INICT01 INFI-NET TO COMPUTER TRANSFER MODULE
INTRODUCTION
F - 2
I-E96-427B
®
4
0
Port 2 option serial port to host.
1
Port 2 utility option. If this option is selected, port 1 data characteristics are auto-
matically set to 8 data bits, 1 stop bit, no parity. Otherwise, port 2 data characteris-
tics are set by dipswitch positions 2 and 3.
5
0
Modem password protection disabled.
1
Modem password protection enabled.
6
0
Port addressing mode disabled.
1
Port addressing mode enabled. When this option is enabled,, the ICT module will
expect all commands from the host to send the port address configured through the
UTILITIES as the first character of each command.
7
0
Checksumming option disabled.
1
Checksumming option enabled. When this option is enabled,, the ICT module will
expect all commands from the host to include a checksum byte as the last charac-
ter before the carriage return. The ICT module includes a checksum in each reply.
8
N/A
Not used.
NOTE: 0 = CLOSED or ON, 1 = OPEN or OFF.
Table F-2. INICT01 Dipswitch U73 Baud Rate Settings
Baud
Rate
Switch Position
Baud
Rate
Switch Position
Terminal Port 1
1 2 3 4
Printer Port 2
5 6 7 8
Terminal Port 1
1 2 3 4
Printer Port 2
5 6 7 8
50.0
0
0
0
0
0
0
0
0
1800.0
0
0
0
1
0
0
0
1
75.0
1
0
0
0
1
0
0
0
2000.0
1
0
0
1
1
0
0
1
110.0
0
1
0
0
0
1
0
0
2400.0
0
0
0
0
0
1
0
1
134.5
1
1
0
0
1
1
0
0
3600.0
1
1
0
1
1
1
0
1
150.0
0
0
1
0
0
0
1
0
4800.0
0
0
1
1
0
0
1
1
300.0
1
0
1
0
1
0
1
0
7200.0
1
0
1
1
1
0
1
1
600.0
0
1
1
0
0
1
1
0
9600.0
0
1
1
1
0
1
1
1
1200.0
1
1
1
0
1
1
1
0
19200.0
1
1
1
1
1
1
1
1
NOTE: 0 = CLOSED or ON, 1 = OPEN or OFF.
Table F-1. INICT01 Dipswitch U72 Option Settings
(continued)
Position
Setting
Function