3-24 Receiving and Installation
MN715J
EPOT 2 Wire Connection
Figure 3-18 Electronic POT 2 Wire Connection Diagram
11
12
13
14
15
16
17
18
Forward
Reverse
EPOT/CMD Select
Accel/Decel Select
Increase
Decrease
External Trip
Input Common
Refer to Figure 3Ć9.
J4
See recommended terminal
tightening torques in Section 6.
J4-11
OPEN motor decels to stop (depending on Keypad Stop mode).
CLOSED to enable operation in the Forward direction.
J4-12
OPEN motor decels to stop (depending on Keypad Stop mode).
CLOSED to enable operation in the Reverse direction.
J4-13
OPEN for normal speed mode. Terminal strip speed source is selected in the
Level 1 Input block, ANA CMD Select parameter.
CLOSED to enable the Electronic Potentiometer Mode.
J4-14
OPEN selects ACC / DEC / S-CURVE group 1.
CLOSED selects group 2.
J4-15
Momentary CLOSED increases motor speed while closed.
J4-16
Momentary CLOSED decreases motor speed while closed.
J4-17
If J4-17 is connected, you must set Level 2 Protection block, External Trip to
“ON” to activate the opto input.
OPEN causes an external trip fault. The control will disable and the motor
coasts to a stop. An external trip fault is displayed (also logged in the fault log).
CLOSED allows normal operation.
Содержание ID15J101-ER
Страница 1: ...Series 15J Inverter Control 7 04 MN715J Installation and Operating Manual ...
Страница 5: ...iv Table of Contents MN715J ...
Страница 11: ...2 4 General Information MN715J ...
Страница 59: ...4 22 Programming and Operation MN715J ...
Страница 75: ...6 6 Specifications and Product Data MN715J ...
Страница 79: ...A 4 Dynamic Brake Hardware MN715J ...
Страница 86: ...Appendix C Remote Keypad Mounting Template MN715J Remote Keypad Mounting Template C 1 ...