Wiring and Protective Devices
This control must be provided with a suitable input power protection device. Use the recommended
fuses or circuit breaker listed in Tables which follow. Input and output wire size is based on the use of
75 degree C rated copper conductor wire. The table is specified for NEMA B motors.
Circuit Breaker
3 phase, thermal magnetic. Equal to GE type THQ or
TEB for 230 VAC or GE type TED for 460 VAC.
Fast Action Fuses
Buss KTN on 230 VAC, Buss KTS on 460 VAC or equivalent.
Time Delay Fuses
Buss FRN on 230 VAC or Buss FRS on 460 VAC or equivalent.