27
27
english
Simultan
eous
class:
64
Hex
instance: 01
Hex
attribute: 70
Hex
Factory setting:
Disable
(= 0)
Read/write jobs and data transmission on DeviceNet take
place in succession.
Other settings:
Enable
(= 1)
Read/write jobs and data transmission on DeviceNet take
palce simultaneously.
See description of the Simultaneous Data Transmission
function on 45.
Parameter 21
Simultaneous data
transmission
Function Description
Parametering the BIS C-60_3 processor
C60_3-025_825645_1310_e.p65
28
english
28
Buffer_Ready
class:
64
Hex
instance: 01
Hex
attribute: 71
Hex
Factory setting:
Not ready
(= 0)
With this parameter the BIS C-60_3 Processor signals that
the settings for the buffer sizes should now be applied.
Other settings:
Ready
(= 1)
Please note that the settings for the parameters
Buffer_Length,
Buffer_Length_Head1, Input length 1, Output length 1,
Input length 2, Output length 2
are not applied by the
BIS C-60_3 Processor until the parameter
Buffer_Ready
with
Ready
(=1) has been sent.
For explanations of buffer sizes, see 32 ff.
When the parameter
Buffer_Ready
with
Ready
(=1) is sent, the BIS C-60_3 Processor checks
whether the setting is valid. If yes, the new settings are applied. Otherwise the parameter
setting is rejected with
„Invalid attribute value“
.
After checking the buffer settings, the value from
Buffer_Ready
is automatically reset by the
BIS C-60_3 Processor to
Not ready
(= 0).
☞
Parameter 22
Apply buffer setting
Function Description
Parametering the BIS C-60_3 processor
☞
☞