3-14 Receiving and Installation
MN715J
Analog Output
One programmable analog output is provided at J4-10 and J4-9. The output
is scaled 0 - 5 VDC, 0 - 10 VDC, 4-20mA or 0-20mA. The output function is
programmed in the Level 1 Output block, Analog Out parameter value. The
scaling of the output is programmed in the Level 1 Output block, Analog
Scale.
Relay Outputs
One normally open (N.O.) and one normally closed (N.C.) relay contact is
available at terminals J4-1, J4-2 and J4-3. J4-2 is relay common. The output
is programmable in the Level 1 Output block, Relay Output parameter.
1.
Connect the N.O. contact to another circuit by attaching the wires to J4-1
and J4-2.
2.
Connect the N.C. contact to another circuit by attaching the wires to J4-3
and J4-2.
External Trip Input
Terminal J4-17 is available for connection to a normally closed thermostat or
overload relay in some operating modes as shown in Figure 3-9. The
thermostat or overload relay should be a dry contact type with no power
available from the contact. If the motor thermostat or overload relay activates,
the control will automatically shut down and give an external trip fault.
The optional relay (CR1) shown provides the isolation required. The N.O.
contact is closed when power is applied to the relay and the motor is cold.
Connect the external trip input wires to J4-17 and J4-18. Do not place these
wires in the same conduit as the motor power leads.
To activate the external trip input, the external trip parameter in the Level 2
Protection Block must be set to “ON”.
Figure 3-9 External Trip Input Connection
T1
T2
T3
T1
T2 T3 G
*
Motor
17
18
J4
Do not run these wires in
same conduit as motor leads
or AC power wiring.
Customer supplied
source voltage
Motor Thermostat Leads
CR1
*
*
Optional hardware. Must be ordered separately.
See recommended terminal tightening torque in section 6.
Note: Add appropriately rated protective device
for AC relay (snubber) or DC relay (diode).
External or remote motor overload
protection may be required by National
Electrical Code or equivalent
Содержание ID15J101-ER
Страница 1: ...Series 15J Inverter Control 7 04 MN715J Installation and Operating Manual ...
Страница 5: ...iv Table of Contents MN715J ...
Страница 11: ...2 4 General Information MN715J ...
Страница 59: ...4 22 Programming and Operation MN715J ...
Страница 75: ...6 6 Specifications and Product Data MN715J ...
Страница 79: ...A 4 Dynamic Brake Hardware MN715J ...
Страница 86: ...Appendix C Remote Keypad Mounting Template MN715J Remote Keypad Mounting Template C 1 ...