The factory preset is Remote On. Pressing the Stop Key (if programmed active) while in remote
control automatically selects LOCAL mode of operation to prevent a restart command.
Keypad Stop Mode
- Selects if the motor will "coast" or "regen" to a stop. In the coast mode
power to the motor will be turned off and the motor will coast to a stop. In the regen mode, the
motor will be decelerated to a stop within the time specified in the DECEL TIME parameter.
NOTE:
IN THE REGEN MODE THERE IS A POSSIBILITY OF CAUSING AN OVER
VOLTAGE TRIP CAUSED BY DECELERATING THE MOTOR AT A RATE
FASTER THAN IT WOULD COAST TO A STOP. UNDER THESE CONDITIONS,
THE MOTOR GENERATES POWER BACK INTO THE CONTROL. IF A FAULT
IS EXPERIENCED, INCREASE THE DECEL TIME PARAMETER. IF A FAULT
STILL EXISTS AT THE MAXIMUM DECEL TIME ALLOWABLE IN YOUR
APPLICATION, AN OPTIONAL EXTERNAL DYNAMIC BRAKING KIT OR
ASSEMBLY IS REQUIRED.
Keypad Run FWD
-
Enables or disables the FWD key during LOCAL operation. The choice is
ON or OFF.
Keypad Run REV
-
Enables or disables the REV key during LOCAL operation. The choice is
ON or OFF.
Keypad Jog FWD
-
Enables or disables the "FWD" key during a LOCAL jog operation. The
choice is ON or OFF.
Keypad Jog REV
-
Enables or disables the REV key during a LOCAL jog operation. The
choice is ON or OFF.
Input Block
Operating Mode
- Selects the basic operation of the control including functions of the input and
output terminals on the J1 terminal strip. The Series 23H control has several modes of operation to
suit various application requirements. Please refer to the servo control connection diagrams to
determine which operating mode is right for your application. The choices from which you can select
are: Keypad (only), Standard Run, 15 speed, Bipolar, Process and Serial. The factory preset is
Keypad.
Command Select
- Selects and scales the type of external speed reference command you input to
the control. The possible values are Potentiometer, +/- 10 vdc, +/- 5 vdc, 4-2OmA, 10 volt W/EXT
CL (with differential command present at J1-4 and J1-5 this selection allows additional input at J1-1,
2, and 3 which allows reduction in programmed current limit for torque trimming during operation),
10Volt W/TORQ FF (with differential command at J1-4 and J1-5 this selection allows additional
torque feedforward input at J1-1, 2, and 3 to set predetermined amount of torque inside the rate
loop with high gain settings), EXB PULSE FOL (pulse follower expansion board), 10Volt EXB (high
resolution expansion board), 3-15PSI (expansion board), Tachometer (expansion board), Serial
Communication (expansion board), Fixed parameter (process mode), or none. The factory preset is
+/- 10 vdc.
3-8
KEYPAD PROGRAMMING AND OPERATION
MN723H-10/95 11/28/95 1:11 AM Page 62 (Black plate)
Содержание 23H Series
Страница 11: ...1 8 GENERAL INFORMATION MN723H 10 95 11 28 95 1 07 AM Page 12 Black plate...
Страница 83: ...3 30 KEYPAD PROGRAMMING AND OPERATION MN723H 10 95 11 28 95 1 13 AM Page 84 Black plate...
Страница 99: ...4 16 DIAGNOSTIC INFO AND TROUBLESHOOTING MN723H 10 95 11 28 95 1 14 AM Page 100 Black plate...
Страница 125: ...5 26 APPENDIX G MN723H 10 95 11 28 95 1 21 AM Page 126 Black plate...
Страница 126: ...MN723H 10 95 11 28 95 1 21 AM Page 127 Black plate...