www.balluff.com
19
5
Integration
Note
After the upload of the parameter data, the vendor ID and device ID of the
connected IO-Link device are also still saved until the data records are deleted.
When the connected IO-Link device is started, a validation takes place. Thus,
only an IO-Link device of the same type can be used for the data management.
If an IO-Link device of a different type is to be used, the contents of the
parameter server must be deleted.
The data storage is supported only by IO-Link devices with IO-Link Revision 1.1.
Upload Flag on
the IO-Link
Device
The upload flag is needed to overwrite already saved data in the parameter server with new
parameter data of the same IO-Link device.
To enable the upload flag of an IO-Link device, the data value 0x05 must be entered in the
index 0x02, subindex 0.
(For information about configuration via IO-Link, refer to the "Web Server" chapter under
"Device Properties" or the "Configuration via Explicit Messages" chapter
under "IO-Link Device Parameterization")