Function Description
Parametering the BIS C-60_3 processor
Parameter 17
Mode 2:
No. of bytes to read
Head 2
☞
Input length 2
class:
65
Hex
instance: 01
Hex
attribute: 6B
Hex
Factory setting:
31 byte
Other settings:
2 byte ....
(Buffer_Length – Input length 1 – 2) byte
This setting specifies how many bytes should be read from
the data carrier in BIS Mode 2 on Head 2.
Please note when setting this parameter the explanation of
the in- and output buffers starting on 32.
Input address 2
class:
65
Hex
instance: 01
Hex
attribute: 6C
Hex
Factory setting:
Start address 0
Other settings:
1 ... 8191
This setting specifies the starting address for reading data
carriers in BIS Mode 2 on Head 2.
Parameter 18
Mode 2:
Start address for
reading, Head 2
C60_3-025_825645_1310_e.p65
26
english
26
Function Description
Parametering the BIS C-60_3 processor
Parameter 19
Mode 2:
No. of bytes for
writing Head 2
☞
Output length 2
class:
65
Hex
instance: 01
Hex
attribute: 6E
Hex
Factory setting:
31 bytes
Other settings:
2 bytes ....
(Buffer_Length – Output length 2 – 2) bytes
This setting specifies how many bytes should be written to
the data carrier in BIS Mode 2 on Head 2.
Please note when setting this parameter the explanation of
the in- and output buffers starting on 32.
Output address 2
class:
65
Hex
instance: 01
Hex
attribute: 6F
Hex
Factory setting:
Start address 0
Other settings:
1...8191
This setting specifies at which start address the data carrier
on Head 2 should be written to in BIS Mode 2.
Parameter 20
Mode 2:
Start address for
writing Head 2