background image

 

www.balluff.com   

   

  

 

21 

Configuration via Explicit Messages 

Rockwell 
Automation 
products that 
are compatible 
with 
QuickConnect 

 

 

 
Source: 
Allen-Bradley Ethernet/IP QuickConnect Application Technique 
Page 13 

 

Содержание BNI EIP-508-005-E002

Страница 1: ...BNI EIP 508 005 E002 EtherNet IP IP69 modules User s Guide...

Страница 2: ...8 4 2 Mechanical Data 8 4 3 Operating conditions 8 4 4 Electrical Data 8 4 5 Ethernet 9 4 6 Function indicators 9 Module Status 9 Port 10 5 Integration 11 5 1 Integration in Rockwell RS Logix 5000 11...

Страница 3: ...ocess Data 30 7 1 Process Data Inputs 30 Standard Input Data 30 IO Link Input Data 31 7 2 Process Data Outputs 32 Standard Output Data 32 IO Link Output Data 32 8 Web Server 33 8 1 General Information...

Страница 4: ...e indicated as numbers in parentheses 1 Step 1 2 Step 2 Syntax Numbers Decimal numbers are shown without additional information e g 123 Hexadecimal numbers are shown with the additional indicator hex...

Страница 5: ...ary to the instructions provided in this User s Guide Obligations of the owner operator The device is a piece of equipment in accordance with EMC Class A This device can produce RF noise The owner ope...

Страница 6: ...EtherNet IP port 1 2 Power OUT 3 Port 00 01 4 Port 02 03 5 Port 04 05 6 Port 06 07 7 Mounting hole 8 Port 14 15 9 Port 12 13 10 Port 10 11 11 Pin port LED signal status 12 Port 08 09 13 Status LED co...

Страница 7: ...V Module sensor supply 3 0 V GND module sensor and actuator supply 4 Note Provide sensor bus power and actuator power from separate power sources if possible The total current of the module must not...

Страница 8: ...t 2A 5 n a Attention Each output supplies maximum 2 A Note For the digital sensor inputs refer to guideline on inputs EN 61131 2 Type 2 Note The total current of the module must not exceed 9 A Note Un...

Страница 9: ...d in Supply voltage 7 8 4 pin connector female Input ports output ports M12 A coded 8x female Dimensions W x H x D in mm 70 x 228 x 44 1 Type of mounting Screw mounting with 2 mounting holes Weight Ap...

Страница 10: ...n UA Green Output power OK Red flashing Low output power 18V Red No output power 11V US Green Input power OK Red flashing Low input power 18V Mod Green flashing Incorrect or no configuration of the mo...

Страница 11: ...tatus of the input or output pins is 1 Red flashing Short circuit Short circuit between pin 1 and 3 Red Short circuit Short circuit at dedicated pin IO Link port Green IO Link IO Link communication ac...

Страница 12: ...gration 5 1 Integration in Rockwell RS Logix 5000 Here you see an example of how the module can be integrated into a Rockwell RS Logix 5000 First go offline Right click Ethernet on the correct scanner...

Страница 13: ...12 5 Integration Then select the general Ethernet module as the ETHERNET module in the communication path Now enter a user defined tag name to select the Data SINT general format enter the IP address...

Страница 14: ...www balluff com 13 5 Integration The new module and corresponding controller tags are generated automatically Then download the configuration...

Страница 15: ...ad is done you can observe and control the tags using the Controller Tags option Make sure you select the correct tag name which you configured beforehand The input output and configuration data for t...

Страница 16: ...XXXX BNI EIP 507 005 Z040 BNI EIP 527 005 Z040 Byte Slot Module part Description 0 1 1 Module General configuration for the entire module 2 25 2 IO Link port 0 Configuration of IO Link port 0 26 49 3...

Страница 17: ...6 Module Configuration BNI EIP 508 X05 XXX Byte Bit Description 7 6 5 4 3 2 1 0 0 P3 P2 P1 P0 Port function 0x00 Standard I O 0x01 IO Link 1 P7 P6 P5 P4 Module Configuration BNI EIP 507 005 Z040 BNI E...

Страница 18: ...a of the other IO Link ports are structured identically and described in the following Cycle Settings This parameter can be used to influence the IO Link communication speed Calculated using the multi...

Страница 19: ...management functions disabled stored parameter data and identification data of the IO Link device are deleted Enable upload If only the upload is enabled the master always starts an upload of the para...

Страница 20: ...contents of the parameter server must be deleted The data storage is supported only by IO Link devices with IO Link Revision 1 1 Upload Flag on the IO Link Device The upload flag is needed to overwri...

Страница 21: ...ation disabled Auto MDI X disabled Prepared for linear topology You can configure QuickConnect via the following class instance attribute of the explicit messages Class Instance Attribute Value 245 0x...

Страница 22: ...www balluff com 21 6 Configuration via Explicit Messages Rockwell Automation products that are compatible with QuickConnect Source Allen Bradley Ethernet IP QuickConnect Application Technique Page 13...

