Manual 2100-620A
Page
34 of 107
FIGURE 1.27
LC1000/LC1500 Wiring Diagram
MIS-3632
+
48VDC
24VDC
- +
-
11
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35
14
HT
RELAY
LT
A1
A2
A1
A1
A2
RELAY
HF
12
22
14
11
21
24
22
12
JUMPER
TO
TB
26
TO
TB
25
TO
TB
28
TO
TB
27
TO
TB
30
22
TO
TB
29
24
TO
HT
11
21
TO
LT
11
TO
HF
11
BLUE/BLACK
BLACK/WHITE
BLACK/WHITE
BLACK/WHITE
BLUE/BLACK
BLUE/BLACK
BLACK/WHITE
GREEN
RED
RED
RED
BLUE/BLACK
BLUE/BLACK
BLUE/BLACK
RED/BLACK
BLACK/RED
BLUE
YELLOW
BLACK
RED
RELAY
SMK
RELAY
HYD
RELAY
GEN
A2
A1
A2
A1
A2
G G0
+V
DC
G
ND
+5
VR
EF
B1 B2 B3 B4 B5 B6 B7
G
ND
D
11
D
12
D
13 D14 D15 D16 D17
DIC1
G
ND Y1 Y2 Y3
+V
DC
A2
B
LA
CK
B
LA
CK
B
LA
CK
B
LA
CK
B
LA
CK
B
LA
CK
B
LA
CK
B
LA
CK
B
LA
CK
14
21
24
11
21
11
24
14
22
12
R
X-T
X-
R
X+
TX+
G
ND
VO
UT
R
X-T
X-
R
X+
TX+
G
ND
C1 N01 N
02
N
03
C2 N04 N05 N06
N
07
C3 NC7
A1
RED/BLACK
BLACK/RED
BLACK/RED
BLACK/RED
BLACK/RED
22
24
21
11
14
12
12
14
11
22
24
21
12
RELAY
MIS-3632
NO
NC
NO
COM
COM
NC
TO
HF
12
TO
LT
12
TO
HT
12
TB
#
Wire
Mark Description
NO NC
1
48+ 48+VDC Input
2
48- 48- VDC Input
3
24+ 24+VDC Input - hydrogen
4
24- 24- VDC Input - hydrogen
5
HA2 HA2 - Hydrogen ALR signal return
6
24+ 24+ VDC Input - Smoke
7
24- 24- VDC Input - Smoke
8
SA2 SA2 - Smoke ALR Signal return
9
24- 24- VDC
10 GA2 GA2 - Generator ALR signal return
11
B1 Indoor remote sensor
12 GND GND
13
B2 Spare Remote sensor 1
14 GND GND
15
B3 Spare Remote sensor 2
16 GND GND
17 S24 Smoke ALR relay contact
18 S21 Smoke ALR relay contact common
19 H24 Hydrogen ALR relay contact
20 H21 Hydrogen ALR relay contact common
21 G24 Generator ALR relay contact
22 G21 Generator ALR relay contact common
23 NO1 Lag unit run relay contact
24
C1 Lag unit run relay contact common
25 HT12 High Temp ALR relay contact
26 HT11 High Temp ALR relay contact common
27 LT12 Low Temp ALR relay contact
28 LT11 Low Temp ALR relay contact common
29 HF12 HVAC1 Fail ALR relay contact
30 HF11 HVAC1 Fail ALR relay contact common
31 NO7 HVAC2 Fail ALR relay contact
32
C3 HVAC2 Fail ALR relay contact common
33
R-
RS485 RX- / TX-
34
R+ RS485 RX+ / TX+
35 GND Drain Shield grounding w ire
Содержание D36A2P/BLD.10304
Страница 6: ...Manual 2100 620A Page 6 of 107 ...
Страница 7: ...Manual 2100 620A Page 7 of 107 SECTION 1 INSTALLATION INSTRUCTIONS ...
Страница 39: ...Manual 2100 620A Page 39 of 107 SECTION 2 SERVICE INSTRUCTIONS ...
Страница 73: ...Manual 2100 620A Page 73 of 107 SECTION 3 PARTS MANUAL ...
Страница 88: ...Manual 2100 620A Page 88 of 107 BARD LINKTM PLC LEAD LAG CONTROLLER SEXP 755 6 4 8 7 2 9 1 5 3 ...
Страница 90: ...Manual 2100 620A Page 90 of 107 ...
Страница 91: ...Manual 2100 620A Page 91 of 107 SECTION 4 APPENDICES ...