background image

SureCross™ DX80 Quick Start Guide

P/N 128185 Rev A

Banner Engineering Corp. • Minneapolis, MN U.S.A.

www.bannerengineering.com  •  Tel: 763.544.3164

16

On the Gateway, single-click button one to move across the top level 
menu options to the “Device Configuration” menu

To navigate to the *DVCFG 
(Device Configuration) menu, 
see page 6.

Single-click Gateway push button 2  

Single-click Gateway push button 1 to move to the Slave ID field.

Default value is 1

Single-click Gateway push button 2

The new Slave ID is defined 
by the current position of the 
rotary switches.

Using 0-9 on the left rotary switch and 1-9 on
the right switch, set the rotary switches to the
desired Slave ID

Select between 01 to 99. 
The factory default is set 
to 1. Change the Slave ID 
when running more than one 
network into the Modbus 
Master device.

Single-click Gateway push button 2 to save the new Slave ID.

Single-click Gateway push button 1 to move to the next menu option, the 
BAUD rate.

Single-click Gateway push button 2 to display the current setting. Single-
click Gateway push button 1 to cycle through the available options. Stop 
on the desired setting.

The options are 9600, 19200, 
38400. The factory default is 
19200.

Single-click Gateway push button 2 to save the new setting.

Single-click Gateway push button 1 to move to the next field, the PARITY 
field.

Single-click Gateway push button 2 to display the current setting. Single-
click Gateway push button 1 to cycle through the available options. Stop 
on the desired setting.

The options are NONE, 
EVEN, ODD. The factory 
default is NONE.

Single-click Gateway push button 2 to save the new setting.

Adjust the left rotary switch back to NID value.*
Adjust the right rotary switch back to zero.

Double-click Gateway push button 2 to return to the Device Configuration 
(*DVCFG) menu.

Click Gateway push button 1 until reaching the *RUN menu option.

SET SLA

VE ID

User Action

Display/Status

Notes

Setting the Slave ID, Baud Rate, and Parity

Similar to Network ID, the Slave ID, Baud Rate, and Parity parameters can be changed in the Device Con

fi

 guration (*DVCFG) system menu 

option. 
Follow the top level system menu through *DVCFG to the Slave ID (SLID) parameter. The LCD displays an alternating current value and new 
value for the parameter.

SET BAUD RA

TE

SET P

ARITY

Host Network - Gateway (con’t)

* To avoid losing the network connection between the Gateway and Nodes, reset the rotary switches 
back to their appropriate values before leaving the *DVCFG sub-menus. If the Gateway and Nodes 
lose their connection, the network may take up to 20 seconds to re-synchronize. 

Содержание SureCross DX80

Страница 1: ...e transmission path The Gateway receives a transmission from one Node and forwards it to another Node positioned to avoid the obstacle Host connected systems can contain up to 15 nodes within a single...

Страница 2: ...s chosen Push Button 2 Double click to select a menu and to enter manual scrolling mode Double click to move up one level at a time LED 1 and 2 Provide real time feedback to the user regarding RF link...

Страница 3: ...strial DX80 housing meets IEC IP67 standards Mounting Hole 10 M5 Clearance Mounting Holes accept metric M5 or UNC UNF 10 hardware DIN rail mount adapter bracket available Wiring Terminal Strip Wiring...

Страница 4: ...D SAVESNEW VALUES CUR XX Single click Button 2 Single click Button 2 ADJUSTROTARY SWITCHES TOSET SLAVEID SAVESNEW VALUES NID SLID BAUD PRTY Network ID Slave ID Baud Rate Parity Single click B1 NEW XX...

Страница 5: ...ouble click Btn 2 NEW XX Single click Button 2 Single click Button 2 SAVESNEW VALUES NADR Node Address NOD XX EC XX IGNORE ERROR Single click Button 1 LCD will display NO ERR if no error is detected S...

Страница 6: ...hexidecimal 0 F On the Gateway set the Right Rotary Switch to 0 A Device Address of 0 on the Gateway will display settings for the Gateway itself To view settings for another device on the network adj...

Страница 7: ...e is Gateway Device Address 0 Indicates the current status of the I O The display cycles through each I O point of the device then returns to RUN Apply power This reading occurs only when power is app...

Страница 8: ...LED 2 flashes Red When communication is established the Node s LED 1 flashes Green Status LED 1 LED 2 Power ON Green ON System Error Red Flash Red Flash Modbus Communication Active Yellow Flash Modbus...

Страница 9: ...ble install all devices in positions that optimize the percentage of YELLOW and GREEN data packets received Examine reception readings M R Y G of the Gateway at various locations Note that the numbers...

Страница 10: ...le surfaces Avoid mounting the units on flat or concave surfaces especially if the display will be pointing up Reduce Chemical Exposure Before installing the DX80 units in a chemically harsh environme...

Страница 11: ...loosely and Pushed against the flanged cover When removing or closing the rotary switch access cover manually twist the cover into position Do not allow cross threading between the cover and the DX80...

Страница 12: ...ically for optimal RF communication If necessary consider changing the height of the DX80 position to improve reception levels A wireless network can be hindered by radio interference and obstructions...

Страница 13: ...e o ring when it is damaged discolored or showing signs of wear The o ring should be Seated firmly against the threads without stretching to fit or without bulging loosely and Pushed against the flang...

Страница 14: ...of the battery holder mounted within the case After replacing the battery allow up to 60 seconds for the device to power up When removing the battery press the battery towards the negative terminal to...

Страница 15: ...shown below The following procedure is necessary to change the Gateway Slave ID Baud Rate and Parity Parameter Description Slave ID Default 1 Defines the slave number 01 99 for the serial Modbus RTU p...

Страница 16: ...19200 Single click Gateway push button 2 to save the new setting Single click Gateway push button 1 to move to the next field the PARITY field Single click Gateway push button 2 to display the current...

Страница 17: ...annerengineering com Tel 763 544 3164 SureCross DX80 Quick Start Guide 17 DX80 Gateway and Node Dimensions 65 0 mm 2 56 65 0 mm 2 56 80 3 mm 3 16 80 8 mm 3 18 60 mm 2 36 120 mm 4 72 127 mm 5 19 mm 0 7...

Страница 18: ...f each Node on the network If after a specified number of sequential polling cycles the Node does not acknowledge a message the Gateway considers the link with the Node timed out LCD displays on both...

Страница 19: ...devices After any system parameter changes cycle power to cause the devices to resync with the network If a Node device loses synchronization with the network it is programmed to try to acquire sync...

Страница 20: ...ling mode within RUN to freeze the I O status on the LCD display for the device in question Verify that when the input device changes state or changes value the LCD mirrors the behavior Also verify th...

Страница 21: ...X80 BWA HW 003 Tape PFTE Sealant BWA HW 004 Screws Cover Mount 8 32 x 3 4 18 8 SS Power DX81 Battery Pack Kit DX81 with mounting hardware DX121 Battery Pack Kit DX121 6 cells BWA BATT 001 Replacement...

Страница 22: ...rdance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does c...

Страница 23: ...and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular...

Страница 24: ...ring the warranty period This warranty does not cover damage or liability for the improper application of Banner products This warranty is in lieu of any other warranty either expressed or implied CAU...

Отзывы: