![Baldor ID15J101-ER Скачать руководство пользователя страница 43](http://html1.mh-extra.com/html/baldor/id15j101-er/id15j101-er_installation-and-operating-manual_468788043.webp)
4-6 Programming and Operation
MN715J
Display Screens
Action
Description
Display
Apply Power
Display of mode & drive status.
Press DISP key
The fault log block.
Press DISP key
The diagnostic information block.
Press DISP key
The modified parameters block.
Press DISP key
Display of output frequency.
Press DISP key
Display of motor speed (based on
output frequency).
Press DISP key
Display of motor current.
Press DISP key
Display of motor voltage.
Fault Log Access
When a fault condition occurs, motor operation stops and a fault code is
displayed on the Keypad display. The control keeps a log of the last 31 faults.
If more than 31 faults have occurred the oldest fault will be deleted from the
fault log to make room for the newest fault. To access the fault log perform the
following procedure:
Action
Description
Display
Apply Power
Display of mode & drive status.
Press DISP key
Press DISP to scroll to the Fault
Log entry point.
Press ENTER key
Display first fault type and time
fault occurred.
Press
Y
key
Scroll through fault messages to
the end.
Press RESET key
Return to display mode.
Содержание ID15J101-ER
Страница 1: ...Series 15J Inverter Control 7 04 MN715J Installation and Operating Manual ...
Страница 5: ...iv Table of Contents MN715J ...
Страница 11: ...2 4 General Information MN715J ...
Страница 59: ...4 22 Programming and Operation MN715J ...
Страница 75: ...6 6 Specifications and Product Data MN715J ...
Страница 79: ...A 4 Dynamic Brake Hardware MN715J ...
Страница 86: ...Appendix C Remote Keypad Mounting Template MN715J Remote Keypad Mounting Template C 1 ...