![Bailey infi 90 Modular Power System II Скачать руководство пользователя страница 37](http://html1.mh-extra.com/html/bailey/infi-90-modular-power-system-ii/infi-90-modular-power-system-ii_instruction_3468074037.webp)
IMMFC03 MULTI-FUNCTION CONTROLLER
INTRODUCTION
A - 2
I-E96-427B
®
6
0
Normal operation.
1
Compact configuration - moves configured blocks to the top of NVRAM
while moving free space to the bottom (this is known as compacting).
Leave switch OPEN and insert module into MMU. When front panel
LEDs 1,, 2 and 4 are ON,, remove the module,, put the switch in the
CLOSED position and insert the module. The MFC goes into the con-
figure mode and compacts the configuration.
7
0
Normal operation.
1
Initialize NVRAM (erase configuration) - leave switch OPEN and insert
the module into the MMU. When front panel LEDs 1,, 2 and 4 are ON,,
remove the module,, put the switch in the CLOSED position and insert
the module. The module is now ready to be configured. This switch
must be CLOSED for normal operation.
8
0
Primary MFC module.
1
Redundant MFC module.
NOTE: 0 = CLOSED or ON, 1 = OPEN or OFF.
Table A-2. IMMFC03 Dipswitch U72 Special Operation Settings
Special
Operation
Dipswitch Position
1 2 3 4 5 6 7 8
Description
0
0
0
0
0
0
0
0
0
Force module to configure mode.
1
1
0
0
0
0
0
0
1
Reserved for future use. If you use this setting,, your
module may not operate properly.
2
1
0
0
0
0
0
1
0
Initialize NVRAM configuration space.
3
1
0
0
0
0
0
1
1
Reserved. Do not use. If you use this setting,, your
module may not operate properly.
4
1
0
0
0
0
1
0
0
INFI-NET protocol enable. This allows the MFC mod-
ule to take advantage of INFI-NET/<R> Superloop
capabilities.
5
1
1
0
1
0
0
0 0
Permit segment modification (allows change to seg-
ment scheme configured with function code<N>82,,
specification S1).
6
1
0
1
1
0
0
0
0
Enable time-stamping. This operation instructs the
MFC to generate time information with point data. It
is applicable only to INFI-NET/ Superloop systems.
NOTE: 0 = CLOSED or ON, 1 = OPEN or OFF.
Table A-1. IMMFC03 Dipswitch U72 Option Settings
(continued)
Position
Setting
Function