Balluff Network Interface EtherNet/IP™
www.balluff.com
30
7
Process Data
7.1. Process Data
Inputs
The input data size is 392 bytes. Take a look at the tables below for the allocation of the
process data inputs.
BNI EIP-508-005-E002
Byte
Module part
Description
0…7
Standard I/O ports
Process data inputs at the standard inputs
8…55
IO-Link Port 0
Process data inputs at IO-Link port 0
56…103
IO-Link port 1
Process data inputs at IO-Link port 1
104…151
IO-Link port 2
Process data inputs at IO-Link port 2
152…199
IO-Link port 3
Process data inputs at IO-Link port 3
200…247
IO-Link port 4
Process data inputs at IO-Link port 4
248…295
IO-Link port 5
Process data inputs at IO-Link port 5
296…343
IO-Link port 6
Process data inputs at IO-Link port 6
344…391
IO-Link port 7
Process data inputs at IO-Link port 7
Standard Input
Data
BNI EIP-508-005-E002
Byt
e
Bit
Description
7
6
5
4
3
2
1
0
0
I32
I34
I22
I24
I12
I14
I02
I04
Input data
I04
Input at port 0, pin 4
The result is 0 only if the port is
configured as an IO-Link port.
1
I72
I74
I62
I64
I52
I54
I42
I44
2
S3
S2
S1
S0
Short-circuit status
Short-circuit between pin 1 and 3
at the registered port
3
S7
S6
S5
S4
4
O32
O34
O22
O24
O12
O14
O02
O04
Overload status
O04
Overload at port 0, pin 4
Only if the port is configured as an
output.
5
O72
O74
O62
O64
O52
O54
O42
O44
6
0
0
0
0
0
NA
PS
PA
Status of the power supply
NV: No actuator power supply
PS: Power supply for sensor
PA: Power supply for actuator
7
0
0
0
0
0
0
0
0
Reserved