Страница 23: ...n between PLC and QuickConnect slave with crossover cable Slave to slave connection using patch cable For setting up the topology only the linear topology with a maximum of 20 modules on the tool side...

Страница 24: ...www balluff com 23 6 Configuration via Explicit Messages PLC Program Source Allen Bradley Ethernet IP QuickConnect Application Technique Page 29...

Страница 25: ...Balluff Network Interface EtherNet IP www balluff com 24 6 Configuration via Explicit Messages Source Allen Bradley Ethernet IP QuickConnect Application Technique Page 30...

Страница 26: ...www balluff com 25 6 Configuration via Explicit Messages Source Allen Bradley Ethernet IP QuickConnect Application Technique Page 31...

Страница 27: ...ing class instance attributes of the explicit messages Enable Disable Fault State Class Instance Attribute Value 9 0x09 1 m 6 0 Fault state disabled 1 Fault state enabled Fault State Action Class Inst...

Страница 28: ...ibes how an IO Link can be parameterized with explicit messages via Rockwell RSLogix 5000 For this purpose the MSG components in the PLC program are used Read IO Link Parameter Service Code Class Inst...

Страница 29: ...t Array Write enter which index is to be read In this example this is index 0x4E Destination Array Read shows the read out value In case of a configuration error the error code is likewise displayed t...

Страница 30: ...xactly the same length as the parameter data to be written In this example index 0x4E subindex 0 value 0x02 is written in Source Element Array Write In case of a configuration error the Destination El...

Страница 31: ...port 5 Process data inputs at IO Link port 5 296 343 IO Link port 6 Process data inputs at IO Link port 6 344 391 IO Link port 7 Process data inputs at IO Link port 7 Standard Input Data BNI EIP 508...

Страница 32: ...n failed PDI Process data invalid 42 Vendor ID 1 Vendor ID 43 Vendor ID 2 44 Device ID 1 Device ID 45 Device ID 2 46 Device ID 3 47 Mode Type 0 Event 1 Mode 0 Reserved 1 Event single shot 2 Event disa...

Страница 33: ...IO Link port 5 Process data output at IO Link port 5 198 229 IO Link port 6 Process data output at IO Link port 6 230 261 IO Link port 7 Process data output at IO Link port 7 Standard Output Data BNI...

Страница 34: ...e module has been correctly integrated into your network In addition the IP subnet of the BNI module must be accessible from the PC on which the browser is running Please use Internet Explorer 10 or n...

Страница 35: ...bar is located in the upper area of the window which allows you to switch between the various dialogs of the web interface To do this click on the corresponding icon When the Info tab is selected the...

Страница 36: ...XXXX BNIPNT BNI EIP XXX XXX XXXX BNIEIP BNI ECT XXX XXX XXXX BNIECT The password cannot be changed After successful login the dialog is as follows Use the Logout button to log out again After 5 minut...

Страница 37: ...troller PLC Information is also shown about the current process data and the status of the module via the corresponding LEDs After selecting LED Legend a Help dialog appears which explains the meaning...

Страница 38: ...www balluff com 37 8 Web Server PNT EIP...

Страница 39: ...s an IO Link port No appropriate IODD uploaded It is possible to read and write the configuration parameters of the IO Link device via the Parameters option The parameter indexes and subindexes of the...

Страница 40: ...and Parameters is not displayed but rather an expanded dialog Information from the IODD of the device is used so that the data can be better understood Thus in the following screenshot not only are t...

Страница 41: ...ed in three different modes These modes can be set using an IO Link parameter The parameter values and associated texts are stored in the IODD This means Operation Mode can be read out and displayed R...

Страница 42: ...tricted name length Since IODD files are generally published with a long file name these must be renamed and given a shorter naming scheme on the PC before uploading to the fieldbus module For this a...

Страница 43: ...er 8 7 Config dialog The configuration page enables configuration of the module You can change both the module information texts and the port configuration The Set Ports action is not permanently stor...

Страница 44: ...nd permanently stored in the device The Reboot button reboots the device as if the power to the module had been turned off and on again Clicking on Factory Reset deletes the configuration and log file...

Страница 45: ...ogging function The upper table see screenshot below contains important information for all service inquiries Note If you have a detailed question about a specific situation send us a screenshot of th...

Страница 46: ...rom the outside The system may require troubleshooting Event Informational Notice The fieldbus module has detected an important normal operating event and reports it These may include for example conf...

Страница 47: ...master module 8 IO Link ports Variants 005 2 Port Switch Mechanical Version E002 Stainless steel housing V4A Data transmission 2 x M12x1 internal thread Power supply 7 8 external thread 7 8 internal t...

Страница 48: ...www balluff com Balluff GmbH Schurwaldstrasse 9 D 73765 Neuhausen a d F Germany Tel 49 7158 173 0 Fax 49 7158 5010 balluff balluff de No 931925 726 E 04 127057 Edition H18 Replaces Edition H17 Subject...

Отзывы: