INPPT01 PLANT LOOP TO PLANT LOOP TRANSFER MODULE
INTRODUCTION
D - 2
I-E96-427B
®
3
0
Equipment select output de-energized.
1
Equipment select output energized. A unique equipment select output can exist
between the primary and secondary PPT module. The equipment select output is
digital output 3 of a digital slave (IMDSM05 or IMDSO01/02/03/04 module).
4
0
Port 2 option interface communication.
1
Port 2 utility option. Port 2 responds as DCE when it is configured as a utility port.
Set switch position 4 = 1 if port 2 is not used as a communication interface.
5
0
Interface ID local. Define only one interface as a local interface.
1
Interface ID remote.
6
0
Interface mode two-way control. The following conditions apply:
1. The port 2 option defaults to interface communication (position 4 = 0).
2. The local INPPR01 interface uses port 1 as its command port and port 2 as its
reply port.
3. The remote INPPR01 interface uses port 2 as its command port and port1 as its
reply port.
4. Both the local and remote interface must have a loop address of 0 (U75).
1
Interface mode one-way control.
7
0
Do not initialize NVRAM.
1
Initialize NVRAM.
8
0
Primary module.
1
Redundant module.
NOTE: 0 = CLOSED or ON, 1 = OPEN or OFF.
Table D-2. INPPT01 Dipswitch U73 Baud Rate Settings
Baud
Rate
Switch Position
Baud
Rate
Switch Position
Terminal Port 1
1 2 3 4
Printer Port 2
5 6 7 8
Terminal Port 1
1 2 3 4
Printer Port 2
5 6 7 8
50.0
0
0
0
0
0
0
0
0
1800.0
0
0
0
1
0
0
0
1
75.0
1
0
0
0
1
0
0
0
2000.0
1
0
0
1
1
0
0
1
110.0
0
1
0
0
0
1
0
0
2400.0
0
0
0
0
0
1
0
1
134.5
1
1
0
0
1
1
0
0
3600.0
1
1
0
1
1
1
0
1
150.0
0
0
1
0
0
0
1
0
4800.0
0
0
1
1
0
0
1
1
300.0
1
0
1
0
1
0
1
0
7200.0
1
0
1
1
1
0
1
1
600.0
0
1
1
0
0
1
1
0
9600.0
0
1
1
1
0
1
1
1
1200.0
1
1
1
0
1
1
1
0
19200.0
1
1
1
1
1
1
1
1
NOTE: 0 = CLOSED or ON, 1 = OPEN or OFF.
Table D-1. INPPT01 Dipswitch U72 Option Settings
(continued)
Position
Setting
Function