![Bailey infi 90 Modular Power System II Скачать руководство пользователя страница 39](http://html1.mh-extra.com/html/bailey/infi-90-modular-power-system-ii/infi-90-modular-power-system-ii_instruction_3468074039.webp)
INTRODUCTION
I-E96-427B
B - 1
APPENDIX B - IMMFC04 MULTI-FUNCTION CONTROLLER
INTRODUCTION
Several dipswitches must be set for the IMMFC04 Multi-Func-
tion Controller. Figure
shows the IMMFC04 module layout.
Tables
,
explain the dipswitch settings for the
board. For more information on the module, refer to the
IMMFC04 Multi-Function Controller Module
product
instruction.
NOTE:
Jumpers J17 through J22 are factory set (jumper pins one
and two) and should not be changed. Jumpers J23 and J24 are
reserved for future use. The positions of J23 and J24 do not affect
module operation.
Figure B-1. IMMFC04 Module Layout
T00022B
P1
P2
P3
STATUS
LED
GROUP
LEDS
XU39
XU40
SW4
OPTIONS
SW3
MODULE ADDRESS
STOP
RESET
1 2 3 4
OPEN
5 6 7 8
1 2 3 4
OPEN
5 6 7 8
J23
1
1
3
2
J24
1
1
3
2
J19
1
3
2
J17
1
3
2
J18
1
3
2
J20
1
3
2
J21
1
3
2
J22
1
3
2
Table B-1. IMMFC04 Dipswitch SW3 Module Address Settings
Address Example
Dipswitch Position
(Binary Value)
1
1
2
2
3
3
4
5
6
7
8
(128)
(64)
(32)
(16)
(8)
(4)
(2)
(1)
7
1
Y
X
0
0
1
1
1
15
1
Y
X
0
1
1
1
1
31
1
Y
X
1
1
1
1
1
NOTE: 0 = CLOSED or ON, 1 = OPEN or OFF.
1. Position 1 must be set open for proper operation.
2. Y = 0 for normal execution mode, 1 for diagnostic mode.
3. X= Not important.