BA230
34
UK
Enables the single limit switch reading.
See the paragraph “USE OF THE LIMIT SWITCHES”
Enables the type 1 deceleration function.
Enables the water hammer function to help the release of the electric
lock/s in OPENING
Operation:
After the Start command, the sequence is:
- Electrical locks enabling
- 1 s pulse in closing
- opening
- After 2 s, electrical locks release
Disabled with sliding configuration
Enables the water hammer function to help the electrical lock/s release
in OPENING and CLOSING
Operation:
After the Start command, the sequence is:
- Electrical locks enabling
- Motor pulse in the electrical lock freeing direction
- Motion direction in the required direction
- After 2 s, electrical locks release
Disabled with sliding configuration
Enables the double limit switch reading.
See the paragraph “USE OF THE LIMIT SWITCHES”
Enables the type 2 deceleration function.
Disables the limit switch reading.
Enables the type 3 deceleration function.
Disables the deceleration function.
SAFETY DEVICES TEST
See also menu C20
LIMIT SWITCHES
DECELERATIONS
WATER HAMMER
C4
C5
C6
C7
Y
E1
Y1
Y1
Y2
E2
Y2
N
Y3
N
Disables the safety devices test.
N
The exclusion of SAFETY DEVICE by mean of the menu E3 excludes
the safety edge test.
PHASE 2: if the edge with N.C. contact is enabled, when the Start or
Pedestrian command is given, the power to the safety devices is cut off
for 0,5 s and then restored: : if the inputs of the safety devices open and
immediately return NC, the motors start, otherwise a fault is signalled
with 3 long flashes (2 sec.) of the flashing light.
PHASE 3: if the 8K2 edge is enabled, when the Start or the Pedestrian
command is given the SAFETY DEV input is tested (value 8K2). If the
value is not correct, the fault is signalled with 2 long flashes (2 sec.) of
the flashing light.
The indication of the fault detected will be only one (the first one to be
detected), even if there is more than one fault.
Disables the water hammer function.
N
Enables the final stroke in opening and closing
Operation:
At the end of the opening and closing time without decelerations, a 2 s
pulse with full power is given.
FINAL STROKE IN OPENING
AND CLOSING
C8
Y