Showing Units "Online"
FIGURE 1.30
Clock/Scheduler Menu
2. Verify Communication to Units
Check controller display to see that both units are
"ON-LINE" (see Figure 1.31). This typically takes 3-4
minutes after controller is powered.
DOWN KEY
ALARM KEY
MENU KEY
UP KEY
ENTER KEY
ESCAPE KEY
For shelter applications involving only a single
DUAL-TEC™ DC Free Cooling Unit, see page 38.
Содержание D36A2P/BLD.10304
Страница 6: ...Manual 2100 620A Page 6 of 107 ...
Страница 7: ...Manual 2100 620A Page 7 of 107 SECTION 1 INSTALLATION INSTRUCTIONS ...
Страница 39: ...Manual 2100 620A Page 39 of 107 SECTION 2 SERVICE INSTRUCTIONS ...
Страница 73: ...Manual 2100 620A Page 73 of 107 SECTION 3 PARTS MANUAL ...
Страница 88: ...Manual 2100 620A Page 88 of 107 BARD LINKTM PLC LEAD LAG CONTROLLER SEXP 755 6 4 8 7 2 9 1 5 3 ...
Страница 90: ...Manual 2100 620A Page 90 of 107 ...
Страница 91: ...Manual 2100 620A Page 91 of 107 SECTION 4 APPENDICES ...