Balluff Network Interface EtherNet/IP™
www.balluff.com
18
5
Integration
Possible values of MasterCycleTime and MiniCycleTime
Time base
encoding
Time Base
value
Calculation
Cycle Time
00
0.1 ms
Multiplier x Time Base
0.4 ms to 6.3 ms
01
0.4 ms
6.4 ms + Multiplier x Time Base
6.4 ms to 31.6 ms
10
1.6 ms
32.0 ms + Multiplier x Time Base
32.0 ms to 132.8 ms
11
Reserved
Reserved
Reserved
NOTE: The value 0.4 results from the minimum possible transmission time according to
A.3.7.
Validation
Settings
No validation
: validation deactivated, every device will be accepted.
Compatibility
: manufacturer ID and device ID are compared to the IO-Link device data.
Identity
: manufacturer ID and device ID and serial number are compared to the
IO-Link device data. The IO-Link communication is only started if there is a match.
Parameter Server
Enable
: data management functions enabled, parameter data and identification data of the
IO-Link device are stored permanently.
Disable
: data management functions disabled, stored parameter data and identification
data of the IO-Link device remain stored.
Deleted:
data management functions disabled, stored parameter data and identification
data of the IO-Link device are deleted.
Enable upload:
If only the upload is enabled, the master always starts an upload of the parameter data. In
this case, the upload is independent of the upload flag of the IO-Link device. If no data is
stored in the Master Port, an upload likewise takes place. (e.g. after deleting the data or
before the first data upload)
Enable download:
If only the download is enabled, the master always starts a download of the parameter data.
In this case, the download is likewise independent of the upload flag of the IO-Link device.
If no data is stored in the Master Port, however, an upload takes place first. (e.g. after
deleting the data or before the first data upload)
Enable upload and download:
If the upload and download are enabled, different parameter sets are distinguished
depending on the upload flag of the IO-Link device.
If no parameter data is stored in the IO-Link master port, an initial upload takes place.
(e.g. after deleting the data or before the first data upload)
If the upload flag is set on the IO-Link device, an upload of the parameter data always takes
place.
If no upload flag is set and parameter data has already been stored, a download of the
parameter data always takes place.