Appendix E
Short Circuit Current Ratings
CAUTION: SERIES 23H CONTROLS FEATURE UL APPROVED ADJUSTABLE MOTOR
OVERLOAD PROTECTION SUITABLE FOR MOTORS NO LESS THAN 50%
OF THE OUTPUT RATING OF THE CONTROL. OTHER GOVERNING
AGENCIES SUCH AS NEC MAY REQUIRE SEPARATE OVER-CURRENT
PROTECTION. THE INSTALLER OF THIS EQUIPMENT IS RESPONSIBLE
FOR COMPLYING WITH THE NATIONAL ELECTRIC CODE AND ANY
APPLICABLE LOCAL CODES WHICH GOVERN SUCH PRACTICES AS
WIRING
PROTECTION, GROUNDING, DISCONNECTS AND OTHER
CURRENT PROTECTION.
MAXIMUM LINE SHORT CIRCUIT CURRENT MUST NOT EXCEED VALUES
IN THE TABLES BELOW. BALDOR STOCKS 3% LINE REACTORS WHICH
WILL ALLOW THIS REQUIREMENT TO BE MET ON LINES WITH HIGHER
SHORT CIRCUIT CURRENT. DAMAGE TO THE CONTROL MAY OCCUR
WHEN CONNECTED TO LINES EXCEEDING THESE LIMITS.
Series 23H Stock Products
Electrical Rating:
Maximum Input/Output Voltage: 200-230 VAC, 50/60Hz
3 ph.
230 VAC Catalog Nos.
Maximum Line Short
Circuit Current Amperes
SD23H2A03-E
250
SD23H2A04-E
350
SD23H2A07-E
550
SD23H2A10-E
550
SD23H2A15-E
1000
SD23H2A22-E
1000
SD23H2A30-ER
1900
SD23H2A45-ER
2400
SD23H2A55-ER
2800
5-8
APPENDIX E
MN723H-10/95 11/28/95 1:19 AM Page 108 (Black plate)
Содержание 23H Series
Страница 11: ...1 8 GENERAL INFORMATION MN723H 10 95 11 28 95 1 07 AM Page 12 Black plate...
Страница 83: ...3 30 KEYPAD PROGRAMMING AND OPERATION MN723H 10 95 11 28 95 1 13 AM Page 84 Black plate...
Страница 99: ...4 16 DIAGNOSTIC INFO AND TROUBLESHOOTING MN723H 10 95 11 28 95 1 14 AM Page 100 Black plate...
Страница 125: ...5 26 APPENDIX G MN723H 10 95 11 28 95 1 21 AM Page 126 Black plate...
Страница 126: ...MN723H 10 95 11 28 95 1 21 AM Page 127 Black plate...