INTRODUCTION
SPECIFICATIONS
1 - 6
I-E96-427B
®
SPECIFICATIONS
Refer to Table
for the specifications of the NTMF01 termi-
nation unit.
INPPT01
Plant Loop to Plant Loop transfer module
NDCS03
Digital control station
NFTP01
Field termination panel
NKSE01
Station serial extension cable (PVC)
NKSE11
Station serial extension cable (non-PVC)
NKTU01
Termination unit cable (PVC)
NKTU11
Termination unit cable (non-PVC)
NTCS04
Control/station termination unit
Table 1-3. Nomenclature
(continued)
Nomenclature
Description
Table 1-4. NTMF01 Termination Unit Specifications
Property
Characteristic/Value
Power Requirements
+24 VDC
160 mA current consumption,, maximum (LED consumes 10 mA)
Communication
2 RS-232-C serial ports
1 control station serial link
Cable Insulation
Specifications:
PVC (UL Rating CL2)
Non-PVC (UL Rating PLTC)
80°C (176°F) at 300 V|
90°C (194°F) at 300 V
Mounting
Screw mounts on the field termination panel
Environmental
Electromagnetic/Radio
Frequency Interference
Values are not available at this time. Keep cabinet doors closed. Do not use
communication equipment any closer than 2 meters from the cabinet.
Operating Temperature
0° to 70°C (32° to 158°F)
Relative Humidity
5% to 90% (±5%) up to 70°C (158°F) (noncondensing)
Altitude
Sea level to 3 km (1.86 mi)
Air Quality
Bailey equipment should be operated and stored in a noncorrosive environ-
ment.
Cooling Requirements
No cooling necessary when used in Bailey cabinets and operated within
stated environmental limits.
Certification
All termination units are CSA certified as process control equipment for use
in an ordinary (nonhazardous) location.
SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE.